Fan will come on for heat(auto), but not for AC or set to ON

\015 Had to replace blower motor in October. Now that it is starting to get warmer I tried to run th AC. The blower fan will not come on. If I run the heater set to auto, it will work. If I turn the fan setting to ON or try to run the AC it will not. Outside unit runs fine.\015

Answers :

You have a blower relay in the furnace that's probably bad. In the heat mode the blower is on a temperature relay, in cooling mode the blower has to come on immediately so there is another relay for cooling. The green wire on the thermostat feeds that relay, so if you go to the furnace and shut the power off and find the green wire from the thermostat that feeds that relay and replace it, being careful to mark all the wires before removing them, also the relay terminals have numbers for identification.
You are not wired correctly at the fan limit switch. or the fan delay relay is bad. Find the fan relay, with the unit set to run and turned on, check for 24 volts on the fan relay from the t-stat.(should be a green wire going to it. No 24v repair or replace the t-stat wires or the t-stat.
\015\012If 24 v goes to the relay and it does not engage to let high voltage through, replace the fan relay.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Have NEC RIH-2667 Inverter Split system.I set to Heating mode,set temp to 25 degrees.The compressor light comes on.The run light flashes for about 30 seconds.Then the vent opens,the fan comes on and starts blowing out heat.Within 5-10 mins the temp on split displays starts going up.when it gets to 26-27 the run light flashs,fan stops,no heat coming out.The temp on system keeps going up to 30 degrees.it takes approx 40-60 mins to come down to 25ish the will come on again and repeat.I have an inde


... Air Conditioners

Model(MC42B-1A) The unit stoped working. Now it will not come on. There is 240v at the outside unit. When the contactor is pushed in manualy it starts and runs untill released. Filters are new, thermostat is set below room temp. Settings are on cool, fan(auto). Tried to switch fan to manual and it did not come on. Swithced it over to heat and it still did not come on. All breakers are good. I am at a loss. Why will my unit not come on and run.


Hello. It appears that your thermostat is bad. Change it and you should be up and running again. J. ... Air Conditioners

I am puzzled. Nothing was working with the Ruud unit. The fan was not coming on while setting was set to auto or on. the condenser fan was also not coming on. I traced back to the transfomer and there was no low voltage coming from transfomer though the two legs of 120v were going into the 240v and common leads. I changed the transformer with a 120/208/240 to 24v transformer and saw the same results. I thought well maybe I bought a bad transformer. I picked up a nother transformer from a


You said you have 120 vac but then you say you have it connected to the 240 v and common legs. If you have 120 v going to the transformer you should have it connected to the 120 v and common legs. Before you reconnect the transformer use an ohmmeter ... Ruud UBHC Air Conditioner

Fugitsu ART45LUAK ducted airconditioning. To heat the house I set the fan low, heat manual and thermostat 24C, the temperature keeps creaping up to 27C. The you can hear the thermostat being reached but the heat comes on agin, then agin till its really hot. Same thing happens when using the cooling setting, but in opposing temp ie set to 24 will drop to 20. If the select temp and fan is set to auto, it will heat up too much and then will then auto cool down too much like its fighting itself.


... Fujitsu Air Conditioners

When I switch the T-stat to (fan on) the blower won't come on unless I move the Fan limit up close to the 100 degree mark and then I move that limit back down close to 130-135 degree and after approx. 10 seconds blower shuts off. I'm not sure where that fan limit is supposed to be set at, it was originally set around 130-135. It's a 2 wire limit and the range is 100-140. I know the stat is sending signal, I get 24v on green term. at fan center relay. Thanks, Dave


To help you we need more info. What thermostat and what furnace or air handler. There are two circuits involved. One is the green wire or g terminal that switches the fan relay into high speed for ac. The other is the w white that actuates the fan cy ... Air Conditioners

I have an old Kenmore window unit that looks like a 72055 (control panel on top left). Although I have it set at 90 degrees and the room temperature is 75, the fan cycles on and off. How can I set it so than neither the fan nor the cooling comes until the set temperature is reached?


Most have a 'continious \012\012 mode' that operates the air moving fan whenever the unit is on, or a 'cycling mode' that operates from a temp sensor usually near the input over the evaporator coil.Look for the instruction for setting the mode ... Air Conditioners

When I set tstat to call for a/c, compressor outside comes on. Blower on furnace does not. When I manually rotate fan limit switch on furnace wall, blower comes on, blows cold air, and then goes off when I release the fan limit switch. I have a Honeywell 83251008a low and high voltage transformer, and Honeywell (I think) limit on off switch. I also noticed the 2 wires coming from the Honeywell Gas regulator are off. They were connected at the onset of the problem. I am not sure where to re


Sorry, you mean gas valve control? when you have only 2 wires, usually it doesnt matter which terminal as there,s no polarity differentiation at that locationYou should never rotate this dial by hand, you will bend the helix inside and fan will not o ... Air Conditioners

Can someone tell me why my AC won't turn on and why the fan will not come on in ''on'' position when I have set temp low and moved fan setting to ''on'' the ''fan'' word on the unit just keeps flashing. Help!


Is this on a car and if yes... what type of car. there is a relay behind the glove box on honda's that you can replace that causes that to happen. I had a 96 civic EX and that was the problem.... the next solution would be to change the fan motor. ... Air Conditioners

Burner lights, fan wont come on, fan runs on manual setting, has new fan switch set at 110


YOUR FAN ON SETTING IS THE SECOND SETTING ON THE SWITCH .THE LOWEST SETTING IS THE TEMP AT WHICH THE FAN CUTS OFF AT THE END OF A SUCCESSFUL HEAT CYCLE. THE THIRD SETTING IS THE TEMP AT WHICH THE FAN COMES ON MAYBE 140 ISH. THE THIRD SETTING IS THE ... Coleman Air Conditioners

You can set the temp for the unit to come on and it comes on and runs and cools for a few minutes then the compressor cuts off then the fan a little later. After a few minutes it comes back on and does the same thing. It never cools down to the set temp. The coils are wet but not frosting.


Is the AC set on an energy saving mode. Together with this program if the thermostat is defective the same symtoms can appear. So please check on the thermostat and replace.\012Since the compressor is cutting off the cooling does not take place ... Whirlpool ACC184PS Thru-Wall/Window Air Conditioner

I just installed a new goodman gcvc90704 today, and it didnt come with a schematic of how to set the dipswitches for the fan control, i went by the one on the door, and when the air conditioner comes on, the blower comes on extremely slow speed, and continues that way, i need to know how to set the dipswitches, all of them to go with an ssx16036, 14 seer ac, with a capf4860c coil, there was no information in the booklet that came with the furnace


Hello,Make sure the yellow wire from the thermostat is connected to the Y termnal on the blower unit control board for proper cooling speeds.The dip switches can then be set. ... Goodman Air Conditioners

Fan won't turn on. When I turned it on for the first time this summer, it won't blow cold air. I tried the different settings. The air compressor comes on, but the fan doesn't. Nothing happens with the fan only setting. I tried the reset button, using the remote, unplugging it and trying again. Any suggestions? Will it be cheaper to buy a new one? Thanks from Salem, MA.


\015\012Shut the power off to the unit, spin the fan blade to see if it spins freely. If it doesn't spin freely, (there appears to be a little drag when you spin it),the bearings are bad, if it does spin freely, then try moving the motor shaft ... Maytag M6Y12F2A Air Conditioner

I have a heil -- model NUGK100DH12-- problem is when power is supplied to it the blower fan comes on right away along with the induction blower and it does have the electronic pilot which all works to thermostat setting. when setting is reached the flame shuts down normally and I think the induction motor cycles correctly, but the blower motor never cycles off. It's on constantly. I tried replacing the fan relay to no avail and am considering replacing the timed fan controller as the next move


... Air Conditioners

Carrier ac fan works when remote is set to fan. When set to ac it come on for a few seconds then the unit shuts off. The filters are clean. I took the top cover off and there are no leaves bees etc plugging anything up.


You have an electrical short or need capacitor replacement because when you set to cool compressor tries to star but take more current then trips. ... Air Conditioners

I have installed a UPM model THM101B thermostat on my Intertherm model E3EB-015H electric furnace. I wanted the feature of turning the blower "ON" without the heating elements. I picked up the green 12v for the fan relay. Once the power is restored the furnace comes on even though the temp setting is low and the only way I can turn the furnace off is by disconnecting the green fan relay wire? The jumper has been properly set in the new thermostat for electric furnace operation.Right now I feel t


... Intertherm Air Conditioners

My central air unit blower fan doesn't come on but the outside unit comes on & the fan works with the heater and continuous setting


Check wall thermostat and wires ... Air Conditioners

I have a goodman GMS8 gas fired furnace and the customers complant is that the fan comes on to soon I Know it is factory set at34 seconds and I have it on the lowest fan setting is there anything else I can do


... Goodman Air Conditioners

Blower fan will not come on when set on Auto in heat mode.


The fan is controlled by a fan center or a stack switch. as burners light and heat up the spring sensor on the bulkhead above burners heats up and turns and a a point energizes the indoor fan if it gets to hot the burners go out on safty. sounds lik ... Ruud UBHC Air Conditioner

I have an intertherm electric furnace FEH-A020, with multispeed blower installed when A/C added. My problem is blower operation. at the end of the cooling season with fan set to auto operation the fan ran continuously. Now that I've turned the unit back on for heat the blower will only function with the switch in the on position (continuous operation), in auto mode the heating elements come on with the signal from the thermostat (Honeywell CT3400), but the fan does not. I checked the fan relay p


The model of T-stat you gave comes up as a discontinued model on Honeywell's web site, but it looks to be a manual stat that type of stat would have to be wired with a summer winter switch with electric heat, allowing it to turn on the fan with a cal ... Intertherm P3RA-048K Air Conditioner

Fan will come on for heat(auto), but not for AC or set to ON


You have a blower relay in the furnace that's probably bad. In the heat mode the blower is on a temperature relay, in cooling mode the blower has to come on immediately so there is another relay for cooling. The green wire on the thermostat feeds tha ... Air Conditioners

Domestic rooftop ac unit. Fan will not spin. From thermostat i can hear the relay click on but no fan movement. From any setting it will not come on. I can hear the compressor spool up, but no fan? Tried to free spin it and it will not move?


... Dometic Rooftop RV Air Conditioner

Have a 620765 capacitor for my Intertherm ac outside unit. There are three connections on the capacitor. 1. Fan 2. Herm 3. C I have a yellow and red wire coming from the compressor. There is an orange wire from the fan and then there's a green wire which I think is ground. On the top of the capacitor there are three sets of push on blades sticking up. Two of them which are marked Herm and fan have 4 blades each. Then there is the third one which has 2 blades sticking up which has a C next to it.


Pls connect capacitor terminal as folow\015\012\015\012\015\012 fan = connect wire come from fan\015\012 C = common -connect 1 wire from power\015\012 - connect1 to compressor term R\ ... Intertherm P3RC-048K Air Conditioner

Fan is set on highest speed but doesn't appear to be "spinning around" and little to no air is coming out of the unit


... Sanyo Split System Air Conditioner

Model 59516331G9 on the comfort control center digital screen will show temp set for a short time the show E-4 this goes back and forth fan will come and go off. The controls come on for furnace or coll but still show the same notes


... Dometic Rooftop RV Air Conditioner

I have a dometic dual-therm rooftop RV air with analog thermostat. When I set the thermostat to heat, the unit will hum but the fan does not turn and no air is coming thru vents in the floor. Then unit will blow cold air (hums and fan turns) when thermostat is on cool, but it won't turn off unless I shut it off at the breaker. What could be wrong?


... Dometic Rooftop RV Air Conditioner