Indoor unit comes on for 5 seconds and then shuts down

\015 When the indoor unit is turned on the operation light blinks twince and then shuts off why is this?\015

Answers :

Then there is wrong with your room air thermistor or the freeze up sensor, if you have a multitester you can check the resistance of the sensor. The resistance is 10kohms.
"Off" the circuit breaker and then "on" again then start the unit .

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Compressor problem? My outdoor unit comes on with the fan blowing just fine. Then I hear a buzzing sound for about 2-3 seconds which I believe is the compressor trying to come on. (Incidentally, a couple of lights inside the house seem to dim at the same time that the buzzing sound occurs.) The buzzing sound reoccurs every couple minutes while the outdoor unit fan and the indoor blower both continue to run. I have shut down both the outdoor and indoor units for a couple hours and tried restarti


The buzzing is your compressor trying to start. It is going off on internal overload caused by heating up of the motor windings.If you have an amp meter you could check the amp draw of the comp against the locked rotor amps listed on the tag You cou ... Ruud UBHC Air Conditioner

Indoor unit comes on for 5 seconds and then shuts down


Then there is wrong with your room air thermistor or the freeze up sensor, if you have a multitester you can check the resistance of the sensor. The resistance is 10kohms. ... Mitsubishi Mr. Slim MXZ30TN Air Conditioner

I have a 1 year old LG LMU245HV with 3 indoor units (a 12K, and 2 9K btu). This is the second heating season and I have noticed that when any one unit is on the temperature coming out of the unit is not very warm. This however changes when I run a second or the 3rd unit. When I run 2 or more units there is plenty of heat coming out. What would cause this? Any ideas would be appreciated.


Hi,\015\012\015\012Is this a new saituation for this year??? \015\012My first thought is that the unit is over charged, but that could not be happening if the unit worked okay last year....\015\012If it worked okay kast year a ... Air Conditioners

Electrical Schematic?? Hi, Here is our problem:  We have this unit installed in our desert vacation home in the wine "cellar" room, at times when we are not here, the electricity has gone out (even just for a second) and this unit shuts down and doesn't come back on until we come here and physically turn it on again. We are looking to bypass this so we don't have wine ruined while we are away.  How can we get this unit to come back on by itself?   Another problem is: this unit is installed in su


An easier solution would be to connect it to an UPS. May not be the cheapest though. ... Hitachi RAS-09UH Air Conditioner

I purchased an Amcoraire split system unit for my 2 story garage. Licensced electrician did the wiring and licensed HVAC co. installed the 2 indoor units and outside unit. Outdoor unit is Model # AOM 243 HX 24000 BTU Indoor units are both Model #AWM123 HX, 12000 BTU each When I turn the unit on, it runs for about 60 seconds and then I get an error code on the inside wall unit that says P7. My manual says this has something to do with voltage. I had the power company come out and they show the


Since the manual says the error code has something to do with voltage it means the voltage is either too high or too low. And as the electric company says the voltage is within limits the the error is as a result of the voltage fluctuating. All you h ... Amcor Air Conditioners

I have a Goodman GPD075-3 REV B gas heater that tries to come on but shuts down within 4-5 seconds. After the gas burners come on they shut off. The exghust blower is running and also the house blower is on. What is causing the unit to shut off? Is it the flame sensor or something else?


... Goodman Air Conditioners

I have a frigidare gas heating unit aprox 8 yrs old. the problem is the unit comes on the ignitor heats up gas comes on and lights but the gas only stays on about 5 seconds then shuts off?


You have a flame proving device that senses the flame. It is located on the last burner in line looks like a piece of thick wire. Take some steel wool and gently rub the outer surface 4 or 5 strokes is all it takes to remove the carbon that has bui ... Frigidaire Air Conditioners

RV AIR CONDITIONER KEEPS COMING ON AND OFF. AIR IS COLD COMING FROM UNIT BUT IT SHUTS OFF THEN SECONDS LATER COMES BACK ON. DOES THIS EVERYFEW MINUTES.


... Air Conditioners

There is water coming out of my indoor unit. So much water that I had to shut off the ac unit. It is a Mitsubishi Mr Slim split type air conditioner/heating unit


Water coming out of an a/c is normal .its water outlet hose is wrongly installed or not installed at all.get it installed.also level the indoor unit towards the water outlet side when u install the hose . ... Mitsubishi Mr. Slim MXZ30TN Air Conditioner

I have a ten year old carrier heat pump unit. I recently replaced the indoor tstat. the outside contact and the transformer. Had a tech put freon in the unit also. I have to problems one is the airflow is minimal coming out of the vents it has new air filter and I cleaned the inside and outside unit coils. And the second problem is the ac with not get cold.


Two things are the most likely culprit. First check ytour inside coil with the unit running for 10 minutes or more and see if the coil is sweating there should be water running off of it. Also after one hour is there ice forming on it. These problems ... Air Conditioners

RHEEM HEAT PUMP RKMB-A18OCM25E COMMERCIAL UNIT HAS TWO OUTSIDE FANS SHUTS OFF 5 SECONDS THEN COMES BACK ON 45 SECONDS LATER COMPRESSOR RUNNING IS THIS NORMAL WHAT COULD BE WRONG


Head pressure control. is it cold? that is normal ... Ruud Air Conditioners

My indoor fan comes on but the compressor does not. I checked voltage, fuses and wiring and everything was ok. When I depressed the contact (single pole) the compressor would run and make cold air. When I did it a second time it held in and ran so we cooled the house down. Thinking the contact was bad I got a new one but it wouldn't come on but would run if I held it in and would shut off if I let off of it.. It has control voltage to the coil on the contact. The contact just wont kick in or sta


Aside from the contactor, you may have a bad capacitor. You will have to check the mfds reading to rule this out. ... Ruud Matching Split Air Conditioner

My indoor fan comes on but the compressor does not. I checked voltage, fuses and wiring and everything was ok. When I depressed the contact (single pole) the compressor would run and make cold air. When I did it a second time it held in and ran so we cooled the house down. Thinking the contact was bad I got a new one but it wouldn't come on but would run if I held it in and would shut off if I let off of it.. It has control voltage to the coil on the contact. The contact just wont kick in or sta


As u written here that the power is their in coil voltage than check for the neutral connection of the coil ,if it potential voltage across the coil is normal change the contacts coil & buy a new one with the same potential that u have in your ho ... Air Conditioners

Amana PTH153E35 unit works fine. With the unit on auto, about every 20-30 minutes the fan comes on for about 30 seconds and shuts back off. Temp is 80 outside and thermostat set to 76. Why is fan doing this?


... Amana PTH153B50AJ Heat Pump Air Conditioner

Burnham Oil fired boiler-burner unit Model # RS/112. Probably over 25 years old. The unit would run for 20 sec. or so and cut off. A little smoke was coming out of the little hole. Took it apart and cleaned the flue tubes/ turbulators etc. It was pretty dirty. Some of the tubes were completely blocked w soot. Cleaned the electric eye. Put it back together and it would still shut off after 20 seconds. Took out the gun assembly and adjusted the electrodes to specs. It appeared one of the electrode


Hi,\015\012The problem is the nozzle and quite probably the air adjustment is off.\015\012To be quite honest, working on an oil burner is not a DIY project. When any changes are made the air should be readjusted using a combustion analyse ... Air Conditioners

Panasonic Invertor I have two units they work fine, but the remote for one has gone blank. I have the screen go blank on occassions on the second remote but i give it a tap and the screen comes back up. The Model number for the indoor unit is CS-E18HKR and the outside CU-E18HKR. I'm assuming they require batteries but there doesn't appear to be anyway to do so. Please help.


... Panasonic Air Conditioners

I have a Sanyo Split System the indoor unit is a KHS0921 and the outdoor unit is a CH0921. When i first turn the indoor unit ON the fan will run for a few minutes and then go off. The outdoor unit never comes ON when there is a cll for cooling. The only way to get the fan to come ON again is to turn the breaker OFF and then back ON. The Operation loght will come ON when the fan is running but it will start flashing when the fan goes OFF. What should i look for?


... Sanyo Split System Air Conditioner

Carrier ac fan works when remote is set to fan. When set to ac it come on for a few seconds then the unit shuts off. The filters are clean. I took the top cover off and there are no leaves bees etc plugging anything up.


You have an electrical short or need capacitor replacement because when you set to cool compressor tries to star but take more current then trips. ... Air Conditioners

Hi expert the problem i have come accross is when i start the split system 2.5hp the unit will run then the compressor will run for a few seconds then compressor cuts out and indoor turns off as well. I am an electrician and a ac installer but not a ac mechanic, its got a charge of about 200kpa I then managed to get it to 250kpa once it cut out again it was sending my scales to near 800kpa so I ended the charging process the next time it kicked ,then disconnected my hoses. So what could this be


Hi\015\012\015\012This is not the low charge as the unit is gettin charge of about 200kpa. I believe its the compressor thats about to die as usually the clicking sound comes from the compressor when its about to die or is bad. You can fi ... Air Conditioners

Tempstar CAE120HAA Unit comes on for 5 seconds and then shuts down


... Air Conditioners

I have LG LMU240HE multi type air conditioner. It is about 5 years old. It will not stay on. When power on, runs about 30 seconds and power indicator blinks and Sleep mode indicator comes on and completely shuts down. I have two units and both are acting the same. I have cleaned well, checked power supply, used remote to cancel sleep mode, reset remote numerous times and still not running. Please help.


... LG LMAN090HNS/LMU240HE Air Conditioner

Model No. 8333C876, Serial # 070512361: This unit had been cycling on and off (as it normally does) for 2 days. After being idle for about 30 minutes, it kicked on (fan and compressor) for about 10 seconds then shut down. Now it will not come back on at all. Could the termostat be the problem? If not, what?


Coleman Mach Model No. 8333C876, Serial number 030508618. I just bought a 2005 Jayco Popup Camper with this unit on top. Both Low and High Fan controls work OK. when I turn the AC knob to High Cool, it will blow cool air. then after about 2 minutes ... Coleman Mach 15 Air Conditioner

4270151 keeps tripping the plug circuit breaker (not the house). We can reset the plug and comes on for a second, then shuts ac unit off


... Kenmore Air Conditioners

SW6DEA GAS HEATER UNIT FLAME WILL NOT STAY ALIGHT ! Switching gas water heater unit on inside the RV, the red light comes on and approx 6 to 8 seconds later ( normal time cycle ) the gas flame lights up OK but goes out again after approx. 6 to 8 seconds with the red light going out at the same time. Leaving the unit switched on inside the RV, after a further 6 to 8 seconds, the red light comes back on automatically and repeats the start up cycle over - again without success. *4 times unsucces


... Air Conditioners

The control for the compressor is not turning on when the remote is set on cool, but the indoor fans turn on. This is a C4822N outside unit and a RS 2422A twin indoor unit. there is 220 volt being sent down on black and white to the indoor unit but nothing comes back to the outside unit on red


... Sanyo Split System Air Conditioner

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || www.ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.0825 seconds