Air handler squeals

\015 The air handler in my air conditioner squeals. what's wrong?\015

Answers :

Squealing sounds from a forced-air heat pump generally occur when the belt that connects the motor to the fan slips. If the blower is making a grinding noise, shut off the unit and call a heat pump repair technician --the motor's bearings are probably shot.\015\012\015\012In most cases, the belt is improperly aligned or worn and needs replacement. Follow the instructions in your owner?s manual (if you don?t have one, contact the manufacturer and ask for one).\015\012\015\012This job involves removing the access panel, loosening a couple of bolts that hold the blower motor at the proper tension, and realigning or adjusting the belt. In many cases, it?s a good idea to remove it and buy a replacement at the hardware store.\015\012\015\012When reinstalling the belt, be careful not to over-tighten it--this can wear out the motor bearings.
There's no belt in these units. It's probably a warped blower wheel or bent blower housing.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Air handler squeals


Squealing sounds from a forced-air heat pump generally occur when the belt that connects the motor to the fan slips. If the blower is making a grinding noise, shut off the unit and call a heat pump repair technician --the motor's bearings are probabl ... Haier Energy Star ESA3183 Air Conditioner

Air handler squeals for one half to a second only upon startup


Time for a new drive belt. Clean the air filter while you are at it. ... Ruud Air Conditioners

Rheem Air Handler will not run. This is a 2006 Rheem model RHLA-HM3617JA Air Handler. I replaced both the condenser and air handler circuit boards. I replaced the motor in the air handler.. The condenser works fine, the board flashes normal. The air handler board shows 0 volts on the X13Com brown lead,..28 Volts on the center, X13G green/black lead, 1 volt on the Bottom, Blue, X13SPD terminal. The 24VAC Terminal shows 27 volts. The 3 amp fuse is good. The transformer appears normal. I replaced


We tried to bypass at the Tstat. Thanks for your time and interest. ... Air Conditioners

Rheem Air Handler will not run. This is a 2006 Rheem model RHLA-HM3617JA Air Handler. I replaced both the condenser and air handler circuit boards. I replaced the motor in the air handler.. The condenser works fine, the board flashes normal. The air handler board shows 0 volts on the X13Com brown lead,..28 Volts on the center, X13G green/black lead, 1 volt on the Bottom, Blue, X13SPD terminal. The 24VAC Terminal shows 27 volts. The 3 amp fuse is good. The transformer appears normal. I replaced


Have you hard wired your fan motor to verify that the motor and or the capacitor are good? If you do a continuity test of the motor leads(with electricity off of course) you can see if the motor has open or grounded windings. ... Ruud Handler Air Conditioner

Hello, my HVAC is constantly freezing, even after freon is added. I was told that I have a leak in the coils and need to chance the air handler - the outside unit is about 10 years old - air handler about 18 years old. I would like to get only the air handler for my R22 outside condensing unit. My question is if in the future can I use this same 3.5 ton air handler with a new 410 condensing unit once my outside unit needs to be replaced. In other words can a Goodman air handler be used firs


I'm new at this and I can't tell how old the post is but I'll contribute anyway.You probably have fixed the problem by now. I wonder what part of the system is freezing up. I don't have a lot of experience but I know you can get frost where there ... Goodman CKL42AR42 Air Conditioner

I have a Lennox CB29M Air Handler with an electric heater, which is used to heat the lower two rooms of my house. The handler unit is located in a mud room right behind the back patio. I'd like to get an air conditioner unit that can mount on the patio that can be hooked up to this air handler, so I can have air and heat in these two rooms. Are there units that are available that can work with this air handler? How hard is the install, and can you recommend anyone in the 19030 area that I can tr


Any of these Lennox dealers can help you choose a compatible HS29 or HP 29 condenser and evaporator coil to match your system.http://www.lennox.com/locate/default.asp ... Air Conditioners

Air handler Is a 3 1/2 ton air handler too big for a 2 1/2 ton air conditioner? air conditioner FT3BA 030KA air handler B3BV 042k BB Also duct work in garage has a gap bringing in air from garage.


Yes and that's dangerous as fumes and exhaust may enter the house ... Air Conditioners

Installed goodman air handler, system has hot water coil in duct for heat, how should i wier the 6006, or 4006 control to turn the fan on, on the air handler? if the limit switch turns the fan on for heat, isn't it going to send 24 volts back up the green wire to the t-stat? old air handler ( york) had a fan center relay.


\015\012\011\011\011\011\015\012\011\011\011\015\012\011\011\011\015\012\015\012\011\011\011\015\012\011\011\015\012\015\012\011\011\015\012\011\011\015\012You abso ... Goodman Air Conditioners

There is a condensate build up in my Trane XP 100 Air handler located in my hot Florida garage. The unit sweats on the out side and inside water drips through the heating unit which now shows rust marks and onto the squirrel cage fan. Condensate water is then splahed onto the fiberglass insulated walls of th air handler. Mold is beginning to build up both on the inside walls and on the fan unit. The air handler performs fine. My home is kept cool, but I am concerned about this condensate and


This is complicated, as you know condensation can not be avoided when cold air comes in contact withhot humid air. Here is what I would try. You have to gain access to your evap coil. Which means tearing into the sheet metal cover. The updraft ... Air Conditioners

Hi, I have an air handler motor made by GE Commercial motors. I think the motor number is N656 S. It's a 1/2 HP, 1075 rpm motor to replace my existing air handler motor. I want to install it in my air handler, but it's wiring appears to be different than on the system I currently have. The current system has a purple wire hooked up, and I don't know what it's for. There is also a red and black wire which correspond to the yellow and black wires on this motor, but nothing to compare to the purple


See where the purple wire is hooked up in the existing motor diagram (it could be the capacitor or a lower speed for the heater) and compared with the new one , and put it in the same place .But the easiest way to do it ,is to get the original replac ... GE Air Conditioners

LOW VOLTAGE WIRING CONNECTIONS BETWEEN NORDYNE FT4BF-0-36KA 16 SEER 3 TON HEAT PUMP AND B4VMX36KBAH VAR 410A AIR HANDLER AND RITE TEMP 6036 THERMOSTAT. THE CONNECTIONS ON THE OUTSIDE UNIT ARE Y, R, O, C, W2IN, Y2, L, W2OUT. THE CONNECTIONS ON THE AIR HANDLER ARE Y1, W2, W1, O, Y/Y2, G, R, C. THE CONNECTIONS ON THE THERMOSTAT ARE C, B, O, W2, W1, Y1, Y2, RH, RC, G, A. ARE ANY OF THE TERMINALS ON EITHER THE AIR HANDLER OR THERMOSTAT JUMPERED TOGETHER AND IF SO WHICH ONES. I AWAIT YOUR RESP


... Air Conditioners

Our Carrier central air is unresponsive, nothing at all, no noises, air handler and condenser unit will not turn on, please help me before I lose more weight in my 150 degree attic. The serial # for the air handler is 0695803341 and the product # on AH is FB4ANF030000ACAA / we only have central air, system is not connected to any heat source Early sunday morning I turned the T stat to the off position, when i came home a few hours later I turned it back to the on position and nothing at all, no


I think you need to slow down and start fresh. \0121) You have 115v at Transformer-You are reading from Red to White\012 on windings?\012\0122) If that checked out OK are you reading 24v out of Transformer?\0123) If ... Air Conditioners

My outdoor heat will not operate. It is a Carrier 38YRA042330, with a Carrier Thermidistat thermostat and a Carrier Air Handler 40FFKB005300. I have an H5 error code on the thermostat will I put it in Heat mode and raise the setting to call for heating. I changed the air filter on the air handler when I realized the heat pump was not operating. The air filter was pretty dirty. The system will operate in aux/emerg heat mode, with the fan in Auto or On mode, and will maintain the thermostat


You need to go oside and look for a red reset button on the unit. you tripped the high ressure switch when you let your filter get that dirty. go check on this and when your done if it still is not working then ask me more. ... Carrier Air Conditioners

How to fix the leak between the air handler and escutcheon that connects to my drain pipe on my carrier air handler


... Carrier Air Conditioners

Is it ok to replace outside unit of central air and heat and not the inside air handler ? The upstairs A/C( over 10 yrs old) is not keeping up with South Texas heat. The temp upstairs climbs to 84-86 degrees by the afternoon and takes 4 or more hours after dark to cool back down. I have cleaned the entire unit outside- no help. I have replaced the downstairs unit 2 yrs. ago and it works fine. I don't want to replace the upstairs air handler if I don't have to---much more cost.


I'm assuming you have had a competent Air Conditioning contractor look your unit over.if you trust your A/C contractor, why don't you work with them towards an answer? I would get an air flow and sizing analysis, a full equipment service/performance ... Air Conditioners

Hi, After finding out that Freon is low by seeing snow/icy surface on outside compressor, I went up in the attic to find snowy/Icy surface all over the coil inside the air handler. I wahsed it and made sure all snowy/Icy surface is melted inside and ouside and Freon is full all the way. Now when I start yhe system fro the Thermostat, the compresor and outside unit start, but nut the fan inside the air handler, so no air is blowing inside the house. Where should I look for ? This is a R


Hello\015\012Your still froze up.There is a freeze cutoff device in the air handler upstairs.\015\012Look for a thin silver color tube near the coil and follow it to the control box,there may be a reset button.If not, try using a hair dry ... Ruud Air Conditioners

I have a honeywell pro 2000 programmable thermostat which controls an enerzone ahc 31-18 series water source air handler with heating and cooling coils built in. This therostat and heater worked fine all winter. Last week i had a air conditioner stalled and connected to the air handler and the AC worked for one day. When i tried to turn on the AC yesterday, the fan would not come on for either AC or heat. any troubleshooting suggestions? thanks ... Donald


... Air Conditioners

Does the RUUD UBHA14J11SFAA air handler have a filter which needs cleaning or replacement? I change the cold air return filters regularly but have never serviced the air handler in the ten years it has been running.


... Ruud Central System Air Conditioner

How to evacuate system after installing air conditioner air handler?


... Air Conditioners

Condensing unit continues to run after air handler is stopped. Problem is intermittent. Thermostat replaced. Suspect air handler relay. which one?


When this happens, most often you'll have a stuck contactor coil on the condenser. If you buy it , it should cost $20---to 15.00 and you can add if you turn off the power (240volts) and the furnace power! ... Goodman Air Conditioners

I have a Jantrol heat pump & A/C. It is approximately 10 years old. For the last 3 summers the compressor unit will freeze when the air handler fans fails to come on. It worked fine for 2 weeks this year before it happened. I've be able to thaw it out and restart the unit and it works from days to weeks before this occurs again. The last time it happen, I had a problem getting the air handler fan to come back on, but it did eventually. I've been thinking it may be the sequencer, but now I'm wond


Hi,\015\012\015\012If you can safely check the supply to the motor when it should be on, then this is the best method to check it.\015\012\015\012Check the fan turns very freely - oil the bearings if it doesn't.\015\012 ... Goodman Air Conditioners

One of my AC units froze up. I cut the unit off. after it defrosted I turned it back on soon after we smelled wires burning. I turned the unit off. Now when I turn the unit on the outside comp. goes on but the air handler will not turn on , I checked the low volt fuse it is fine and ther is no reset switch, what could have happened there are no burnt wires inside the air handler.


You may have a couple of problems now. The original issue of icing up is most commonly due to low refrigerant in the a/c. For this you will need a professional to correct.The second problem sounds like it may be a bad capacitor for the in ... Air Conditioners

Hi,I am really hoping to find someone to help me if possible. I have a one year old carrier infinity 4ton 17seer condenser and a 5ton variable speed air handler. I has worked fine but now i am getting a SYSTEM MALFUNCTION on the thermistat. When this message appears the air handler continues to blow and only the fan on the condenser continues to run but NOT the compressor so it is not cooling. At times it begins cooling again but then later stops cooling and shows the same malfunstion message. I


Hi,\015\012If this si what I am thinking it is, it will be very hard to find and prove.... \015\012The compressor windings have aflat spot and if the motor stops at the right place it will not atart. The voltage goes way up and kicks out ... Air Conditioners

The air handler motor does not turn on just a humming sound from the air handler


Capasitor is shot ,replace ... Goodman CLQ36AR49 Air Conditioner

Lawn mower cut control cable going to outside unit. a 3 amp fuse was blown inside air handler. spliced cable togerther, color to color and replaced fuse. air handler will run but compressor does not come on


Can you take an A.C. voltmeter and see if you have 24v.a.c at contactor on outside unit, if not recheck for same at control board inside to see if the same then you can start isolating the trouble ... Ruud Central System Air Conditioner

A detailed question is important to get you a relevant answers