A/c help Installed a new 2.0 ton 13 seer condenser and can not get the contactor to ingauge i have 240 on line side and 240 on load side when i push the pins down and the unit starts, i have 24v at the t-stat going in the contactor but it will not close, and i switched it out and the same thing happens, i checked the transformer and t-stat and all checks out good. why is the contactor not closing when it is calling for it?


Answers :

Do you have 24volts at the contactor when the T-stat. is set to cool or heat if unit is a heat pump? The outside unit must have 24v at the contactor to engage

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

A/c help Installed a new 2.0 ton 13 seer condenser and can not get the contactor to ingauge i have 240 on line side and 240 on load side when i push the pins down and the unit starts, i have 24v at the t-stat going in the contactor but it will not close, and i switched it out and the same thing happens, i checked the transformer and t-stat and all checks out good. why is the contactor not closing when it is calling for it?


Do you have 24volts at the contactor when the T-stat. is set to cool or heat if unit is a heat pump? The outside unit must have 24v at the contactor to engage ... Hitachi RAS-09UH Air Conditioner

On my goodman ssz160481ab heat pump. When going into either heat or cool mode the contactor won't hold. its as if the coil voltage is going on and of very fast causing the contacts to burn out. I replaced the contactor beacause it was so badly burned and found that the thermostat was bad too and replaced it. However it is still doing the same thing. I am getting a full 28v from the transformer, but get a weird reading at the contactor coil, 18vac and 8 v dc. could it be a bad circuit board?


Disconnect the yellow Y1 wire from the thermostat to the control board in the air handling unit and read the voltage from C - common to the yellow wire. It should be 24 VAC, 0 VDC. If it is, cconnect the wire back to the control board. Now, discon ... Air Conditioners

When the thermostat turns off, the condensing unit continues to run. The old contactor was sticking. I could go out and tap on the side of the electrical box beside the compressor, and the contactor would drop out, allowing the unit to shut down. I have replaced the run contactor, but the problem has not gone away. In fact tapping on the electrical box won't even make it shut down now.


You most likely have a short. Start by removing the wire on the terminal marked y in the t- stat then see if it shuts down. Look in the air handler for wires touching together. I have also eound wires touching in the wall from the t-stat. ... Carrier 38CKC042 Air Conditioner

On evcon split system the wireing digram shows low voltage therm wires going to the same side on contactor. i thought the red came off the right side and the black came off the left?


Hello,The LOW voltage wires go on the 1/4" spade connectors and can be on one side or one on each side(in the middle) depending on what brand contactor you have.Red & black sound like line voltage.Common & Y should not matter(witch way) when you get ... Ruud UAMB Air Conditioner

This is a weatherking central air conditioner. Had been looked at by another person before me. Wasn't cooling right is all the information I had. When I walked past it one day (this is at a golf course), I noticed the suction line going into the condenser cabinet was iced up. First thing I thought about was maybe it had to much freon in it. After looking into it further I noticed it was iced up all the way to the compressor. When I had a person turn the t-stat down to turn down, the head pressur


Sounds like the compressor is tripping it's thermal safety. You say you turned the thermostat off and your head pressure climbed? I would check the contactor for stuck points that are leaving the compressor running continuously. BTW, you should have ... Weather King 10AJA3601AH Air Conditioner

I have a 2000 chevy blazer 4 wd. the ac does not work. We bought a recharge it from advanced auto and checked how much freon was in the truck. It was reading low, so we added some to the specifications given on the package. However, the air still blows out really hot. The thing under the hood that has a belt around it for the ac cuts on and off quite frequently. When we were measuring the freon, as it cut on and off the levels we were reading would go from 55 psi to 0 back up to 55. We live in F


Hi Florida, sounds like you have a leak in the system some where. This is called short cycling on the low pressure switch, on off, on off. I am surprised that the charge you added did not do the trick. A normal charge is around 22oz. give or take. Th ... Air Conditioners

The ptac unit is not heating or cooling the aux heat works the line out of the compressor gets hot but the line going to the coils up front does not get real hot just warm and does the same thing on the cooling side does get cold can not figure it out can anybody help


Verify all your components are operating - Compressor? Condenser fan motor? Blower fan motor?\015\012If not check voltage to any that are not operating.\015\012If all components are operating and the coils are clean - the refrigerant leve ... Amana PTH153B50AJ Heat Pump Air Conditioner

Shut unit down for cleaning, outside unit will not start now, I have line voltage at the contactor but the contactor will not engage.one wire from the thermostat runs to a little black box next to the contactor (white) the red one runs to a device down by the dryer on one side and back to the black box on the other side. Both of these wires come out of the box and attach to either side of the contactor.Could this piece be the problem or is it the black box.If I manually engage the contactor the


You are talking about the low voltage transformer ... Ruud Handle Air Conditioner

Hi, i have 07 dodge nitro 3.7 with a/c system no cool enough, i change a/c comp,a/c condeser. evaporator and sxpation valve. the gage reding 40psi low side and 250psi hi side temp 55 gd. whent turn on a/c the hi press go to400psi, leitor go to 250. whent i put engine 1500rpm the hi side go 400psi or moor .what think hapen?


... Air Conditioners

1 Solution for "i have a 1976 after market auto air conditioner The inside swithces are hooked up all but one solid brass wire/cable it has to white wire coming out side to side one going to the other switch and one going to the blower The third solid copper/brass is coming out of side and at the end it looks like it should be stuch in something Where


NEED EXACT INFOMATION, MODEL NUMBER AND CAR IT IS INSTALLED IN TO GIVE 100% RELIABLE INFO. BUT BASED ON WHAT U ARE SAYING THIS IS THE AC EVAPORATOR CORE THERMAL PROBE, THE EVAPORATOR CORE IS WHAT COOLS THE AIR STREAM IT IS LOCATED INSIDE THE DUCT WOR ... Air Conditioners

I have a split system air conditioner. the inside fan turns on fine but the out door will not. i pushed the contactor in (located at the outdoor fan)that seems to turn on the fan. i measured the voltage with multimeter across the contact 24 volt side and got low voltage reading. then i disconnected the wires to the 24 volt side of the contactor and measured the wires, the wires read 24-27 volts. i dont know why when i connect it the readings are low. i even got a new contactor and still the same


Contactor working means fan might be bad can you feel any resistance from fan or bad capacitor. ... LG LSC091PMA Split System Air Conditioner

How to change 3 wire motor with 4 wire motor for outside ac unit fan motor?....old motor had blk wire going to a circuit board, also pur wire going to c terminal on cap, also brw wire going to f terminal on cap...... new motor , on the name plate , shows blk and wht wire going to line. also brw and brw/white stripe wires going to cap.... does the blk go to the same place as the old blk and the white does it go to the other line wire coming off the contactor? also which terminals do i attach t


You need this wire onto the "F"terminal- fan terminal as this is a 230 volt condenser fan motor all your doing is parrelling the cap ... Air Conditioners

I need to know the same thing as asked by Alan in Aug. I have a coleman thermostate 6703-340 and need to know which three wires go to which 3 termimals.Thank-you, Frank


... Coleman Mach 15 Air Conditioner

My ac unit does not have power to the thermostat. There is 200 volts going into the transformer and 24 volts going out. There is 24 volts on the back side of a terminal with thermostat wire running to the thermostat and the outside AC unit. However, no power on the front side of this terminal and therefor no power to the thermostat.


Please exercise due caution in checking voltages in live circuits!24 volts sourced by the transformer, through the thermostat, then through the contactor (turns on power to compressor/fan) and returns to the transformer, If the thermostat ... Air Conditioners

The system runs but both the high and low so pressure erratically go up and down. the low side does not go under 600kpa, the high side between 1500 and 2000kpa. the system is an lg ducted on R22 refrigerant


This can be caused by moisture in the system and when the moisture freezes on the capilliary tube you get a fluctuation, it the defrosts and passes through and again causes an up and down. Same would apply for excessive air in the system. You would h ... Air Conditioners

Replace contactor I have an ruud air conditioner model no UAMB-048JAZ . relpace contactor with a new part protech contactor part no 42-25101-01. Is this the correct part number? on top of the contactor the L1 L2 T1 7 T3 loction is not the same as the old contactor, when installind new cantactor wich wire go to L1 Lt ect. on new part


On single phase your incoming power lines go to L-1 & L-2, the lines to the compressor go to T-1 & T-2. With A/C current it does not matter which one goes to which side as long as the line goes to the L side and the compressor power lines go ... Ruud Central System Air Conditioner

1994 corolla-I charged the air cond., and it was cooling fine. After about a mo., it was not cooling very good. I assumed it had a small leak. I put my guages on it and the low pressure was running 15 to 20. The high side was reading about 150.I put a can of stopleak and detector in it. Then I put a can of freon in it. While I was putting the freon in it the pressure started to drop on both the low side and high side. Now the low side pressure is running about 15 and the high side is running 0.W


Hi\015\012\015\012\015\012Thanks for using FixYa. This has happened because of the low side pressure on your AC pump isn't kicking on, because when the pump is off, the pressures equal out and the low side shows a high ... Air Conditioners

CONTACTOR WIRING IAM REPLACING THE SAME CONTACTOR AS YOU HOWEVER, I'M REPLACING CONTACTOR WITH FASCO H140A AND AM NOT SURE WHERE THE L1 T1 SHOULD GO BECAUSE THERE ARE TWO PRONGS ONE ON LEFT AND ONE ON RIGHT. ANY CLUES YOU CAN SHARE?


Sorry but I could not find a picture of a Fasco h140a but L's are connected to line (supply) voltage and T's are connected to load (motor). C's are connected to your control voltage, usually the smaller sized wire. ... Ruud Central System Air Conditioner

I bought a Honeywell air purifier HPA-051. Pre-filter was in a plastic bag at the bottom of the box. The instruction manual is not very clear about the installation of it. I don't know where it should go. Should I install it inside the rear grille? The pre-filter has a black side and kind of a grey side. Which side should be facing the true HEPA filter? Thanks a lot for your help! Andrea


... Air Conditioners

My thermastate went out and i cant hook up the new one because it is not labled, and i need to know how i figure out what wires need to go to with letters (o/b, y, r, g, w). There is a plug with 10 wires ( there are colored ) that goes from the a/c unit to the thermostate, and seperate red and wite wires going to the thermostate. Also there was 12v power going to the other thermostat. The only thing the new thermostat has for hookups is o/b, y, r, g, w. can you help


Let me guess, you have a flat ribbon type harness coming from AC unit to thermostat, correct?Older Ac unit? What thermostat model came off, and what type are you trying to install? ... Dometic Rooftop RV Air Conditioner

On outside compressor for whole house AC: Critters ate wires. Have Blk & Red power in from breaker. 24vac switched from thermostat. 1 contactor with 24vac coil(original). 1 Capacitor w/ 3 terms labeled: C, fan, herm. compressor w/ 3 wires: #10 yel & blk, #14 red. fan w/ 3 # 18 wires: Blk, Orn, Blu. I need wiring. Here is what I think: All blacks connect together. Red power wire connects to contactor in. Fan orn & Compressor Yel go to contactor out. Capacitor is the problem. "C" marked terminal g


There should be a wiring diagram on the back of the access panel. If you can't read it, check online for model wiring diagram. Don't guess, you may cause more expensive damage. ... Air Conditioners

I have RUUD and just replaced the condensor fan motor with a 5 wire Protech....the old fan was wired with black connected to contactor, orange to one side of cap and brown to the other side of the cap.....The new motor is a five wire...I have black connected to the connector, orange to one side of cap and purple(to change direction of fan) instead of brown...now i have a yellow and brown wire left over....Now when I start the unit the fan will not spin unless i turn the fan blade manually....am


Look on the side of the motor it will have a wiring diagram your fan supplies voltage to the capacitor its self so two of your wires go to the capacitor not just one. good luck ... Air Conditioners

Upne-024jaz unit burnt contactor found comp. shorted replaced . vac. and charged unit found cap. tube broke at coil on cond. tvx repaired and recharged unit , found suction side pulling into vac. replaced tvx and recharged unit still pulling into vac. on low side and high side set app. 180 and doesn't move as unit runs. assume tvx at coil or rev. vale ?


There is lack of airflow across the coil due to not being CLEAN. Perhaps a dirty return air filter. Could even be slightly undercharged. Either way, the evaporator is operating below the freezing point of the atmospheric humidity.F ... Ruud UAPA024 Air Conditioner

Hvac i have a 2 ton goodman package unit. the ac side works great the heat side not so good.man lol. it cycles on the gas is ignited and runs for 5 to 10 seconds and flame goes out. it will do this three or for times and then the blower shuts off. if i take out the quick disconnect and put it back in it does the same thing over again. i replaced the flame rollout switch now it lasts a little longer 10 to 15 seconds but still ending with the same results... please help


Dirty flame sensor ... Goodman Air Conditioners

High side pressure going up and down from 300 to 400. No exspansion valves on unit. What's going on ?


Possible over charge or air flow problems through condenser ... Air Conditioners