No control power

\015 What should the primary & secondary voltage be at the transformer?\015\012Is it on when the unit is plugged in?\015\012The transformer says primary 240v, but it is not...Thank you\015

Answers :

PRIMARY means INPUT(from supply side)
SECONDARY means output( to load side)

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I posted a question about the Ultra sx 90 (Armstrong) furnace not lighting and the combustion blower keeps running. I did clean the flame sensor and no change. I also changed the spark control moduleas well and it still does not lite. I checked power at the control module and is 24V. When it calls for heat, there is power coming up to the control module and the PV terminal only. There is no power on the PV/MV terminal at all. I am sure that power is required there for it to let the gas out. I ca


When this problem has occurred on my York furnace, the temperature limit switch had to be replaced. You may have checked this in your troubleshooting but if not, it's worth a try ... Fasco Air Conditioners

Model AOT25RZAL. First time use...came with apartment. Power went out in control box when I changed the temperature. No power issue with main power supply to the house just a blank screen on control panel. Is there a fuse inside the panel? LC


... Fujitsu 24C1 Air Conditioner

The circulating pump for the central heating from my stanley brandon is not working there is no power to it from the electronic control board I have changed the electronic control board and there is still no power (the boiler starts and runs but stops when the temperature gets too high due to no water circulation


Hi,i think the problem is possibly from the thermal fuse or the electrical motor of your device,i think you should run a troubleshoot on these parts and change the part that is affected to restore your unit back in a perfect working condition.\015\0 ... Air Conditioners

Turned on the air conditioner, it ran for 5 seconds, then switched off. I now have no power lights or anything on the control panel (a MICOM MKK Control). Have tried turning the power off at the switch for 10 mins then back on again, no luck. Desperately need to fix it, NYE tomorrow and 40+ degree day! Thanks, Jay


As you don't mention error code, out of two reasons, you check one by one. 1. First check manually rotate the blower wheel. If it hard to rotate, blower motor mechanism blocked.Replace bearings or motor. 2.Your indoor coil and room sensor ... Air Conditioners

There was a lightning strike last night, outside near my AC Condensor Unit. The system is not functioning at this time...confirmed that there is power from the house power panel. There is a disconnect on the house near the Condensor Unit, non fused. Any ideas? I assume that I need to go find the AC controller up in the attic near the fan units. What do you think, a blown fuse or control board?


Could be anything if hit by lightning. i would look for something burnt, black, visual search for frying. ... Mitsubishi MSH09TW Air Conditioner

I have aFujitsu split air conditioner, the remote control have got lost. I then bought a univarsal chaina remote control named Amely. I instaled the code for the air conditioner but the remote can only power it off and can not power it on. Please what can I do?


... Air Conditioners

Window Air Conditioning model ACQ189XSO. Unit will not run or show power at the control panel even though power is applied to electronic control panel and capacitor as verified with multimeter. Fan is not seized. What could cause this problem?


... Air Conditioners

A/c control only works on high the power in the control turns of a/c and all unless the blower is set to high when you turn it to low or med its as if your turning off the a/c and power to the whole system


Check your resistor in the blower area this is most likley a problem area ... Air Conditioners

I have a furnace 90+ . I have no power at the t-stat..no led, blank screen, and the blower will come on. The furnace is tied into a control panel. I can jumper the the unit at the furnace to have the A/C to come on. It will go thru shut down cycle and stop. 5 min. later the blower comes on.I've cut power to see if it will reset the board, no change in operation. control board has 24 volts with status light on but other lights off. All limit switches closed. I,m in need of sugestions Thanks.


Either a thermal switch is open or the pressure switch is closed at start up the system checks all of these before sending power to the T-Stat ... Air Conditioners

Panasonic Inverter CS-E12EKU timer indicator blink. The unit not work at all, I follow the manual instructions using the remote control but the instructions are not clear. Using other similar Panasonic model instruction clarify the process and get 4 seconds beep, 30 seconds power indicator on and the code F99 at the control. In the error code table for the similar model F99 means Outdoor Direct Current (DC) peak detection and instruct to verify the- Outdoor unit PCB- IPM (Power transistor) - Cop


Today I install a new unit Panasonic CS-S13KKP also have a same problem timer blink and the outdoor unit wont start. Error code is 11. after checking the problem, can not using a 3 cable cord, solve the problem using 4 Cable cord and its run ! ... Panasonic Air Conditioners

No Power Unit will not power up. Display is dead, control panel and remote does not work. Power is present at outlet and power cord. 230VAC detected at Frigidaire part number 5304476450 power board wiring blocks and terminals. Am I to assume this board is bad and needs replacement


... Frigidaire FRA124HT2 12000 BTU ThruWallWindow Air Conditioner

Split AC 1200-BTU Kenwood Model ANK12P Pearl series Power lights ON but Unit does not become ON. Its power LED becomes ON but buzzer does not beep as it beeps with normal power ON,and no response from remote control. When manual button is pressed for about 5 seconds, its whole two(7 segment ) LEDs become ON and then blower motor and compresser power supply relay becomes on. then the 2 (7 segment) LEDs go OFF. and timer LED becomes ON then (compressor) power LED becomes ON, then sleep LED (all on


HE, I Dont Know where youre getting these #'s from but the only thigs comes up under kenwood model ank 12p pearl series is "GERMAN" websites and nothing I could understand websites. ... Samsung AS18A6RB Air Conditioner

Mitsubishi MXZ- 3A30NA 20 Amp fuses blown at disconnect, replaced, energized no responce fuses did not blow, no LED lit on PC control Board. Page 41, 10-6 Troubleshooting Flow of Tech Manual, Outdoor Unit Does not operate. (LED display: display off) Input power to Noise filter board good. output power to reactor not reading 240VAC between legs TAB1 and X-64 pin located on contactor on noise filter power board, however I do get 120V each leg to ground. Replace noise filter power board? I removed


Have you checked the reactor board for a defective M.O.V. thyristor that way have a burned spot on the side of this component that normally would have, due to a lightening strike,over-voltage or under-voltage,if they open they will kill one leg,or po ... Air Conditioners

I have a LUX TX9000LC control, connected to a Carrier Model 394GA036100. The controls don't seem to control the furnace or air conditioning. The fan on the furnace runs continuously even when the switch on the control is in the off position. The only way I can turn the fan off on the furnace is to switch off the power to it. I put new batteries in the TX9000LC. No change. Thank you, Ron Casto


Ron, \015\012It sounds as though a "safety device" opened on your gas furnace......which shut off your furnace and has the fan running non-stop. Go to your gas furnace and look for manual reset switches......these switches typically have a smal ... Air Conditioners

No Power Like everyone else the unit was working fine the 1st summer. Pulled it out again and nothing. It powered up for about 30 seconds then shut down. Now no power at all to the control panel. Is there a fuse link, or some kind of auto shut off I should be looking for? I can't say if it still blows hot and cold as I can't power up to find out.


Did you check the drain switch ?? this will shut them dowbn as well? ... Danby DPAC8399 Air Conditioner

I have a Haier AC model # ESA3087. The temp control down button will not work and actually changes the fan and timer controls. Do i need a new power panel or something else.


... Haier Air Conditioners

Warmflo controller won't switch over to propane when the power company controls my plenum


... Electro Industries EM-WU153D8-SL2, WarmFlo Three Stage Electric Plenum Duct Heater-18&qu

Brivis Ducted Heating system. No display on Programmable controller inside hoiuse. Electronic Control (Model 14100) located on Heater (outside house)displays "Searching". Have turned off power and left for 1 hr then turned back on - no change. Tried resetting through buttons but no change. Have assumed Electronic controller has died - but can't find troubleshooting guide to prove. Don't want to waste $$$ if can be avoided.


Hi,I have an identical issue with my Brivis.Did you get a solution?Mine can be running, then goes blank and says searching. it will eventually come back.Just wondering if you had to replace the 14100?CheersJ ... Air Conditioners

Hi guys i hav a ampac pulsar series micro spa controller model 2082spx 15amp it just stop and the touch pads just flash plug pump and air blower to other power sorce thay work fine but put them through the controller works for about a hour then stops and touch pads flash its a signture spa im asuming its the controller is the fault


... Air Conditioners

I have a Heat Controller EKTH15-150J PTAC. Of lat,e toward the end of winter here in southern Missour,i the unit while in heat mode has been randomly blowing cold air. Often you can shut off the unit and let it sit for awhile and when you turn it back on it will come up heating again. A couple of years ago I replaced the control board that had been killed by a lightning induced power surge with a RSKP006 control board kit. It has run fine since, until the last few months. Sometimes I can pu


Your problem sounds more like a reversing valve issue.The reversing valve will tend to stick and not close completely causing cool air instead of warm.Check the low voltage wires to the control board(usually orange) and the 24 volt signal ... Comfort-Aire EKTH15-150J Air Conditioner

Vulcan bonaire evap cooler with touchscreen controls suddenly not working. Touchscreen not doing anything when pressed.. Have tried what I think to be the reset button on the control with no luck. Have turned the mains power off and on, nothing. I have no user manual but it looks to be model: Touchpad Control (LV) - Tekelek, after looking here: http://www.bonaire.com.au/support/documentation/owner/default.aspx . This looks exactly like our touch screen. Any help/ideas greatly appreciated!!


... Air Conditioners

I have an split-type aircon (brand: General) remote control AR-DL2. it has power and display when i put on batteries. but the aircon unit does not respond to the remote control. what do i do to fix this? Is there something to do to reset the remote control and re-program ? Or shall i buy a new one


I have general electronic ac brand i cant found universal remote can u find one for me what are the universal remote that compatible for my ac tq ... Air Conditioners

I can not control my furnace. The handyman pulled all the control wires off trying to fix it. is there a standard way of wiring the control of a furnace. I need to hook up the Bryant Magnetic Diaphragm Valve to the thermostat, power source, hi temp safety switch and pilot. The system runs on natural gas. Valve is model ib634. Thank you for your assistance. Sincerely, Jack Cohen, Mananger Apex Property Manangement, LLC tel: 610-656-2401 e: [email protected]


... Bryant Air Conditioners

My Carrier Infinity Hybrid Furnace/HeatPump is suddenly not responding. It's been working for a few years, but today it's acting dead. All the breakers are on. At the furnace (58MVB series 100) I hear a light buzz/hum from the control panel that stops when I turn off the switch on the side (or open the control panel access door), and returns when I turn it on again, but there's no amber light on the control panel, and the thermostats and electrostatic filter seem to have no power either. What's


Turns out the condensation pump wasn't detecting that it was full, but the furnace was, and the furnace was disabling. A local heating contractor suggested that I jiggle the condensation pump. When I did that, the pump ran, and immediately the furnac ... Air Conditioners

Bonaire evaporative +cool change control is on heat setting even though this is not a function it can do. Cannot get control to reset - have turned off at maisn power, have new batteries , have reset. The control is no recognising the installed model.


... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || www.ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.0422 seconds