1st Problem: Doesn't evaporate the water. 2nd: Power will not stay on.

\015 I used to use it all the time. First problem I had that it started leaking water (big puddles). I checked the manuel to see if I was supposed to be draining it regularly and it said there was no need. After I got tired of it leaving puddles I hooked up a hose to the drain plug. That worked, just had to dump the five gallon bucket every coule days. Now the new problem it wont stay on. After running for about 10 mins it just shuts off. And you have to push the reset button on the plug. And the same thing happends. I called Soleair customer service. And they me a number to somebody's who works there's voicemail. And they wont call back.\015

Answers :

First thing to know is that most window or portable A/C units use\015\012the water from the evaporator to cool the condenser. If the \015\012condensor is not cooled down it will cause high head pressure\015\012on the Compressor causing it to overheat and shutdown. First thing\015\012is to make sure nothing is plugged which will keep the water from\015\012reaching the condensing fan, which slangs water on the condenser.\015\012If this is a portable unit it may only have a condenser and uses \015\012the water to cool it.
Do it the way he told you to!!!!!!

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

1st Problem: Doesn't evaporate the water. 2nd: Power will not stay on.


First thing to know is that most window or portable A/C units use\015\012the water from the evaporator to cool the condenser. If the \015\012condensor is not cooled down it will cause high head pressure\015\012on the Compressor causing it to overheat ... Soleus LX-120 Air Conditioner

Amana AC model MBR2000, installed mid May 2009. When outside temp gets above a certain level the AC does not cool. fan keeps running and it keeps trying but not work. When outside air gets cooler then starts to work again. Tech here twice. 1st time when AC was working - could not find problem, 2nd time when problem was occurring. 2nd time found burnt wire and replaced. Same problem started again 2 days later. AC unit is large enough for our house, is 18 Seer 2 stage. Any suggestions as to proble


Hi it sounds to me like what actvates the 2nd stage of the compressor is not turning the compressor on when the ambeint temiture reaches the point that it calls for the 2nd stage to start it may be an out door thermostat or a ambient senser and I wou ... Air Conditioners

We recently bought a MasterCool P700 evaporative cooler. We discovered that we could turn off the display light (makes sense with the large blue light lighting up the entire room at night) by hitting the power button a 2nd time after choosing selections (cool, sweep, etc.) However, it works only on an intermitent basis. sometimes, hitting the power button the 2nd time simply turns the cooler off. This feature is not covered in the manual. Please advise.


... Mastercool Air Conditioners

We are type testing a 4 Tons water coled Air Conditioner with water cooled Brazed Plate condenser which has water inlet froma 1 HP Pump form the water tank. The AC uses Copeland Scroll Compressor, TEV/Filter dryer & a sight glass. The problem is - the discharge pressure varies between 250-300 PSI & doesnt settle down.


Check that the brazed plate condenser is verical and plumb. Variance can occur when the condenser is moved out of a plumb position to a horizontal position as it affects the free condensation area when the freon gas first enters the chamber. Some dis ... Air Conditioners

My base-board hot water heat system has 3 Taco zone valves in it. One of the valves seems to be not shutting off completly when the thermostat shuts it off, and allows the zone to heat when the furnace is calling for it to heat the hot water tank (for house hot water) My question is the problem most likely in the power head of the zone valve or will I need to change the whole valve?----Thanke you--------------- Lacy Smith


No you can replace just the head no need to drain the system. Push the head in with a slight twist and it will pop off. At this point check to see if the problem has gone away. If it has replace the head, if you still have the same problem drain the ... Air Conditioners

My air conditioner evaporator housing appears to be clogged. The normal drain line goes to the sewer. When it is not draining properly, a back-up drain line coming from the same evaporator housing, drains to the pan (below the unit). Then the pan drains to a visible outlet on the roof (which signals the home owner that there is a problem). We noticed the roof drain line was draining last weekend, so we checked the pan under the evaporator unit, and it had water in it (which is not normal


If you are sure that it's not the line, you are going to need to get to the drain pan to clean it. Take the cover off (with power off) to access it. It's not that muchto get to it. Use a drill and a socket. Once you get in there you will ... Air Conditioners

Hi, I have Lennox gas furnace Model G12Q3E-82 (about 30 yrs. old). When running the A/C, I noticed there was water leaking or dampness around the bottom of the furnace. I removed the hose from the drain spout on the evaporator and noticed it was plugged and unplugged it to drain some water out of it. I also removed some water that accumulated in the bottom of the frame that wraps around the blower motor and fan wheel. I have a problem where now the blower motor runs for about 1 to 2 minutes then


Hi Todd, you did the right thing by checking the uf on the run capacitor and it is with in range , the reading is good. What is happening is with the condensation building in the pan, the blower motor has picked up some water and burned the windings. ... Air Conditioners

Hi sir i have a vokera heating boiler its water pressure is 0 and its not working i tried to open tap of cold water to increase water pressure bt it doesnt work no pressure come up can u plz solve my problem ?


HI, Heating hot water but cold house. Open-water mark on the panel to open the package when the hot water is turned off. ... Air Conditioners

I have a 2000 Coachman Class C mini motorhome. My problem is with the water heater which is a a Atwood model G6A-8E. The electronic ignitor is a Atwood p/n # MPD93257. The water heater will ignite and then go off after just a few seconds. As designed I assume after three attempts the control lock out on safety. If I keep trying for sometime the burner will finally stay on line and heat the water until it is at temperature. What should I be looking for and what repair can be made?


... Air Conditioners

Evaporator Coil I have a Goodman A/C system (2 systems...1 for 1st floor, 1 for 2nd floor). The one for downstairs is 3.5 ton. the one for 2nd floor is 3 ton unit. Installed when house was built 5 1/2 years ago. The upstairs unit has had the evap coil replaced once, and repaired a leak once - 6 months ago. The downstairs unit has had the evap coil replaced twice -and is now leaking again. Model for the air handler is ARUF042-00A-1A. Goodman part# for the coil is P140142. Can I replace this coil


Yes, just count how many pins per inch and replace with the same number of pins per inch. ... Air Conditioners

Air condioner water drain problem water in the back of unit does not evapore or drain


... Frigidaire 18500-BTU Window Room Air Conditioner ENERGY STAR LRA187M

I have a GE model # AGV14AJG1 I bought back in 06..it has a problem staying on when it's around 95degrees or hotter. I blow cold air at first then it makes a loud noise then shuts down then blows again n it repeats all day until it cool outside or I throw water on it but would have to steady throwing water on it like every 30 mins or less. Can u help?


... Air Conditioners

My bonaire evaporative cooler cycles from high to low fan speeds when set in the cool mode. It works fine at the required speed setting when just the fan (no water) is selected. It also dumps water immediatly the cooling cycle is turned off rather than holding it for about 40Min as it should. Sounds like a controller problem, but I'm not sure if it would be the touch pad or the board up on the roof mounted unit.


... Air Conditioners

Got cv-p10nc, exhaust pipe was lost, replaced with other one wich gets hot. The problem is different, the power of blowing after 10-20 minutes becomes low, and overall performance is much less than it was before. Tried to drain the water - there was none inside, tried to work only on fan couple of hours - problem still not solved.


... Sharp CVP10NC Air Conditioner

Dometic Duo therm RV a/c rooftop unit. 15,000 btu with heat pump. model 620515. age 5 years. Problem- will not always stay ON. Starts and cools fine. but shuts off within 5 mminutes sometimes.. or will run for hours and hours with no problems. when it stops, I can sometimes restart it by cycling thermostat.. if that does not work I can unplug thermostat from 12v power and then it starts when asked to. Have replaced computer circuit board and wall thermostat.. no change.


... Air Conditioners

My problem is with frigidaire air conditioner model fah126r2t. the digital electronic panel doesnt work, power button doesnt work either (no buttons work on panel). but the fan will not stop spinning when unit is plugged into ac


I am not too familiar with these systems but, it sounds to me like it may be in a safety lock out mode. Possible failures:Fusible linkon board Surge protectorfaulty circuit board ... Air Conditioners

I have an old Bosch TF 325 hot water heater. The pilot light stays on OK. When hot water tap is turned on the heater fires up but then the flames immediately start to go down eventually going out altogether after about 10 seconds. What part is casing this problem ? Can anyone help please?


... Air Conditioners

Afternoon, I have a major problem with my Dimplex DAC15HC portable air-conditioner. It either requires constant top-ups to its external water tank, or the main evaporative water tank leaks constantly, irrespective of both tanks being emptied on a daily basis. At this rate, I'll be re-carpeting the room the unit is in!! Any help would be gratefully received. Cheers, Simon


Hi SAJJF2,\015\012\015\012Its not leaking. As the fan blows air across the cold coils the water in the air condenses on to the coil. When enough water condenses it forms drops which drip out of the AC unit. In humid parts of the world AC ... Air Conditioners

Got cv-p10nc, exhaust pipe was lost, replaced with other one wich gets hot. The problem is different, the power of blowing after 10-20 minutes becomes low, and overall performance is much less than it was before. Tried to drain the water - there was none inside, tried to work only on fan couple of hours - problem still not solved.


Hi, \015\012\015\012According to your problem, your\015\012new exhaust pipe may not compatible with your air conditioner. First check that\015\012the pipe is clean enough. You may have to clean the machine or it may need a\015\012repair. ... Sharp CVP10NC Air Conditioner

Problem in the power Plug AC doesnt turn on


That means you have a short to ground somewhere in the system. They can be a pain to track down. You must have a volt/ohm meter and check each component and part individually untill you find the short.\015\012\015\012There is a small chan ... Haier HWF05XC5 Air Conditioner

I have a GE 1.5hp window type aircon which i think has a power problem. when i plugged it on the outlet it beeps like its turning on but suddenly turn of again after a minute or 20 seconds and doesnt turns on again


... GE AGQ08FB 8,000 BTU Electronic Room Air Conditioner

Unit leaking ever since i had a new central ac and heating system installed i have a problem with water leaking. the unit is on the 2nd floor and it leaks thru the kitchen ceiling which is rite below the unit. please someone help


Leakage from my central air unit from drain pan, please help ... Whirlwind FH-778 Air Conditioner

My hot water heater will not stay lit. What could be the problem and would I be able to fix it?


The thermal couple that senses the heat from the pilot and holds the gas valve in the ready condition must be bad. It is not difficult to replace. Note: When you first lite the pilot flame you must hold the button down for at least 30 seconds before ... Air Conditioners

I have a 1993 buick lesabre and my ac doesnt work causeit not get power fom the compresur how do i fix this, the mechaniac said it could be electrical problem


Hi; The biggest problems Ive seen are low freon level causing no voltage making the compressor clutch circuit complete . Also a fuse could be blown. Now You have to ask Yourself 2 questions do You have a low freon situation or do You have a blown fus ... Ruud UBHC Air Conditioner

Hello, I have a Multizone Air Conditioner that after a few minutes of being turned on, shuts down automatically. When he powers on, the unit seems to run a diagnostic that begins from 10 down to 8. Where it hits 8, it stays there, shuts down and then appears an ''E4'' error. Would like to know what seems to be the problem / what part needs to be fixed. Couldn't find anything on the internet about these error codes. Thank you.


Is the unit an Amcoraire Mini-Split System?\015\012Ifso: tech support & Parts available:\015\[email protected] ... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"