Goodman split unit that heats instead of cools

\015 I have a Goodman CPLE24-1C air conditioner that is remotely connected to a Janitrol AR24-1 (Goodman HKR-05) air handler. The unit cools very well for the first 30 to 45 minutes. Then it starts sending hot air out the air vents and the fan on the outside unit moves very slowly and the outside unit is hot enough to burn you if you touch it. Any ideas?\015\012\015\012Thanks \015\012\015\012Mark\015

Answers :

Hi, Could be a run capacitor on the fan motor. They usually swell up and or leak when they go bad. If not, the only real way to test them it with a specific capacitor tester. A new capacitor would be cheaper. Make sure that the outside unit is disconnected from power before opening it up, try to spin the fan blade by hand. If it doesn't spin freely it may need oiled if possible. See above solution. Your problem is the fan motor though so if this don't do it, It will have to be replaced. If this helps, Please rate my solution.\015\012Thanks,\015\012kstfas
It appears the nuetral wire or improper grounding if its 120V unit. 220v unit will be a loose phase off of line one or two in panel box or unit connection. If this problem is common between other units it will be a factory design problem allow a single phase simulation to occur. Loss off phase would cause motor to slow down and overheat. Once outside unit is not functioning correctly where the outside condensor is not removing the heat through the condensor, you will get hot air through the inside mini split system.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Goodman split unit that heats instead of cools


Hi, Could be a run capacitor on the fan motor. They usually swell up and or leak when they go bad. If not, the only real way to test them it with a specific capacitor tester. A new capacitor would be cheaper. Make sure that the outside unit is discon ... Air Conditioners

Hi I have a Fujitsu Split system. As of recently it has started to mysteriously started to flick over from heating to cooling on its own. It is a 2.5KW unit and heats rather well. ALl of a sudden you hear the outside unit turn over and it starts to cool instead of heating. Any reason why it might be doing this. Please HELP !!!!!!


Yes i can! The mode of operation (MASTER CONTROL)has been set to AUTO instead of HEAT. Easy mistake and very simple to fix. Press the MASTER CONTROL button until HEAT is display on the LCD. I hope that this helps I take the time to answe ... Fujitsu 18R1 Air Conditioner

Hi I have a goodman MSG-18HWN1 heating and cooling mini-split unit. The unit keeps going on and off on a cycle of about 5 minutes. 5 minute, unit not started, unit starts for about 5 minutes, stops for 5 and so on. Is that a normal behaviour ? It is a bit annoying. Thanks


Due to abnormal temp of out door.Check outdoor fan motor and compressor and also sensor.Fan motor not working- rectify/replace fan capacitor.Sensor defective-Replace itCompressor high amps-Replace running capacitor.Sensor misp ... Air Conditioners

I have a goodman heat pump (gsh 130241AA), it's 2 years old. the heat pump will not come on in either heat or cool mode. this is my downstairs unit, my upstairs unit works fine. the air flow is working fine, just nothing cool with the downstairs unit.


... Goodman Air Conditioners

Hi, I have a samsung aqv18ja series split type air conditioner (cooling and heating) wall unit. the unit was install in 02/12/2009. By "one hour heating and air conditioning". In this short time service the outside compressor has been replace, the system has check and recheck,for cooling leak. the inside unit fan motor has been change. but the problem still exists. The inside unit fan continues to run when the unit is "off" and with the remote off.


Simple, check in your remote. There is an option button "Blow". Just press it. Your unit gets completely off. Please write back if helpful? ... Samsung Air Conditioners

I have a Goodman Model number AR24-1 unit and the blower moter will not start with it turned on to fan or cool or heat. I have checked the thermostat and the unit runs outside. Just no blower. Can I jump the blower motor as I replaced the capacitor today. Hear are some numbers that may help. Part Number #15212-50 Volt 208/240 Amp 1.5 HP 1/5 No heat Kit It has a Goodman switch board # B1370735 that I can check with my meter if needed. I have checked the thermostat in the attic also. Seems like


... Air Conditioners

Hi, I have a 1.5 carrier mini split heat pump. I cant find the model number but believe it was made 2000-2003. This has the remote with the infra red eye mounted in the front of the main unit (like a tv). (There is no other controller as I have seen with other units). The unit is heating and cooling fine, however, it does not seem to be sensing the thermostat. Whether it be in heat or cold, it will turn on and run for about 10 minutes and then shut off and not come again. To get it to run again,


Hi,There are a few things that can cause that kind of problem....The unit could be low on charge and the thermistor on the indoor unit will sense the coil getting too cold and shut it down on a hard lockout....resetting the power resets t ... Carrier 38CKC042 Air Conditioner

Lg Neo plasma inverter split model s18ahn isn't heating or cooling properly. When in heating mode air con will go into defrost/preheat mode for 5 minutes and then air con will blow out air for 5 seconds and then go back into defrost/preheat mode. When in cooling mode indoor fan will pump out air but will not get cold. In both heating and cooling modes the outdoor unit will not start up and the outdoor fan will not spin. I have just replaced the main pcb board and that hasnt made a difference. Bo


... Air Conditioners

I have 3 Fujitsu heat / cooling multi split ductless units connected to one rooftop unit. Only in heating mode and only coming from the same indoor unit is a loud almost screeching/vibration sound. It can happen after the unit is on 30 mins or sometimes not until the next day. Repair techs are stumped as they don't see anything wrong and of course the noise doesn't happen when they are here. The noise is so loud I have to turn the unit off. Does anyone know what this could be?


... GE Zoneline AZ38H12DAD Split System Air Conditioner

Heating problem hello! My air conditioner stopped to heat. (there is a around 8 degrees C, outside and 16 degrees inside). It worked just fine, and now, when I switched to heating mode, there was nothing. the defrost LED ond the inside unit is switched on, but air is not comming from the unit. Cooling mode works fine. If you could please help me finding the solution for my problem. Thanks in advance. RAdan GE AIR CONDITIONER SPLIT SYSTEM WON'T WORK ON HEAT CYCLE Seems to work ok doing eve


Hi Radan, Did you get this problem solved? We have an Electrolux Kelvinator Split System and ours is doing exactly the same thing. I am struggling to find a solulution. Would be great if you can offer any advice.\015\012\015\012Thanks Nic ... Air Conditioners

Goodman AC Unit with Heat Pump - Works great cooling when switched to heat the outside unit does not come on - inside comes on and uses emergency heat? What can I check? I first checked the contactor and it looks fine, the inside thermostat had low battery voltage...replaced batteries but still not working? Any help? Thanks


Because the outdoor unit works in cooling, it sounds as though the contactor and other components outside are working correctly. The problem sounds as though it might be somewhere in your thermostat. Has the thermostat been replaced recently? If so, ... Goodman CKL60AR60 Air Conditioner

Split system outside unit won't come on for cooling, only heating


Check your filters, dog hair and lack of maintenance will definitely burden the cooling mode of the Mr Slim units. ... Mitsubishi Air Conditioners

Hi, I have a wall mount midea split a/c model- MSG-36HR that will only heat. when put in cool mode it only blow's room temp air and the outdoor unit won't run. On heat mode it works normally. I have cycled power a couple of times, changed modes on the remote numerous times and just in case, changed the batteries in the remote. The unit is about 3 yrs old. Do you have any pointers. Cheers Tom


Most heat pumps are 'fail-safe to heat'. That is: the normal position of the valve which reverses the function is in the position which provides heat. The reversing valve must be powered to switch to the cooling position.Although the ... Midea Air Conditioners

A/C need hlep with a carrier model # 40aq030-300bb. just bought a house with this unit inside but outside different unit, think its a Goodman. When turned to heat everything ok, but when turned to cool it still puts out heat. Think reversing valve is bad or switch controlling it may be bad. Not to familiar with the system and wiring diagram is gone. Somebody made a mess of the wires anyway, need some help if you have any. Thanx and... GOD Bless


Orange or O terminal on Tstat energizes valve in colling cycle. Go to outside unit jumper red to orange and see if Reversing valve energizes. If it does . Problem inside possible Tstat. You shoulf here the valve click. Have someone inside switch fro ... Air Conditioners

I have a Goodman air handler Model# PHJ042-1B Goodman unit- --------------------- R G Or Br W Y B Tstat (present wired in unit R G Blu W Y Present Hunter stat wires wire --- G Blu R Y W stat connectors G Rc Rh Y W (Rc & Rh have jumper) How do I wire new stat a pro 5000 2 heat a cool w/ 18/8 wire and have it work correctly and have the compessor reverse valve work. Pro 5000 stat reads Top


... Air Conditioners

Hi, I have a goldStar GA 1866VHR split Airconditioner, (5050w cooling and 5040w heating capacity). Today I noticed that compressor/condenser unit was still running after I turned off the aircond: from the remote control. The fan unit turned off as normal. I had to turn off the isolation switch to turn off the compressor/condenser unit. After about 2-3 hrs I turned on the isolation switch and the compressor/condenser unit came "on" stright away without the fan unit. Went inside and turned on fro


Thanks for your detailed information. But solution is very simple. The compressor contactor in out door unit. Struck. And hence, when you power on, without indoor commanding, the out door starts running. Replace same type Contactor relay ... Air Conditioners

Indoor Sanyo ductless split Model # KHS 2432 serial # 0012832, Works fan on and off functions and speeds. As soon as you set the remote to heating or cooling the unit beeps 5 times quickly and then the unit no longer responds to remote control. The blower will then run for 1 minute and then the the unit no longer will work. Power must be reset for blower operations to function again. Out door unit, has enough charge, Ambient temp 39 M#CH2432 S#0012424


... Sanyo Air Conditioners

Heat pump goes str8 to heating strips compressor does not run in heat mode pump was manufactured in 03 installed in 07 and has sat dormant till now could it be wired wrong it is a ruud split unit with digital non-programable 2-stage heat and cool t-stat


I think that you have the right idea. The wiring is probably wrong. If you can trace the low voltage wires to the air handler. make sure that the Y1 wire on the t-stat is going to Y1 on the hair handler and then to the condenser. The Y2 wire should b ... Air Conditioners

I have an LG mini split ac / heat pump system ( LAN096 ) that is only 4 months old was working great in all ways until suddenly it quit heating. I am sure it happened quickly because I was nearby when very warm air changed to cool ( unheated ) and hasn't heated since. When I shut it down and restart it the indoor fan runs right away, which is not normal and the outdoor unit will run for a minute or so then shut down and stay off. The indoor fan will continue to spin as though it is set in a 'fan


... LG Air Conditioners

My goodman unit is Blowing cold air when in Heat mode, I called the heating & cooling man and he came out and in ten minutes he got the heat working but he just disconected one of the Black wires from the Reversing Valve from the defrost board.


... Air Conditioners

I have a Goodman air and heating unit model#gsc130601bc and the problem is the unit comes on but the fan does not, also the unit gets hot and no cool air is coming out of vents in the house. What can I do to fix it?


... Air Conditioners

I have a WINIA WSH 188AL split unit. It will come on with the remote, give a green Cooling indicator light for 10 seconds then go to the heat indicator and a time delay indicator and the green cool light goes out and it never cools. What could be the problem?? and where can I get a manual with some wiring prints in it??


... Air Conditioners

GSH13 Goodman heat pump split system is running a long time in cooling mode and will not cool below 74 degrees. A lot of condensation generated. The low side pressures 78 to 81 and high side pressures are 180 to 200 psi. Energized and deenergized the reversing valve several times.Pumped down the sytem (pumped down well) and checked the flowrater for any type of obstruction. Have a sight glass on the system - will get clear then bubble up. System is in the second cooling season with clean air fil


Check sub cooling and super heat. the New ac units are very critical to charge. There is a charging chart on the inside of the cover to the unit outside. Check temp difference across coil. Should be 18 to 22 degress. If you have an ampmeter. Check th ... Goodman CLQ36AR49 Air Conditioner

Hi I have an NEC Split Air Conditioner. Model RIH6867. Power rating - 6.8Kw Cooling Capacity 8.2Kw Heating Capacity. Single Phase for 240Volt environment. I only have the outdoor unit. It is new. But missing the complete indoor assembly unit and remote. Can I substitute other indoor units to make this work. NEC no-longer supports their appliance division. Regards Ash


Hi Ash,Off the cuff, I would say no to being able to use any other indoor unit. But, with a bit of work and research, you might be able to connect 2 systems, even if different manufacturers, together. The compressor / conden ... Air Conditioners

I have Goodman combination heating and cooling outdoor unit PBB series. I am wanting to know if when the heat is on should the fan outside turn or is that only ac


If it's a heatpump, then yes the outdoor fan will turn unless the unit is going in defrost mode. But for the majority of the time a heat pump is operating in heat mode, the outdoor fan is running. ... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific