"Cool" mode shuts off

\015 After running for a few minutes, the cool mode shuts off and I get a flashing "E-1" error code. If I unplug and plug in the unit, the unit starts and the same cycle happens again after a few minutes. Sincere thanks for your suggestions.\015

Answers :

An E1 error is automatically generated after the AC runs for so many hours to remind you to clean the filter. The owners manual says to clean the filter and unplug the unit, then plug unit back in and code will be reset. \015\012\015\012However, a User review stated that his code was not reset until he followed a fairly simple routine. "Unplug the unit. Hold down the power button and plug back in. Wait to hear a "beep" and then unplug it again. Plug unit in again and it should restart without E1 code."
We recently experienced a sever thunderstorm in which my unit got wet. A few hours later it shut off with an E1 error code. I simply placed the unit on its back allowing it to drain completely of fluid and plugged it back in and it worked fine

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I have a Ruud Heat Pump system. The outside unit makes a humming sound in either heat or cooling modes. The fan won't come on. In cooling mode, the compressor starts up, but them shuts off after about a minute.


Sounds like your condencer fan motor is stuck. Can you take a long rod and when the power is off to the outside unit, spin the fan blade? Maybe it will be enough to get it working again. ... Air Conditioners

Air flow indoors good.I cleaned condenser, found outdoor TXV not responding, Tested sensing bulb w/Heat&cool. M#-UFMAo36jaz 1995. In the cool mode temp. & pressure was good.But in heat mode pressures were within three PSIG of each other and compressor would shut off on high thermo. What is your suggestion


SOUNDS LIKE THE COMPRESSOR S NOT KICKIG IN OR THE REVERSING VALVES NOT KICKING IN.. ... Ruud UBHC Air Conditioner

Duo-Therm park model A/C unit MD# 39045. With the Tstat in the off position periodically I hear the compressor kick on and run for a bit then shuts off. Then turns back on again. All while in the off position. When in the cool mode the ac unit cools fine and shuts on and off fine. Could it be the stat? Bill


... Air Conditioners

Everstar mpk10cr grinding compressor I think.... Fan works fine, will kick into cool mode (elevated fan level) for a few seconds then it sounds like the compressor has a loose mount or something... sometimes it rattles for a few minutes (and cools) but sometimes it shuts the rattling off as fast as it starts and doesnt really ''cool'' or dehumidify.... Some days its works fine all day, others it just never really gets its ''**** together'' so to speak... Can users recharge the coolant themselve


Hi, I hear you , you have to keep her happy and cool!! First of all, no you can't buy R-22 unless you are a contractor and you have a certification card showing you are qualified to use freon. This is not your problem from what you are saying. If thi ... Air Conditioners

Chigo kfr-51gw/gx1a 1800btu split unit, when it is in cool mode the compressor runs for ten min , shuts down for 3 min repeatedly while the inside head unit fan still operates. I have read that this unit has a de humidlifier mode that has simular response, is there any way I can bypass this dehumidifier mode? or is that normail operation for this unit? Thank-you


Do you have a dehumidifier? ... Air Conditioners

"Cool" mode shuts off


An E1 error is automatically generated after the AC runs for so many hours to remind you to clean the filter. The owners manual says to clean the filter and unplug the unit, then plug unit back in and code will be reset. \015\012\015\012However, a Us ... Sharp AF-S85FX Wall/Window Air Conditioner

Ramsond split system ac ( 9000/12000) showing error codes P4 & P8 in cool mode . initially units operate correctly for a few minutes and then stop cooling and show the codes. continues to blink error codes after unit is shut down.


HI\015\012\015\012YOUR BROBLEM I THINK IS THE SENSOR FOR THE ROOM TEMP \015\012\015\012OR\015\012\015\012Indoor/outdoor c ... Air Conditioners

I have a chigo kfr-51gw/gx1a two piece air conditioner that runs in cool for 10 minutes then shuts down for 3 minutes and keeps repeating cycle while The indoor units fan keep running I've read that this unit has a dehumidifier mode that dose this same cycle. If this is what it is doing is it possible to stop this mode from cycling Thanx


... Air Conditioners

Air conditioner When in cooling mode, cooling unit shuts off after 10 min. with fan still running and flashes E3 on display.


I managed to find the people who supplied the unit, it was still under warranty, and they said it was the thermistors (temprature probes, they replaced both of them) It is now working perfectly! ... Mitsubishi MSH09TW Air Conditioner

Rbhc-17j11sfa blower fan refuses to shut off in heating mode when heating is not required and fan is set on "Fan Auto." But it shuts off in cooling. It's a new Honeywell programmable thermostat. Wonder why. Many thanks.


... Honeywell Air Conditioners

Thermostat ? no matter what temperature is selected, the compressor keeps running and doesn't cycle off.  compressor shuts off when just fan is selected, but cool mode just keeps chilling.  unit is six months old.


The unit doesnt blow out continual cool air, it blows out cool air for 5 minutes, then stops, and after 10 minutes it starts blowing out cool air again. The room never gets cool like this.\015\012\015\012It was working fine last year, nic ... Kenmore 73089 Air Conditioner

In heat mode thermostat set for 68 and room temp on thermostat reads 68, but unit contines to run. The air coming through vents is cool air. Unit never shuts off, runs constantly. This is the case when outside temp is 30 degrees or 45 degrees.


Could be under sized unit or fan relay on unit. ... Goodman PHKJ024-1 Air Conditioner

On start up seems to work (in cool mode) but not very well then after a few minutes the timer light (yellow) flashes & then the unit shuts down


Hi,\015\012\015\012You did not mention a make or model number, so I can only make some guesses as to what it going on there...\015\012But the most common cause of this type of problem is that the unit has a refrigerant leak and this ... Air Conditioners

My LG LAN125 mini split heat pump occasionally shuts down in cooling mode while displaying the code CA. The LG tech tells me there is no such code. When this happens, I have to cycle power off and back on to the unit. Simply turning it off with the remote does not work. Any ideas?


Wash out your outside coil and monitor the outside fan. sounds like a lockout due to dirty condenser or intermittent motor operation. Could mean condencer air problem. ... LG LS-L1210CL Mini Split Air Conditioner

Product Chigo thermopump. E4 is written on display. It won't cool the air and it shuts down after about 10min. Seems to be stuck in autostart mode


... Air Conditioners

Our York P4HUB12N08001A furnace has an A/C unit installed and we are running it in cool mode for the summer. Yesterday, my wife noticed a repeated hum from the furnace, and the house was 4 degrees warmer than it should be. She said that it would hum a couple minutes, turn off, then repeat a little later. I told her to shut it off, and I'd look at it when I got home. With the two covers off the furnace, I returned power to it, then pressed the safety switch so I could see everything happening. Th


A fan capacitor can be bad 'without' showing any visible defects - so - I would 'First" try a new capacitor, be sure to take the old one (after you've marked the wires for easy re-wiring) and get an exact replacement.\015\012\015\012Howev ... Air Conditioners

Fan runs on fan mode then shuts down when changing to cool no start up of compreesor or fan duo-therm


If it is analog, it should have fuse behind front cover. ... Dometic Rooftop RV Air Conditioner

Thermostat ? no matter what temperature is selected, the compressor keeps running and doesn't cycle off.  compressor shuts off when just fan is selected, but cool mode just keeps chilling.  unit is six months old. energy saver does not work. unit just keeps running.


I'm thinking the bi-metal is working, that's why you can hear a click, but the contacts are welded together. The bi-metal doesn't have enough strength to break the weld. Time for a new thermostat. ... Air Conditioners

I don't know which Carrier A/C model I have at this rental home and there is no manual on this unit. But the box attached on the wall upstairs has the ProgramOn Heat set at 62 and Cool set at 85. What is this ProgramOn mode and how from this ProgramOn mode that I can set to cool 75 and not 85. I can lower it to 75 but once I leave that mode it would return to cool 85 again. But i always have it on just Cool mode at 75 but i don't know why the house most often get hotter at night. Do you know w


Hello NTRINHVU You have to hit the HOLD button to keep 75 permantaly,otherwise it will go back to 85 every 3 hrs automatically. ... Carrier 38CKC036 Air Conditioner

Fan runs constantly on cool mode


Unit too large for area ... AmcorAire UCHW-H12AF2 Split System Air Conditioner

Lg Neo plasma inverter split model s18ahn isn't heating or cooling properly. When in heating mode air con will go into defrost/preheat mode for 5 minutes and then air con will blow out air for 5 seconds and then go back into defrost/preheat mode. When in cooling mode indoor fan will pump out air but will not get cold. In both heating and cooling modes the outdoor unit will not start up and the outdoor fan will not spin. I have just replaced the main pcb board and that hasnt made a difference. Bo


... Air Conditioners

I have a 8 years old window ac. It's working quite ok. I just want to know which mode is safer low cool or high cool when humidity is high but temp. is about 32-34 degree celcius. Technican advised me to run in high cool mode for some time n then switch is off, but i want long hr. running in low cool mode which is quite comfortable. Kindly advise.


Its not a mater of safety. Its only a matter of witch is best for you. If you want to maintain the temp then leave it on low temp. If you want to save money then you can switch it to power saver mode on high to bring the temp down. Hope this helps. G ... Air Conditioners

My thermostat is set on 72....but shows it is 76 in the house. I shut it off yesterday in case it was freezing up. 2 hours later, turned it back on and it cooled great the rest of the evening. I woke up at 3:00 am this morning and was doing the same thing. I shut it off for several hours, now has cool air blowing, but not as cool as it should and still shows 76. Cool flashing on the thermostat.


It sounds as thought the coils on the unit need to be cleaned, make sure it is draining, if it still freezes up after cleaning coils and checking for draining then the unit has a leak and needs to fixed/charged. Hope this helps tim ... Air Conditioners

Unit will cool for about 10 minutes and then compressor shuts off an unit blows warm air for about 10 minutes and compressor will start again blowing cool air and then compressor will shut down again and unit will blow warm air ... etc. the unit is running off a generator to cool down a 10x14 enclosed trailer and does not do the job of cooling


... Haier CPN10XCJ Air Conditioner

Frigidaire A/C FAC107P1A2 won't shut off on energy saver mode


... Air Conditioners