Having problems with your Air Conditioners ?

Aircondition I have a air conditioner problems, the unite inside the house is working I can hear it and feels the air coming out of the vent but it's not getting cool air, the unite outside all I hear is click once and about 2 to 3 mint. click again. I have the other air condition next to and it click and then seem to locked and worked. help..


Answers :

You will need an OHM meter to check the relay and compressor. Make sure all power is off. The most common types of compressor winding failures are open, grounded, or shorted. You have to know how to read a meter. If you don't find someone who can. Or call an HVAC tech, a small businessperson and ask if you can pay him/her to "confirm" a problem. Tell him or her to check your start components. This approach gives you an insiders edge and also shows that you know or are learning something about your product....
The clicking you hear is the compressor relay trying to start the copressor.. you have a bad relay or a lock up compressor. if you can jump the relay or replace it then you will know which one is bad... hope this helped.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Aircondition I have a air conditioner problems, the unite inside the house is working I can hear it and feels the air coming out of the vent but it's not getting cool air, the unite outside all I hear is click once and about 2 to 3 mint. click again. I have the other air condition next to and it click and then seem to locked and worked. help..


You will need an OHM meter to check the relay and compressor. Make sure all power is off. The most common types of compressor winding failures are open, grounded, or shorted. You have to know how to read a meter. If you don't find someone who can. Or ... Ruud UAKA030 Air Conditioner

Contactor not engaging to start condenser unit . When setting the thermnostat, i hear the click from the unit starting inside the house. Fans start and air starts blowing inside the house, but the condenser unit never starts. I tryed pushing the contactor by hand and then everything works find (cool house) as long as i keep the contactor pushed manually. Seems alike the 24 V (coil) bobine in the contactor is not been energize. When I tried the 24 V outside with a 24 V surce it worked fine. Thank


I would replace the contactor if you are getting 24 volts to the contactor and it isn't engaging therefore the magneto on the contactor is out and the contactor will need replacement. If you don't have 24 volts at the contactor then the transformer ... Air Conditioners

I have a goodman a/c unit, model cprt36-1. The outside unit has a faint hum and the blades are not turning. Inside,i cash hear the thermostat click, the blower damn also be heard at the air return


... Air Conditioners

The outside unit is running, but the inside air handler unit does not work? The blower is not working, but you can hear a clicking noise.


Turn the power off to the indoor unit and see if you can spin the fan by hand. the bearings may be locked in the motor. if so you need to replace your blower motor. let me know what you find out ... Weather King 10AJA2501AH Air Conditioner

WHEN AC UNIT IS TURNED ON WE HEAR A CLICK BUT NOTHING ELSE.... WHEN UNIT WAS FIRST TURNED ON IT WAS BLOWING AIR IN THE HOUSE NOT COLD BUT OUTSIDE FAN WAS NOT TURNING.,,,,, WE THREW ALL THE BREAKERS AND STILL NOTHING CHANGED THE BATTERIES


The capacitor in the electrical compartment has probably gone out, it will be a dual run configuration and a large round device with three terminals with multiple connections. Slao check all electrical connections. ... Goodman CKL60AR60 Air Conditioner

We have a new house and it came with central air. I have turned on the air and turned on the circuits and noticed that the outside fan on the outdoor unit was spinning round (good) now, I checked and the fan is not turning. Turned the unit on and off, still no turning and checkecd the circuit breakers...Any help please. Model is Aire_Flo Outdoor unit AFAIR12B30-A P I hear a low hum to the unit outside. I see trouble here.


First check to be sure the circuit breaker for the outside unit is not tripped. Turn the two pole breaker all the way off all the way off and then back on. If the outside unit still does not run you may have fuses in a disconnect box by the outside ... Air Conditioners

Ac problems i have a goodman ac system. i can not get it to cool one side of the house. i have it turned down to 72 and the thermostat says it is 80 in the room. i can hear the return vent sucking air and the ac unit outside is running but no cold air is coming inside. the unit outside has cold air coming out the top when the fan inside it is turning


Hello from KOOLBREEZES, this is a simle problem and easy to fix. You have 2-lines going to / from your outside unit. a SMALL COPPER -line and a LARGE COPPER line with insulations. The fat line is suppose to have moisture on it wheres it,s not insulat ... Air Conditioners

I have a goodman cpk j42 -1b ac unit on the outside and a central heat and air unit inside. the ac unit come on and runs fine but when it hit the temp the thermastat clicks and the fan outside goes of but the one inside stays running and will not turn off unless i hit the breaker. is it he fan relay at the outside ac unit?


Hello BWOOD Check the thermostat FAN button is in AUTO position not ON position.That might be it .The relay is in the blower unit but they RARELY become frozen/welded stuck on. ... Air Conditioners

What outside temperature can you not charge an air conditioner unit?when is it to cool outside to put r-22 in a condenser unit? sometimes i hear from techs that it to cool in outside temp. to charge a unit with freon,but no one has told me the range of temp.to which you can or cant service charge a unit.does anyone know the official answer?


If you need to charge a unit whe it is to cold. if you know how to un plug out dooor motor take wire off that well let head perssure go up . or you can cover up condenser that will work to good luck. ... Air Conditioners

The air conditioning unit outside is running but there is no cold air coming into the house. I hear the inside unit turning off and on but no cold air. I also smell a burning odor. I have turned off the unit via the thermostat.


If unit is going on then off within a few minutes needs service can be needing freon,outside dirty causing overheating,power supply if 220 not getting full power ,to compressor going bad ... Goodman CLQ36AR49 Air Conditioner

I HAVE DAIKIN VRV III R 410A, FROM 1 0F THE 5 INDOOR UNITS( THE ONLY ONE THAT IS IN THE UPPER FLOOR OF A MAISONET HOUSE) COLD AIR 24 T EVERY 5-8 MIN YOU CAN HEAR A SOUND FOR JUST 20 SEC LIKE THE SOUND THAT IS MAKING A TRAIN WHEN IS STOPPING ....SOUOU . THE ONLY TECNICAL DIFFERENCE BETWEEN THIS UNIT COMPERATIV WITH THE OTHERS UNITS IS THAT IN THIS UNIT THEREA ARE ONLY THE IMPORT WINDOW (BRINGING THE AIR ) THE OTHER WINDOW /OPENING IS OUTSIDE THE WALL FOR THE ECONOMY OF SPACE BEST REGARDS D


... Air Conditioners

Hello i have Carrier Weathermaker 38tkb air conditioner unit. It's about 6 years old and when i got home today, the unit itself wasn't working. Although the blower fan in the furnace inside was blowing, the fan on the a/c unit outside was not moving. I can hear a humming sound coming from it and once in a while, you hear it trying to kick in (the lights in the house even dim a bit, which is unusual), but it never kicks in. The top center of the unit is extremely hot to the touch. I've checked


The humming noise and dimming of the lights is an indication something in the outdoor unit is locked up or has failed.Check the capacitor as it may have gone bad. If the capacitor is good, then you either have a failed motor, a failed co ... Air Conditioners

My A/C outside will not run, inside a fan is blowing air (a little cooler than the 82 degrees it is in here, but not cold). Unlike all the other posts I've read, my unit outside is not making any noise. I makes a click when I turn it on at the termostat 1 time and then nothing. All this started yesterday sometime, after the remains of TS Fay left us. Help. I tried the breaker thing and resetting the 240v box thing outside at the unit. Help.


I am not an a/c expert but mine did this one time and it was the transformer I think it is called pull the panel off and look for wires burnt at connections also. BE sure you cut power off before doing this ... Carrier 38CKC042 Air Conditioner

I have a GE Zoneline 5500 PTAC that doesn't throw any heat. The electronic display appears normal during operation, I hear a clicking when the unit is turned on and the fan kicks on but it just blows cold air. The unit was set to the highest heat setting and the air filters were cleaned and unplugging and restarting but still no luck. I haven't tried using the override dip switch to bypass the heat pump, becuase there is a total of 3 of these units in our condo; one in each bedroom and one in th


Hi,\015\012Just for giggles and grins I would switch that one to coll and see if the compressor runs in cooling... that will tell you if it is the compressor or the reversing valve that is bad...It may also jog the reversing valve and get it to ... GE Air Conditioners

Central air unit sometimes comes on but after the unit outside kicks off the fan inside keeps running and the unit outside clicks and dont come back on


Hello,this can be caused by a defective capacitor, the cap helps to start the compressor and outdoor fan on the outdoor unit. Looks like a silver D size or larger cylindrical object. it will have a few wires going into the top of it. Usually they ... Air Conditioners

Air Conditioner was working fine last summer but outside fna not working. Not hearing any sound at all. I can move the fan amanually and it seems fine. There is an electrical box next to the main electrical box on the back of the house with 2 fuses in it but I can't tell if they're bad. I thecked the thermostat and it apears to be fine. The air conditioner furnce kicks on and blows air out of the registers. It's just the main unit outside that's not working.


There is a relay in the outside unit. Check for 24 volts a/c at the two wires coming from the furnace. also there may be a mouse nest in the control comartment where the relay is and they tend to chew up wiring insulation and sometimes wires get disc ... Carrier 38CKC042 Air Conditioner

Turned on AC was running fine. 30 minutes later began to hear a strange noise. Opened AC/Furnance closet & heard a sound best described as air letting out of a tire. It seemed to be coming from copper pipe. Minute later sound stopped & air was suddenly hot. As if AC was turned on fan not cold. Went outside & neither fan nor motor was running. Turned fan manually. Ran for about a minute then stopped. Outside unit was making what could best be described as a buzzing sound.


Hi!!\015\012\015\012This means that the condenser fan motor (outside unit) failed, this caused to build hi pressure and either activated a safety valve to release the extra pressure or blew a line and R22 Refrigerant escaped from system. ... Goodman CKL42AR42 Air Conditioner

Ac unit clicks outside but nothing engages fan or compressor on unit furnace still runs for heat setting and fan still blows but ac will not engage just hear a clicking was running for three days this season but hasn't ran since


Have you check the outside breaker? If its ok then you got a problem in your electrical system inside the unit probably the contactor is not engaging this is where the 24 volts from the thermostat calls for the 240 volts to run the condenser fan and ... Carrier 38CKC048 Air Conditioner

NOT COOLING I AM HAVING A PROBLEM WITH THE UNIT. I HAVE WARM AIR BLOWING INSIDE, BUT WHEN I GO OUTSIDE TO CHECK THE UNIT THE FAN ON THE UNIT IS NOT RUNNING. I CHECKED THE BREAKER TO SEE IF IT WAS TRIPPED, BUT IT WAS FINE. I WENT BACK TO THE UNIT AND GOT REAL CLOSE TO IT. I CAN HEAR A LOW HUM NOISE AS IF POWER IS GOING TO IT, BUT THE FAN ON THE UNIT IS NOT TURNING. I PLACED MY HAND ON THE TOP CENTER OF THE UNIT, AND IT WAS REAL WARM. I DON'T KNOW WHAT THE PROBLEM IS. NEED HELP


A/c unit refrigerant charge is possibly low due to leakage, call a a/c engineer ! ... Air Conditioners

To whom may concern, my a goodman central air unit has stop working. The unit will come on in the inside but the outside want. The unit is not kicking on and the fan on the unit appears to be a little warmer than usual. I click the breaker but to know change! Any suggestion?


Its likely a start up capacitor. You will need an A/C repair person to come change it. I shouldn't be too expensive. ... Goodman Air Conditioners

I have a goodman central air unit CPK36-1A. The outside fan is not running and I hear a Buzz noise.


... Goodman CKL36AR36 Air Conditioner

I have a goodman central air unit CPK36-1A. The outside fan is not running and I hear a Buzz noise.


... Goodman CKL36AR36 Air Conditioner

I have a Goodman CK36-1B central air conditioning unit. The area where the fan motor is, gets really hot but, the fan will not go on. You can hear the unit click as if it is trying to go on but nothing happens. The house is getting hotter by the minute. Checked all the connections. Everything is good. It is not an electric problem, electric is reaching the unit. Any advice is appreciated. Thanks Charlie


I have a goodman it dont get cold ck36-1b ... Air Conditioners

When my central a/c is on, I hear the unit cooling the house for approx. 15 sec. and then it sounds like the unit stops producing cold air yet it is still running. Also, then fan outside of the house turns on then shuts off while unit is on. Any solution?


Can you tell if the compressor is shutting down, and just the fan is still running? ... Air Conditioners

I have a carrier 38YCBO48300 Over the years ithas a history of eating the start Caps Which I replace myself. This time the cap was leaking so I replaced it but the unit still will not run.The blower runs but not the outside unit. there is power and I hear a click when the system is turned on if I push in the relay the unit will start. but stop when I release it. I have checked the float switch in the condenser pan Any other ideas??


You must have a bad connection from either the thermostat or inside unit. Check the wire going from the outside unit to the inside unit. Look for any in-line fuses or the fuse on the circuit board. ... Carrier 38BRC048 Air Conditioner