I would like to have English version of manual for LIFETEC termostat med timefunktion MD 12460 MSN 5003 5510


Answers :

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I would like to have English version of manual for LIFETEC termostat med timefunktion MD 12460 MSN 5003 5510


... Air Conditioners

I have 3 central ac units for my house. 1 for the upstairs and 1 for the west side of house and 1 for the east side of house. just had a very cold night and the east side of house vents smelled like something was burning. Called the fire dept. to check out and they left with answers that it was probably the dust burning off of heater. few days later smelled the order again but a this time it smelled like wire burning this time. rest of house was warm and smelled normal. unit is off on east side


To make sure that there is not a problem with your blower test it on cool. if it runs good. then start the heater on auto and it should be okay. but still supervise the operation for about 5 mins. if you still smell something burning . then call an ... Air Conditioners

Pop-up-trailer (2000 rockwood freedom 1040 LTD) I seem to have a problem with my heater. Seems like the termostat and the propane is functioning properly. Cause when I turn up the termostat the flame is on but not for long, it shut off. So the blower is blowing cool air. Like I mentioned , I think the propane and the termostat seems to be functioning okay but just wondering if there is a censor that shuts off the flame. Can you please help. tks Vince


There is a switch if you get into unit there is a flap that acuates switch if it doesnt fully engae switch it will shut of i had same problem i bent actuator and lubed switch with silicon oil!!!switch may also be going bad!!! ... Air Conditioners

My air con shuts off after like 1 minute. (like


... Sharp CV-P09FX Portable Air Conditioner

58mvc060-f-1-14 This unit on heating has different speeds . The air conditoner blower seems to have only one and it sounds like a jet plane. Is this normal. It has been this way since it was installed in 2009. I called sears a few times but with no results. I would like to kown what can be done if anything.


... Air Conditioners

For some reason after I switched it off last night then switched it back on some time later it didn't work. It looks like it is going to start say i put it on 23 there is a star and a drip under it next to the 23 and next to that the circle with a vertical line through it. The bottom comes down like it is going to blow air and then it suddnely goes back up after about 1 minute and displays CH then 05. I have done everything I can think of including turning it off at the mains for at least 10 min


Hi, CH05 means a error code.This error code means there is a communication error between the indoor unit and the out door unit.this is usually caused by wiring errors condensate pumps connected to the inter-connecting cable.The communication ... LG Art Cool LA121HNP Split System Air Conditioner

We have a gym that is 150 feet by 75 feet and around 40 feet high, I have 2 york 20 ton heat pumps located on out side of building. CFM are 8000 a peace. when temps outside are in single digits temps in side gym never get above 40 degrees it as been like that sence it was installed. there is only 1 return vent for each unit located ground level where heat vents come in. heat is routed across sealing. seems like all heat stay up high where it comes out at, How can I get temp into the 60's Heat p


Do you have any ceiling fans in the building? Fans forcing the circulation will force the hot air down. Have you had any other professionals take a look at your problem in person?Thank you,Lee ... Air Conditioners

Carrier thermostat I have TSTATCCP2S01-B residental Carrier thermostat . I would like to use it for low temperature applications, around 0 celsius. I dont have it hooked up yet. Can I lower tepmerature on this thermostat to 0 celsius? Regards, Sead


No this t-stat is not designed for low temp ... Air Conditioners

My 1 year old Haier Room Air Conditioner HWR24VC5 will not cool. Everything runs; but when you select cool, the compressor doesn't kick in. Or let's say, the sound of the unit doesn't change like it used to. Also it looks like during a storm, the unit sucked in dirty water. Any suggestions?


Try cleaning first your unit , because this problem can be cause of dirt inside it.\015\012\015\012Hope that helps........ ... Haier Air Conditioners

I would like to know how many square feet a Model # BRCQ0421BD Serial # 990905429 Coleman Central Air Conditioning Unit will cover. The unit supply is 208-230V 1 PH 60 Hz 10.8 RLA 97 LRA.


... Coleman Air Conditioners

I would like if possible to send me the user manual of english for Air conditioner SANYO SAP-ZK22X ,to email [email protected] tanks


... Sanyo Air Conditioners

My A/C outside will not run, inside a fan is blowing air (a little cooler than the 82 degrees it is in here, but not cold). Unlike all the other posts I've read, my unit outside is not making any noise. I makes a click when I turn it on at the termostat 1 time and then nothing. All this started yesterday sometime, after the remains of TS Fay left us. Help. I tried the breaker thing and resetting the 240v box thing outside at the unit. Help.


I am not an a/c expert but mine did this one time and it was the transformer I think it is called pull the panel off and look for wires burnt at connections also. BE sure you cut power off before doing this ... Carrier 38CKC042 Air Conditioner

I own a honeywell thermostat #rth230b and I cannot seem to locate my owners manual. I would like to be reminded as to how to set the four daytime settings for the temperature desired as well as the time to change the daytime setting. The four settings show on the readout as small houses with numbers either 1,2,3, or4. The temperature limits and times for can be set so that various settings can exist for different times of the day. When I am sleeping or not home at a certain time of the day, thes


Go to honeywell.com under welcome sign \015\012bootom red box literature / image search\015\012type in model# click on arrow at right, then click on PDF file. ... Air Conditioners

A repairman has told us that we need to replace the evaporator coil on an a/c. They put in Freon and its taken care of the problem temporarily but he says that it will likely run out in 1 week due to holes in the coil. The cost is really high so I want to understand alternatives.


Hi,It is a Common Problem because of Poor Workmanship or it Rotted out.Unfortunately, Other than Replacement, there is no Permanent Fix.I could only suggest you that, if possible you could try to Find the Coil ONLINE, if available or Comp ... Air Conditioners

No problem, would like a free download of manual in Dutch or English of the Daikin FTYN35G*** Heat pump.


Manual for Troy Bilt Mulcher leaf vac 47035 4 1/2 HP ... Air Conditioners

I have the MR36TQY3f outdoor unit with 2 MW09Y3FM units and 1 MW12Y3FM indoor units! The MW12.. works great and one of the MW9... works great! When I run the 2nd MW9 only (other MW9 & MW12 off)..... the outdoor unit compressor or fan does not come on! If I run all units then ... compressor kicks on runs great, fan runs... lines get cold on the 2 good units ... nothing on 3rd unit... then I turn 2 good units off....and it sounds like the compressor kicks off and the fan will continue to run reall


After looking at the manual for the units, I believe that the system is having trouble with the number of units that you have linked. Here is a portion of the manual about multi system operation>Also link to manual:http://www.fri ... Friedrich MR36TQY3F Split System Air Conditioner

1 month old Haier 12000BTU Portable Unit LEAKS like mad!


If it has an evaporation pan to "Cook Off" the moisture, it would be putting it back into the air, where it just removed it from. This will, in time cool the room but the humidity is being returned. It is possible however, that drain from the cond ... Haier HPAC99ER Air Conditioner

I have a Carrier Weathermaker Infinity furnace model 58MVP100-F-1-20 with 3 zones and Carrier Comfort Zone II programable thermostat. I recently installed ageothermal heat pump system which includes a hot water coil in the furnace plennum. The heat pump is sized to meet loads except for the coldest days of winter - (below 0 F) - when the gas furnace is expected to kick in. My problem appears to be the Weathermaker's characteristics don't accommodate the low heat /slow response provided by


Http://www.hvac-talk.com/vbb/archive/index.php?t-85094.html here is a site i found very useful ... Carrier Air Conditioners

Rheem Air Handler will not run. This is a 2006 Rheem model RHLA-HM3617JA Air Handler. I replaced both the condenser and air handler circuit boards. I replaced the motor in the air handler.. The condenser works fine, the board flashes normal. The air handler board shows 0 volts on the X13Com brown lead,..28 Volts on the center, X13G green/black lead, 1 volt on the Bottom, Blue, X13SPD terminal. The 24VAC Terminal shows 27 volts. The 3 amp fuse is good. The transformer appears normal. I replaced


Have you hard wired your fan motor to verify that the motor and or the capacitor are good? If you do a continuity test of the motor leads(with electricity off of course) you can see if the motor has open or grounded windings. ... Ruud Handler Air Conditioner

I would like to find out how-to do the calculation for temperature different on a chiller piping with different insulation Example 1 A 3? diameter pipe x 200? lung with R8.6 insulation 70 dg F ambient temp @ 34 F entering temp what is the out coming temp. Example 2 A 3? diameter pipe x 200? lung with R 22.34 insulation 70 dg F ambient temp @ 34 F entering temp what is the out coming temp.


TRY tierling.home.texas.net/pipeheatlosshelp.htm has a nifty fill in the blank calculator.I tried the examples but required more spec info. ... Air Conditioners

E1 problem what is the remote code set on your remote? you can get it by pressing vcr/dvd the hold the set button until it blinks twice enter 990 it will blink 2x then press 1 count the blinks if it diesn't blink number is 0 then go on to 2 and 3 and 4


... Haier hwr10xc6 Air Conditioner

I have the delonghi retro fan heater. when i plug it in and turn the dial, the red light on top goes on and then sometomes the fan turns maybe for 1 minute then the fan stops. the red light remains on but it won't turn anymore and just stops responding to any movemnt on the dial except when turned to 0 when the red light goes out. I haven't use either of them in about 4 months but they worked perfectly before when i used them. Please help!!


It indicates fan motor problem .servicing urgently required too. ... DeLonghi Air Conditioners

I have a MAC 1155. The burner comes on and then goes out after about 1 minute. It will stay on if I remove the cover below the gas valve. I don't think it is safe to run it like that even though there is no heat that comes out thru the opening. is there a filter somewhere that needs to be cleaned or changed? Should I remove the unit and check for an obstruction?


Hi, I repair heaters and air conditioners for a living. No you are right, do not leave the panel off. You may need to get back to me on how this system is set up, like is it a central heating unit? Most all furnaces have a filter that goes on the ret ... Air Conditioners

Rheem Air Handler will not run. This is a 2006 Rheem model RHLA-HM3617JA Air Handler. I replaced both the condenser and air handler circuit boards. I replaced the motor in the air handler.. The condenser works fine, the board flashes normal. The air handler board shows 0 volts on the X13Com brown lead,..28 Volts on the center, X13G green/black lead, 1 volt on the Bottom, Blue, X13SPD terminal. The 24VAC Terminal shows 27 volts. The 3 amp fuse is good. The transformer appears normal. I replaced


We tried to bypass at the Tstat. Thanks for your time and interest. ... Air Conditioners

I have a new Mitsubushi 18,000 BTU Mr. Slim ceiling mounted (SEER 13.2) Comfort System. It is for one room only sized 20' by 20' by 12 ' high. The room is on the second floor, has no windows and is insulated on all sides. Like other posts I have seen, the Mr. Slim generally cools the room (even at 100 degree outside days in Texas) to 75 degrees or lower but the humidity immediately goes up within the first 1 to 2 hours to 60 to 70% relative humidity. I have complained and Mitsubishi authorize


A/C units do not remove all humidity - that is the purpose of a de-humidifier. Instead they STABILIZE the humidity in the form of condensation when the hot refrigerant is misted into cool vapor. The humidity condensate collects on the coils... thereb ... Air Conditioners