Having problems with your Air Conditioners ?

Amana ptac i have an amana heating and cooling unit in my room at school and i was messing with it to lower the temperature setting and now the LED just read 'on' in lower case letters. the ac or the heat will not turn on. is there anyway to reset it? how do i clear it so that my unit works again? thanks.


Answers :

First you have to hit the plus(more heat) and minus (more cool) and hit off twice then the unit should show c1 and wait till it shows L5 the hit the plus sign till you get to zero then hit off.
Unplug it, or turn the breaker off for 3 minutes, unit should restart.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Amana ptac i have an amana heating and cooling unit in my room at school and i was messing with it to lower the temperature setting and now the LED just read 'on' in lower case letters. the ac or the heat will not turn on. is there anyway to reset it? how do i clear it so that my unit works again? thanks.


First you have to hit the plus(more heat) and minus (more cool) and hit off twice then the unit should show c1 and wait till it shows L5 the hit the plus sign till you get to zero then hit off. ... Amana AAC051FRB Air Conditioner

I have a Goodman PC-060-1B All-in-one unit on a Double Wide home that I have one problem with and one question about; the problem is that the heating side is not working properly. I found the lower heating element to have a corroded connector, which could not be replaced, so I bought a new one and installed it along with five of the related control sensors around it. Now, if I turn the thermostat to heat, I can see the heating coils glow bright orange for about 1 minute and then the whole thi


... Air Conditioners

Amana PTAC Unit is not producing heat. Fan works fine. can not locate manual reset for heat although a label on the unit says there is one. I have an Amana pth153b35ae ptac unit that the heat will not come on. The compressor will run in the cooling mode but not in heat mode. I verified the switching valve is working and the capacitor seems to be fine as the compressor will run in cooling mode. The thermostats seem to be functional because relays can be heard clearly when changing temperature se


I know this is late but I had to add a solution to this problem since I had the exact same problem and was able to solve it. The probelm is not your control board. On these units, the heat pump compressor will not kick in unless the temperature you ... Amana PTH123B25AJ Heat Pump Air Conditioner

I have a AMANA PTh153B50AE (PTAC unit). The air conditioner works fine. It is when I turn on my heater and it does not get warm. It just blows cold air. I have looked at the board and it appears that there are no bad spots on the board from where it had burnt. It appears that it may have a manual heater reset button. I am not sure if that will work but I can;t find the reset button. I am wondering if my heat pump has gone bad. Any help would be appreciated. Thank you.


I have the same problem, and I found the manual reset inside the unit. Turn the power off, and unplug the unit. Remove the outer cover of the unit ( inside cover ) , and remove the 2 screws holding the " wire mesh " in the front of the cover. Pul ... Amana PTH153B50AE Air Conditioner

I have a Daikin 4mxs32 with 4 indoor 9K wall mount units. About 3 months old. All of a sudden it stopped heating or cooling in all rooms. It works in the closest room to outdoor unit. Not at all in furthest room but does work somewhat on unit directly on other side of the wall and also somewhat on unit directly on other side of wall behind closest unit. Then I also noticed that when I turn the furthest unit that somewhat works off the close unit that somewhat works goes up in discharge temp in A


... Cfm Daikin R410a Split System Air Conditioner

Amana PTH153B35AK This unit is less than 30 days old, heats fine cools fine, but when i have it in heat mode,set @ 70 or so, as soon as the room heats up, the unit will cycle into a/c mode and blow super cold air for about 5 minutes than return to heating. Sometimes it will reach the desired temp. and turn off like it is supposed to do, but for the most part it just cycles back and forth from hot to cold...Amana has the worse help/service i have ever seen, i was on the phone for an hour,everybod


This often happens if the unit is oversized or to close to a wall or object. ... Amana PTC153B35AK Air Conditioner

Amana #PTC153b50AJ ser 0410686783 Customer heard a pop in unit and it went off. Breaker was tripped. Reset breaker and unit runs in a/c mode but does not heat in heat mode. This is not a heat pump but electric heat strips. Unit says there is a manual reset for the heat but we have not located the reset. We turned power off to the unit to reset fault etc and still no heat. The flashing light just blinks once every 4-5 sec. Could use some help in diagnosis Thanks DK


... Amana PTC153B50AJ Electric Heat Air Conditioner

I have an Amana central air/heat unit. Model PHCB10C1 Serial # A040900070 Manufacture # P1219409C, Cat # 81K95. The problem I am haveing is the unit will not kick in(heat). When I turned off the main pwer and let off for about a hour and turned back on the unit ran fine for a couple days. Now the unit will not kick in at all even after turning the main power off and on to reset the unit. I have a brand nre thermostat in the house. When I turn the fan from auto to on the fan runs and blows out


... Amana Air Conditioners

My AC My Compressor keeps kicking off. I turn the unit on, the fan works. The Heat works but the compressor turns in about 60 sec. If I unplug the unit and turn it back on, it comes on but the compressor shuts off again after 60 sec. Can this be from dirt in the coils? They have some build up. Any other causes?


One might think so, YES the compressor is running till it gets hot and tripps on hi-temperature, and after it cools down awhile, the switch willcautomatically reset itself and back- & forth......Thank-you-very much! ... GE Zoneline AZ38H12DAD Split System Air Conditioner

I have a 10-year old Carrier Gas pack Model #48GS024060301. Turned on the heat for the first time this season and the unit did not turn on. I was able to turn on the house circulation fan and since it was a warm day today I also tested the A/C side and it worked fine. The inductor motor and fan were replaced last year. All the fins on the fan blade basically flew off on the first start up attempt last year. The entire unit, heating and A/C, were serviced within the last year by a certified p


If the induction motor ain't going I would look for a blown 3 amp (purple) fuse on the control board. If that was good I would check if any of the roll out switches were tripped. If a rollout switch was tripped check or air restrictions somewhere. ... Air Conditioners

I have an Amana Model GUC-C 90 Hi-efficiency furnace that we installed in 1992. It has a central air unit as well. On Friday we tried to turn the air on and nothing will work. I have replaced switches in the air unit in the past but this time there is no clicking, I can't turn the circulation fan on for the unit, the heater unit will not turn on. I have power at the breaker, and on the unit itself there is a on/off switch with a round screw in fuse, that fuse is good and I have power there.


Hello,Your control transformer may have quit on you, or your thermostat may have gone out. The transformer is what supplies the current for the hvac system. The thermostat just controls what relays are energized. Since you have a probl ... Air Conditioners

I have an NewAir 12000H Portable Air conditioner with a heat pump. The problem is that the heat pump no longer seams to be working. The desired temperature is 79 degrees. the unit never gets above 75 degree. when it actually gets that high it because my heat from the house has turned on. once the heat goes off then the unit goes down to 72 degrees and stays there until my heat comes back on. whats wrong with the unit? is there anything that i can do?


It sounds like the actual control module, the "brain", of this heater / air conditioner has failed and can't sense when to kick on the heat any longer. Have you tried just unplugging the unit for a good 5 minutes minimum and seeing if it will help " ... NewAir Air Conditioners

Had a ac tech service central heating unit for the fall. Tech left and I left to do some errands . Now AC unit is not cooling its blowing warm air. I turned the circuit brks off and on inside and outside. I have also checked to see if unit was left on heater. thats not the problem. If I turn theAC on the fan does not turn on outside and there is no sound coming from the unit outside HELP!!! AC was working properly before this.


It may not help but it sounds like the tech took a control wire for the cooling circuit loose at the indoor air handler/furnace so that he could bring the heat on to check it, and forgot to hook it back up. That may not be the case, but if it is it w ... Air Conditioners

The motor or blower wheel om my Goodman model GMP 100-4 unit whistles and sticks. How can I fix this? Can the motor or blower wheel be lubricated? Does the motor need to be replaced. If I manualy spin the blower wheel and get it turming some what and then start the unit by pressing the safty switch located behind the lower front panel the blower will start, the wheel fan will turn. If I turn the unit off and try to turn it on again before the wheel stops turning the blower will work. But, if


Yes its the motor problem.the noise is from motor.as the blower wheel is not making noise when car is turned off.and when checked manually the blower wheel is not making noise.that means motor is faulty\015\012thanks.please do rate the solution ... Air Conditioners

Heating and air condition unit will not kick on when i try to turn the heat on in the morning. we have tried the auto fan and the on fan for both ac and heat...will only work for the ac. the breaker switch at the breaker box is the only solution we have found to get the unit to fire up and to start the heat for the unit...my brother has checked the wiring at the thermostate..mercury type..found no burned out wires...he changed the filter on the system...tried to clean all the contact points on


Hello , I can help you out here. First check the T-stat with all breakers on take the red t-stat wire and white t-stat wire and green t-stat wire , tie the 3 together and wait 5 minutes to see if anything starts up. If the heat starts running replace ... Air Conditioners

I have a Carrier Air HVAC unit, It is not heating the house. THe fan works, the AC works, but when I turn the thermostat to heat it will not come on. I am thinking maybe a thermocoupler. The model number is 585HJ036060. Where can I find a service manual for this unit?


Do you know if the heat side of the T/stat is actually calling for heat? Depending on the wiring of your stat, normally the Red wire is the power supply (usually 24V) and the White is the heat. Have you tried setting the stat to max temp and jumper t ... Carrier Air Conditioners

A/C need hlep with a carrier model # 40aq030-300bb. just bought a house with this unit inside but outside different unit, think its a Goodman. When turned to heat everything ok, but when turned to cool it still puts out heat. Think reversing valve is bad or switch controlling it may be bad. Not to familiar with the system and wiring diagram is gone. Somebody made a mess of the wires anyway, need some help if you have any. Thanx and... GOD Bless


Orange or O terminal on Tstat energizes valve in colling cycle. Go to outside unit jumper red to orange and see if Reversing valve energizes. If it does . Problem inside possible Tstat. You shoulf here the valve click. Have someone inside switch fro ... Air Conditioners

My indoor unit on my heat pump will not shut off. The electric heat keeps running, and the fan keeps running. It only happens when it is really cold, like 25deg or below, above that and it functions fine. The outdoor unit shuts off, but the indoor stays running. I do HVAC work, but I have never seen a problem like this. I have switched the stat out, and its just so strange. I figured the relay may be stuck, but if I turn the stat off, it turns off shortly after which tells me it may not be the c


I would venture to say your stack relay is getting stuck. either that or you have a short in your low voltage wiring somewhere that is not always making contact....or it may be making contact through another median...like ice or frost. Remember ele ... Intertherm P3RA-036K Air Conditioner

I'm having a problem with my heating and air system, my heat only works on emergency heat ( and run 24/7) if i turn it to regular heat it only blows cold air. i dont think my outside unit fan is turning( i could be wrong about this one) how can i fix this problem so i dont have to run my emergency heat all the time


If your Heatpump's fan isn't running but your compressor is, your fan motor is out. If nothings happening at all ensure your getting power to heatpump (ex: breaker tripped, fuses blown on outside power switch, or fuses blown in breaker box?) ... Air Conditioners

Have a Amana Wall Unit with Heating and Air Conditioning - Model PTC123B50AE. The unit's heater just stopped heating. The fan/blower and air conditioner are working fine. Unit says the fuses are OK. Would appreciate any guidance in fixing this unit. Thanks, NC


PLEASE CHECK THERMOSTAT SETTING +29 AND ALSO MODE"HEAT". STILL PROBLEM \012CHECK THE HEATING SENSOR IS NOT OPENED. BY A OHMS METER CHECK THE \012SENSOR. iF ANY READING IN OHMS IT'S O.KAY. ... Air Conditioners

Amana My Amana has a gas pack that uses a porcelain ignitor. The thermostat will turn on the unit, but it will not always ignite the motor will just run. I can turn the system off for a few minutes, then turn it back on and everything will ignite and run till the next time. Is there a sensor not working just right because the ignitor will ignite?


Yes, there is a flame sensor that will tell the gas valve to open, thus igniting the burners. When you say the fan is running is it the blower fan or the little exhaust fan connected to the vent. Because the blower fan shoul ... Air Conditioners

I HAVE A 2000 HOLIDAY RAMBLER WITH TWO AIR CONDITIONERS. THE REAR A/C WILL NOT COME ON UNDER ANY MODE (FAN ONLY,HEAT PUMP OR COOL)WHILE IN ZONE 2.WE HAVE BEEN ON 50 AMP SERVICE AND IT STILL DOEN'T WANT TO TURN ON.ZONE 1 (FWD A/C UNIT )WORKS FINE IN ALL MODES.115 VOLT A/C IS AVAILABLE VERIFIED AT THE UNIT CONTROL UNIT.3 AMP FUSE IS OK.ANY IDEAS ON WHAT IS WRONG? PS THE FAN ON THE AFT UNIT TURNS FREELY. STERLING SNOW


Have you tried running both, when plugged in, as well as generator running? What about testing voltages etc at terminals on control boxes, has anyone done that? Just in case this unit is new to you, are you sure there is no extra switch that has to b ... Dometic Rooftop RV Air Conditioner

My unit is located outside and when I turned on the heat it made some noise and shut off. I turned it to on right after and it blows cold air not heat. I do not understand I had it running all summer and when I go to switch it to heat now its not working please let me know what I need for it.


Is it a heat pump or an air conditioner? ... Air Conditioners

I have a Lennox CB29M Air Handler with an electric heater, which is used to heat the lower two rooms of my house. The handler unit is located in a mud room right behind the back patio. I'd like to get an air conditioner unit that can mount on the patio that can be hooked up to this air handler, so I can have air and heat in these two rooms. Are there units that are available that can work with this air handler? How hard is the install, and can you recommend anyone in the 19030 area that I can tr


Any of these Lennox dealers can help you choose a compatible HS29 or HP 29 condenser and evaporator coil to match your system.http://www.lennox.com/locate/default.asp ... Air Conditioners

Have a Amana a/c heater central furnace. Model number PGA30R0452A. The a/c part works fine. The heater part does not turn on sometimes. We have to keep turning it on and off to get to work. No matter what you hear a slight humming when we turn it on just it doesn't always blow air out of the vents. It also does not always kick back on once the temp. has dropped and should start heating the house again. We have programmable thermostat. Any suggestions to whats broken or breaking. My husband woul


When you change from cooling to heating the fan will not come on immediately. A solenoid valve is energized (check that it is working) and operates a reverse valve, changing the gas flow in the system. It takes a few minutes for the system to build u ... Air Conditioners

A detailed question is important to get you a relevant answers