Air conditioner I have a Honeywell air conditioner unit. For the last several days it has failed to cool down to the temp I set except at night. When I came in this evening it was 87 degrees in the house. I went to the main unit in the garage and flipped the fuse buttons to off and then back on. Then I dd the same at the main fuse box for the house. (Dont ask me why I thought this would help). Now I can't get the unit to turn on at all. Any ideas?


Answers :

Yes, first turn your thermostat to the off position. Try to reset both fuse boxes again. If the ac comes back on problem solved, if not fuses and or breakers may need to be replaced.\015\012\015\012Let me know if this helps and we can go futher into why the ac is not only reaching the temp at night.\015\012\015\012Thanks

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Air conditioner I have a Honeywell air conditioner unit. For the last several days it has failed to cool down to the temp I set except at night. When I came in this evening it was 87 degrees in the house. I went to the main unit in the garage and flipped the fuse buttons to off and then back on. Then I dd the same at the main fuse box for the house. (Dont ask me why I thought this would help). Now I can't get the unit to turn on at all. Any ideas?


Yes, first turn your thermostat to the off position. Try to reset both fuse boxes again. If the ac comes back on problem solved, if not fuses and or breakers may need to be replaced.\015\012\015\012Let me know if this helps and we can go futher into ... Haier Energy Star ESA3183 Air Conditioner

Air Conditioner was working fine last summer but outside fna not working. Not hearing any sound at all. I can move the fan amanually and it seems fine. There is an electrical box next to the main electrical box on the back of the house with 2 fuses in it but I can't tell if they're bad. I thecked the thermostat and it apears to be fine. The air conditioner furnce kicks on and blows air out of the registers. It's just the main unit outside that's not working.


There is a relay in the outside unit. Check for 24 volts a/c at the two wires coming from the furnace. also there may be a mouse nest in the control comartment where the relay is and they tend to chew up wiring insulation and sometimes wires get disc ... Carrier 38CKC042 Air Conditioner

Heath, thanks so much there were 2 fuses in the disconnect box on my armstrong air conditioner that were bad not allowing the main power to get to the unit, you were right


We are glad your problem was solved, is there anything else we can do for you today? ... Air Conditioners

I changed a light fixture in the washroom and It seems that there was a line in the connection box that also serves the wall air conditioner in the bedroom. After checking all the lamo connections again and all the jumpers in the electrical panel the air conditioner seems to bet out of power. I wonder if there is a internal fuse in the unit or in the fan outside. This is an LG Neo Plasma with remote control.


Hello Check the wite connections again with a flashlight and see if a wire end broke or is loose.Check the curcit breaker panel box to see if they are all on.How did you turn off power to work on the lamp?The problem is there ,some units require 220v ... LG LS-L1210CL Mini Split Air Conditioner

I've changed out my central heat and air ,with a larger unit , after 5 weeks working fine ,now if my air conditioner ,hot water tank and stove is on along with a few minor appliances my main breaker trips , my main breaker is 150 amps the max for my box , i've heard that you can wire directly to a power meter through a breaker


No,you can not wire directly to a meter. All wiring must come through the circuit panel or sub panel.150 amps is sufficient to run what you describe. You may have a weak main breaker or loose wiring to these appliances. Place a amp meter on a i ... Goodman Air Conditioners

Tempstar 5000 This spring I turned on my air conditioner for the first time and it would not start at all... The fan did not turn on either. I turned off the main 220A breaker and puller the control fuses and put everything back and the unit started working fine. now fast forward to yesterday... house started feeling warm so I did the same thing... Tripped the breaker. Pulled the control fuses, and this time made sure I had new batteries in my thermostat. Started to work again. All was good. pus


... Air Conditioners

I have a hisense kfr-4801 air conditioner and it worked fine until a few weeks ago when I had it on to heat and it blew the fuse now every time I turn it on it trips the main fuse box breaker.


... Air Conditioners

Hi. I have an LG Neo Plasma Air Conditioner. Some time ago it started cutting out (switching itself off) and giving a C6 error message. When this happens, the remote does not work and the unit needs to be switched off and on at the fuse box. What appears to be happening is that when the unit needs to idol, this is when it cuts out. I still have some success using the cool setting, until it starts to idol. I have no success with the heat setting as it won't idol to warm up...it just cuts ou


... LG Air Conditioners

I have a Sharp portable room air conditioner model CV-P10NC. The power plug RESET button and TEST button will not click in order to check out the power plug as the unit will not turn on. They did test O.K. at first but the unit would still not come on. Can the power plug back be taken off to check out the fuse inside - or since it is a type of built in circuit breaker maybe it does not have a fuse inside ? The instruction manual states that " This air conditioner uses a fused power plug". The un


The fused9G.F.C.I.) cord you speak of is probably the G.F.C.I. built onto these units by design, can you or someone you know get access inside the unit and :Hot-Wire" the units cord and,bypass the power cord ( Just To Test the Unit)and see if it stay ... Air Conditioners

Hi All, I have a carrier reverse cycle airconditioning unit and about a week ago the digital thermostat blanked out. I spoke to an aircon repair tech and he suggested that the fuse is blown at the air handler and suggested that I can probably replace the fuse myself. My question is where is this fuse located in the carrier units, do I have to open panels or is it in a box like a fuse box in a car. I have no issues checking the fuse if I know where to find it LOL, The model of the unit is


It will be inside the unit main panel. Turn main power off and remove the main front panel. The fuse will be located on or near the fan control board. Typically they are a flat agc type fuse. 3-5 amps. The problem will be that if the fuse is blown ... Air Conditioners

I have a GE Split-Type room air conditioner model number AA1AH24EWI.I used it last summer but now it wont turn on.Have changed the remotes batteries and checked if it is sending signal(looking through digi camera to see if its sending) and still nothing works.Have turned it on at fuse box etc still nothing.is there a reset switch on the unit itself


Check power is indoor. And also for long time no use cases, please remove batteries from remote and re fix it when it is on use. Keeping with old batteries for long time with no use will affect the remote. Please check with other remote. It doesn't m ... GE Air Conditioners

I have an LG Air Conditioner (model LST243H-2). The circuit switch (in the fuse box unit) keeps switching over to off. My apologies that I'm not technical in my explanation!


Please do not activate again.Call repairman. The circuit switch trips due to:1. Compressor hing amps. 2.Any short circuit.3.Compressor grounded.By resetting the breaker without rectifying the fault will make major expenditure ... Air Conditioners

Goodman a/c j41 fan not running, turned off and on at fuse box, took a look at the box next to a/c unit and opened the box on the wall and pulled the plug and pulled the plastic panel off, there is no fuses. So i put back together and turned the a/c unit on, now at thermostat the snowflake is no longer flashing, some cold air coming out of vents, but outside a/c unit fan still does not run.


First you need to disconnect all power. Try spinning the fan blade, if it spins freely, then try moving the shaft from side to side to see if there's any side play. If not then the bearings are OK. If there seems to be some drag when your spinning th ... Goodman CKL42AR42 Air Conditioner

Friedrich air conditioner stopped running. I was trying to find what the air conditioner was causing to vibrate near the unit. I moved the power cord while the air conditioner was running, pushed the wall plug to make sure that it was tight. THe air conditioner stopped running. I am a woman with no mechanical knowledge. My instinct tells me that I might have blown a fuse or short circuited something within the air conditioner.


This is very possible. Whenever a compressor is unplugged it should rest for about 5 minutes before turning it back on. This is because the refrigerant needs to balance. Otherwise a large amount of amperage may be required to start the compressor as ... Haier hwr10xc6 Air Conditioner

Lennox Merit series A/C unit: Thermostat is set to 73 but the unit is not blowing at all. Checked the fuse box on outside unit and main box for possible power surge (Tampa Bay area - afternoon rainstorm season). After fuse reset, the unit started right up, ran a cycle for 10 minutes and stopped. This happened twice over a two hour period, but nothing since.


... Air Conditioners

Air handler fan running but AC unit is not. Reset ckt breaker off and then back on with no results. Went outside and checked fuse box near the AC unit. Inside box has two red lights with wording Line 1 fuse bad when lit and line 2 fuse bad when lit. In this case the Line 2 light is illuminated. Can you tell me what this is an indication of problem?


... Air Conditioners

I have a Duo-Therm RV Roof Air Conditioner Model 57915.622, Prod # 991731648, Ser # 84818800. It will not run. I changed the Compressor and Fan start capacitors. When I turn the unit on at the Thermostat nothing comes on. The Air Conditioner Control Unit E155095, Part # 3107541.009. The fuses are okay.


... Dometic Rooftop RV Air Conditioner

Our inside unit Coleman EB20B (outside unit Goodman GKL 49-1) keeps blowing the in-line 3 amp thermostat fuse. We've rewired the wires in the wall, rewired the contactor wires, and the contactor was broken so we replaced it. We're still blowing the fuse. Could we have reversed the thermostat wires at the contactor? Or could the short be in the Blend Air box-this box is coupled to the thermostat wires? Thanks Ken Rohm


Hi,Mark\015\012 all your wires using tape or by writing it down to ensure you will be \015\012able to hook them back up exactly the way you found them. Remove all the\015\012 wires from your board again. Tape off the ends so you don ... Coleman Air Conditioners

Air conditioner The air conditioner & fan stopped working. The fuse at the circuit breaker panel is good. Is there a fuse or reset on the unit itself ?


There is a fuse inside the control panel of the AC itself. You have to take the cover off (from inside on the ceiling) and look up in there with a flashlight to find it. It is usually a very small amperage fuse - I think a 1 or maybe a 5 amp. ... Dometic Rooftop RV Air Conditioner

Installing an 24,000btu air conditioner. The original wiring at that outlet has an double pole 20amp circuit breaker. The old air conditioner that was their was plug into an outlet box that sat on the face of the wall that had 30 and 250 on it. I had purchased an outlet that had 20 and 250 on it. The instruction for the wiring of the new air conditioner said 208/230 volts; 0 to 12amps; 20amp time delay fuse or circuit breaker. So tell me if I am doing the right thing with that 20amp and 250 volt


Yes your ok if they say the unit doesn't need to be changed in the incomimg power from 208 up to 230 volts or vice-versa,normally they classify motors as120/208/ 230 /460 volts, instead of 120/240/480 volts,but all line voltage varies in this voltage ... ACE -Air 24,000BTU Heat Pump A/C Free DVD Install it yourself Air Conditioner

My air conditioner is blowing hot air instead of cool air.. what is wrong with it? a/c is blowing warm air. i checked the circuit breakers, all okay. check both fans, all okay. i pulled the filter, just a little dirty. i pulled the main panel off the unit and checked for a dirty coil, all okay. The unit is 2.5 years old and is suspended in the air in my garage. is there a clogged drain. should i get the bleach out? please help.


Check to see if you have power to the compressor. it my be a thermostate problem... ... Air Conditioners

Have a Amana Wall Unit with Heating and Air Conditioning - Model PTC123B50AE. The unit's heater just stopped heating. The fan/blower and air conditioner are working fine. Unit says the fuses are OK. Would appreciate any guidance in fixing this unit. Thanks, NC


PLEASE CHECK THERMOSTAT SETTING +29 AND ALSO MODE"HEAT". STILL PROBLEM \012CHECK THE HEATING SENSOR IS NOT OPENED. BY A OHMS METER CHECK THE \012SENSOR. iF ANY READING IN OHMS IT'S O.KAY. ... Air Conditioners

Dometic 57915.531 Air Conditioner Blows 3 amp fuse in control box


Steve, The three amp fuse is installed in the board to protect from shorts or overloads created by disconnecting or reconnecting components when DC power is still connected to the system. If the fuse is blowing, then you more than likely ... Dometic 57915531 Air Conditioner

We have a Bryant 556a model, puron Central air saystem. The air handler unit keeps blowing the 5a fuses. I replaced the filter. I cleaned the main contactor at the compressor. It ran for a couple hours and is now back blowing 5 amp fuses. Help!!


It sounds like that contactor is the culprit. My reasoning is that after you fooled with it, it worked for a while before resuming the problem A new contactor costs about 15 to 20 bucks and it would be no chore to just hook up the two thermostat wir ... Bryant Air Conditioners

I purchased a 60-Amp Cutler-Hammer Fusible Pullout Air Conditioner Disconnect to replace my older (over 20 years) one for my AC/Heating unit inside the house. Looking for a wiring diagram as I have 2-wires coming into the box (hot) from my circuit breaker box (which I have turned off) and two wires going to the outside AC unit. Thanks. Jim


The two wires coming from the breaker box go to the terminals marked "LINE". The two wires going to your AC unit go to the terminals marked "LOAD". \015\012\015\012Hope you find this to be very helpful. :-) ... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific