\015 I have an OLD Gaffer & Sattler HVAC unit installed at my home. The condenser outside has a lockout box next to it with a 60 amp 230 volt breaker - however, the circuit to the main electrical panel only has a 40 amp 230 volt breaker.\015\012\015\012On hot days, the AC unit will run one cycle fine - but when attempting to start the condenser for the next cycle several minuets later, it will pop the 40 amp breaker.\015\012\015\012Thinking that maybe the 40 amp breaker (also very old) may be weak, I replaced it with a new Square D 40 amp breaker (same as before). This did not solve the problem.\015\012\015\012So... here are my main questions:\015\012\015\012With a 60 amp breaker in the lockout box, and a max fuse rating of 60 amps on the spec plate on the condenser, can the 40 amp breaker at the main panel be replaced with a 50 or 60 amp 230 volt breaker (without burning down the house)?\015\012\015\012And...\015\012\015\012If not an under rated breaker, what else could be the problem?\015\012\015\012Boy it's hot out here! Any fast answers may just save my life (just kidding... I think).\015\012\015\012Thanks for the help,\015\012Ben\015

Answers :

The important thing is not to put in a breaker rated higher than the A/C wiring. If the breaker box is in direct sunlight, the additional heat can cause the breaker to trip before the trip-point current is reached.
\015\012
\015\012Is this a problem that recently started?
Ben,\015\012you are on the right track. To upgrade the breaker, first look at the main house breaker panel and determine if allowing more current through main breaker will be taxing it too highly (will 20 more amps exceed my main breaker limit...what is the main breaker current trip at?) Then look at the wire size leading away from the 40 amp breaker to outside. If it is 6 gage copper or 4 gage copper-clad aluminum wire, you are ok to upgrade. Any smaller wire size could be unhealthy.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

This Air condition donot put out cool air it run very hard and run my electric bill up and i not getting good result


... Goodman Manufacturing Air Conditioners

A friend of mine moved into a home with electric baseboard heat. they also have a king central air conditioning . no duck work tubed in .... question is i cannot find a filter .. do that have one? i thought all units that move air has one ....


I would check on the unit itself where the air returns, may be duct taped or have a metal plate over it ... Weather King 10AJA2501AH Air Conditioner

I have a Goodman CK36-1B central air conditioning unit. The area where the fan motor is, gets really hot but, the fan will not go on. You can hear the unit click as if it is trying to go on but nothing happens. The house is getting hotter by the minute. Checked all the connections. Everything is good. It is not an electric problem, electric is reaching the unit. Any advice is appreciated. Thanks Charlie


I have a goodman it dont get cold ck36-1b ... Air Conditioners

Hello, I recently purchased a new home which has a Nordyne model # JS58D-060KA air conditioning unit. Both times when the home was appraised and inspected, the AC worked when they provided power via a generator. Now, the standard electrical supply has been turned on and I cannot get any results. When I turn the temperature down on the thermostat I hear something kick-on in the attic above the thermostat but no air. If the thermostat temp is adjusted for heat or is disconnected, whatever is k


... Air Conditioners

This Air condition donot put out cool air it run very hard and run my electric bill up and i not getting good result


... Goodman Manufacturing Air Conditioners

We have a air conditioning unit wired into the ceiling. Does not work. Every time we switvh it on it trips the electrical switch. Not sure what size and model number it is. Want to know what size fuse goes into the air con units and any other ifo would also be useful. Thanks


Look for a swollen capacitor that is shorted out out a burnt compressor terminal. ... Air Conditioners

Where should an electrical socket be placed for a newly installed residential airconditioning compressor? The new Lennox 13 Seer air conditioning and heating unit was installed in Norman, OK, in March and there was no electrical outlet installed on the wall near the unit. Did the contractor meet regulations or should they have installed an outlet?


Not an outlet, but you should have a junction box and maybe a circuit breaker.\015\012\015\012It's not made to disconnect, so no plug ... Air Conditioners

Electrical - Air Conditioning


The important thing is not to put in a breaker rated higher than the A/C wiring. If the breaker box is in direct sunlight, the additional heat can cause the breaker to trip before the trip-point current is reached.\015\012\015\012Is this ... Air Conditioners

I need a wiring diagram for an older Tempstar model NPAHC36AK01 mobile home air condition unit with 9.6 KW electric heat strips.


... Air Conditioners

Amana Ultron 12 seer home air condition stopped working got electric to unit. checked out side fuses/ok. can anybody help. unit is only 2 yrs old.


Check low voltage or your control voltage. If your transformer is bad this will cause the unit not to work. ... Air Conditioners

We have a few Mitsubishi electric air conditioning indoor units Model: PCFY-P63VGM-A Year 2002 They all seem to be dripping internally and leaking outside of the foam


They are probably thawing. This can be the result of lots of different failures, However the most common ones would be dirty filter(s) or low refrigerant. ... Air Conditioners

I HAVE DOMETIC DUO-THERM PENGUIN ROOF AIR CONDITIONING ON RV. THE UNIT WILL RUN WHEN PLUGGED INTO ELECTRICITY BUT WHEN GENERATOR POWERED THE AC UNIT KILLS THE GENERATOR ENGINE. WHAT COULD IT BE?


What size & type generator? On start up the AC unit can draw as much as 17-18 amps in some cases, and if your generator is not designed for a quick draw like that it will die. ... Dometic Rooftop RV Air Conditioner

I am looking for electrical drawing for a LG window air condition model # LW5012


... LG LWHD1800R Wall/Window Air Conditioner

I am looking for a kind of air conditioning unit for small electrical panels( for Boiler ) that will protct the plcs from heat..is there an avilable unit?


Try to find a Mr. Slim unit on the internet ... Air Conditioners

My air conditioning unit stop working (outside unit). When I turn the unit I notice a buzzz sound comming from the unit. I have pressed the reset button on the unit to see it that would help but nothing happend. I check to see if there was electricity with a voltemeter and the unit is getting current all the way to the capacitor. I turned the power off to the unit to check if the capacitor had a charge and it did. What other things should I be checking? Also, the fand do not turn on! model numbe


Hi, what is happening is, you have power to the outdoor unit. I am glad you have a volt meter. This system is a split unit,condenser outside and indoor unit. This is what you need to check, and what the buzzing is, and why the fan and compressor will ... Ruud UAMB Air Conditioner

I have a goodman Air conditioning unit CKL49-1. The fan motor connects to the top lid. Recently the metal cracked and broke and the fan fell down inside. I purchassed a new lid mounted the fan back on to the lid. It doesnt seem that any major damage was caused. I put everything back together the way it was. When I turn it on it will only go on for a sec then a switch inside turns it off. When i looked at the electrical on the ac i noticed when i turn it on a little spark on a switch and the swit


Sounds like it is overloading and tripping the circuit breaker (that thing that pops up). More than likely when the fan fell down it stopped the blade from turning which caused the motor to overheat, melting the windings insulation which caused them ... Goodman CKL49AR49 Air Conditioner

Our air conditioning was working during the day. when one family member turned the air up from 72 to 75 she saw the screen process what she wanted and walked away. when another family member went to turn it down, the screen was off. i have a honeywell visionPRO thermastat but no air conditioning at the moment. is my air conditioning not working because the honeywell theromastat needs to be trouble shot or is it not working because the machine that produces the air conditioning itself not wor


Open the thermostat and look for batteries, 3 AAhttp://www.heater-home.com/photos/2129-5b.jpghttp://www.heater-home.com/manuals/th8321u1006manual.pdf ... Honeywell Air Conditioners

My air conditioning blows hot air only, nothing


Ok if unit is split system two piece check to see if out door unit is running fan and compressor the air coming out of the fan should be about 20 deg warmer than out door temp if not compressor not running check the capicitor to see if swelled up on ... Air Conditioners

I have a GE "AS1AH09DWF02" air condition and the remote control stop working... I have change batteries and it shows the display ok but it can't turn on the air condition. The air condition has a green light which is winking! What can I do please?


... GE AJCQ08ACB Air Conditioner

Hello! can you help me.I have air condition GREE splite system. SOme days ago when he start to work( i put heating, to warm) in some minutes stops and write on the air condition (up, not in control) H 1 Can you explane ,what it is? I have 2 air condition in different rooms one bigger then other and they make the same Thank you Yulia


Also have you cleaned your filters? ... Air Conditioners

I need to know the starting current of Air condition 1.5 HP!


... Carrier 36KCARMS Air Conditioner

Size of air condition.


Get the cubic volume of the room. The highest temprature differential. and how many air changes you need. this will give you the btu required.\015\012If this is too high, get the biggest unit that your supply can safely carry. ... Samsung AW1091L 10,800 BTU Air Conditioner Energy Star rated (AW-1091L, AW 1091L)

Hi My Danby 6000 BTU window air condition is not cooling. I set thermostat to maximum cooler level as 8 but still not cooling room. I clean all the dust with wire brush. Fan is working fine and I can feel lots of air comming through the air condition but no cool air.


... Danby DAC6003D Air Conditioner

Where are the air filters located on my 2005 Winnebago Journey 34H with Coleman Mach basement air conditioning unit (True Air residential air conditioning). I need to change them.


The filter is under the bed in rear. ... Coleman Mach 15 Air Conditioner

Kelvinator 90plus 60,000 furnace heat good. pushes little air on air conditioning. checked filter--clean- checked charge in condensing unit. ok. 2 years old. never has pushed air conditioning at all. barley trickles out of the supply air registers. could the fan not be on high speed?


The air flow you feel coming out of the vents is good on heat but not when the ac is running? ... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || www.ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.0903 seconds