Installing a admvh110 thermostat to a nordyne c3qa-036u-b

\015 I have 7 wires two not in use brown and orange,I have red to rc,yellow to Y,Green to G,white to W,and blue to C.Heat works but no air I also have a jumper on RC to RH Thanks for any help.\015

Answers :

There is usually a littl switch somewhere on the back of the tstat that you select for either gas or electric unit. You also need to go outside and see if the unit is being called to come on by the stat as well. The contactor will be drawn in if it is. If not, you need to trace your wires and make sure you have the correct wire going to cool and that can be varified by opening up the unit and looking at the terminal board.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Installing a admvh110 thermostat to a nordyne c3qa-036u-b


There is usually a littl switch somewhere on the back of the tstat that you select for either gas or electric unit. You also need to go outside and see if the unit is being called to come on by the stat as well. The contactor will be drawn in if it ... Air Conditioners

Nordyne electric furnace heats up but fan won't come on when set to auto. Is it a relay switch. Have installed a new thermostat.


If the fan runs in the ON setting then you have a bad fan relay for the heat mode.\015\012Did you install the t-stat before or after the problem?\015\012If after, you have a bad fan relay. ... Air Conditioners

Installed a new Filtrete thermostat on a new Carrier high-efficiency furnace. I followed instructions exactly. It doesn't work. What did I do wrong? Furnace was installed in December. Broom handle cracked faceplate of Carrier thermostat and rendered it inoperable. Installed new thermostat according to instructions. Connected white wire (labeled V+ on the old Carrier thermostat) to the W terminal on the new Filtrete thermostat. Connected red wire (labeled Vg on the old Carrier thermostat) to the


Thanks for the update, regarding the thermostat.Hope replacing the thermostat resolves the problem.Keep updated.Thanks.Helpmech. ... Air Conditioners

I just had a Goodman 4 ton 16 seer system instaled in my home. The thermostat that was instaled is new, but is the old dial type (not programable). At first the tech tried for quite a while to get my original thermostat for a ten seer system to work. I was told that a 16 seer system required a special thermostat. I guess my question is would it be possible to rig the new system to work with a regular old thermostat???


Here is a link to the manual for your unit. http://www.ecoairandwater.com/store/files/pdfs/g-SSX_manual.pdf\015\012\015\012Here ... Goodman Air Conditioners

A Nordyne air handler, model B3BV-030K, with 4 wire thermostat. Thermostat and AC works fine in "cool". Switch it to "heat" and nothing happens.No fan, no heat.(I have built in heat strips -resistors). I jumpered (on the nordyne circuit board-input from thermostat) from R to W. (24 volts from R to W, which should start the heater. Nothing. No relay "click" like when AC comes on. If i jumper R to Y, AC comes on ok. Does this sound like a relay gone bad on the circuit board? Or what? If relay bad,


Do you get heat when you jumper R, G & W? ... Ruud Central System Air Conditioner

I have a Nordyne MGHA-056ABFC-05 furnace. It currently uses a 624567 2 wire control board and 2 wire thermostat. Can I use a Nordyne 902987 relay control box (uses Nordyne 624625A control board) to connect a 4 wire thermostat to it?


You could use a $10 relay ... Air Conditioners

Installing 1 1/2 ton Weatherking Heatpump and ADP WAK351807P2 air handler 1 /1/2 with 7.5KW back up heat kit. Can't seem to get the thermostat hooked correctly. I understand the Weather King product reversing valve is different wired than other models. Color of wires on outside unit and inside unit don't match. Is there an easy wiring guide? I understand the R G Y W, but get hung up on the O B. Installing a Honeywell Digital non programable RTH3100C thermostat.


O energizes the reversing valve when the thermostat is set for COOL. B energizes the reversing valve when the thermostat is set for HEAT.The O/B is usually a orange or black wire.You can't hurt anything if you choose O or B incorrectly. H ... Weather King 10AJA6001AH Air Conditioner

I have just purchased a honeywell ct87n, could you please provide a schematic in order to connect it properly. I had someone install a honeywell digital thermostat several months ago, he did not tag the wires and the tenants complained that at times it was very cold and other times it wasnt cold enough. They broke the thermostat by constantly diconnecting and reconnecting it. I decided to get one that was non programable and pretty simple, I just want to be certain to install and wire it prop


G to the manufactures webpage and type in model # and look upspecs . r- red y-cool w-white g-fan .. The red should be connected to rh--rc already by a jumper wire. ... Honeywell Air Conditioners

Bryant High Efficiency Unit, runs constantly, I suspect the thermostat. Fan control and thermostat were replaced. The installer was to familiar with the installation. Could you please give me an idea of what could be the problem. Thank you for your assistance. The unit is over 20 years old. If replacement is required what would you suggest?


Any unit over 20 years is no longer energy efficient & it is past the lifespan of an AC. Get quotes from 3 different companies & go with best price with best warranty. I'm not partial to any particular manufacturer. They all get their part ... Bryant 462AJC021BA Air Conditioner

Model FC24B3XN1H. Modulating Echelon 60k btu. Fan runs constantly but no heat. Was installed 9/09. When turn thermostat off, fan still runs, have to shut off at furnace. It has never been a hot heat, installer said that is normal?? Used air couple days this week, was fine. We then turned furn off at thermostat as it was not needed. Turned heat on late yesterday afternoon & problem started. Left furn power off for about 15 minutes, but would not reset. Easy solve?? Is it supposed to be a 'cool' h


Hi,The fan running constant and the unit not firing is usually an indication that the high limit reset has tripped. And yes... these furnaces will run a cooler air... that is one way they get better efficiency...Also the ... Coleman Air Conditioners

I installed a new honeywell rthl111 series in Oct. 2012. I wired the blue wire to the RC because that was how the old thermostat was wired. The heat worked all winter but when I tried to change over to cool nothing would work. I checked the schematics online and realized I should have installed the blue wire to the B. I checked the fuse in the power panel and saw I had blown it. I changed it and rewired the thermostat the correct way. I tried again and still neither the cool or heat will work. A


... Goodman Air Conditioners

Wiring instruction diagram for nordyne 903992 thermostat


... Air Conditioners

I'm tryingt to install RTH2410 honeywell thermostat for a central air/gas heat system. I accidentally discarded the old thermostat, because I thought the honeywell would be easier to install, but nothing comes on. It has B, R, W, Y, G wires Any tips


\015\012Call 1-800-468-1502 for wiring assistance.\015\012You probably have the wrong wire on the R terminal. Make sure that the wire on the thermostat R is the same wire that is on the furnace R terminal. ... Honeywell Air Conditioners

I have a Rheem Gas Furnace with an old analog thermostat (Wires conneected to terminals R and 4 for the thermostat). I went to install a Rheem digital and programmable thermostat and it indicated that it would not work for that wire configuration (Instructions indicated that the thermostat would not work with wires to the #4 thermostat terminal). Is there a setting on the furnace circuit board I can change, or is there a digital, programmable thermostat one can use on this unit - Model RGDJ 12EA


If you have 2 wire at thermostat Terminals at furnace that the thermostat wire attach to should be R & W if your new thermostat has R & W terminals is should work, an easy thing to remember is the red wire on R the white wire on W. If 4 wire ... Air Conditioners

Purchased VisionPRO 8000 series model TH810U1003 digital programmable thermostat from Amazon on line to replace my old analog. My furnace company maintenance person was unable to get into the installation menu. It was not installed. Later, I managed to get into the installation menu and set the date and time but not all of the installation menu was available to me. I called Honeywell Support and they would not tell me how to get to the hidden installation menu items. They told me I would ha


The stats come with installer set up instructions inside the box. always do! i have used them always to program stat. go to a home store and as to look at a stat and see the instructions. find the installer setup info and make a copy. there are up ... Honeywell Air Conditioners

LENNOX HS26-048-3P Installing Honeywell wifi thermostat. C terminal on control board was connected to X on the old thermostat. The X terminal wire on the old thermostat is connected to the C terminal on the control board. I used this wire to connect to the thermostat C terminal and now the compressor fails to come on. The slow flashing lights indicate the thermostat is asking for cool and the fan comes on, compressor does not come on.


... Air Conditioners

Hi The old thermostat broke down and the AC technician bypassed the thermostat on our external Brivis Buffalo. I have a new programmible Honeywell Pro 8000 Thermostat, however when the electrician installed it. It still is not being regulated by the thermostat? How do I remove the bypass of the thermostat? Hope you can help Neil - Canberra


Well, how did he bypass the thermostat? Is it just a wire? First turn off the power to the unit and then simply remove the bypass by cutting it out or unscrewing it. I'm not exactly sure what he did, but if you take a picture and post it here of t ... Air Conditioners

I have a carrier 38YKC036300 heat pump with an electric furnace. I am attempting to install a new bryant T6-PRH thermostat http://www.catalog.bryant.com/wcs/proddesc_display/0,,CLI1_DIV42_ETI4641_PRD1583_SIT70,00.html. The wires dont exactly match up with my old existing thermostat. My existing thermostat has the following connections: W2, C, R, G, E, O, and Y. My new thermostat has Rc, Rh, W/W1, G, Y/Y2, C, O/W2/B, Y1. Please tell me which wires go with which terminals on the new thermostat. P


Old Tstat New Tstat\015\012R Jumper Rc & Rh\015\012E W/W1\015\012G G\015\012Y Y/Y2\015\012C ... Carrier 38CKC036 Air Conditioner

I am installing a Honeywell tl8100a1008 that has a Rh, Nc and W slots with two wires. My current thermostat has two wires into the box. The whites are connected to each other but not to the thermostat. Then the one red wire from the box is connected to the thermostat and the two blacks from the box are connected to the black from the thermostat. I tried the red to the Rh and the black to black. The circulator came on but te furnace didn't . I reversed an nothing. Help


... Honeywell TL8100A1008 LineVoltPRO 8000 7-Day Programmable Hydronic Thermostat

My digital thermostat has shut off after a power failure. There is absolutley no display appearing. I pulled the thermostat off thinking maybe the batteries were no longer working but came to find out that the thermostat does not have batteries. I then went and bought a brand new thermostat that does have batteries for the display but when I properly installed the new one, the display worked (of course because of the batteries) but niether the heater nor the airconditioner comes on when I tried


What you have is a 24v control circuit problem. There is a transformer in the air handler ( inside unit ) you will have 220v on the one side and 24v on the other. If you have 24v from transform there is a small fuse on the pc board that could blow du ... Carrier 38CKC042 Air Conditioner

I installed a new colman mack thermostat in my camper witch has a colman ac unit now ac unit runs 5 min then shuts off for 3 min then starts again and keeps doing this . so I by past thermostat and it will keep runing and cool down camper good that way do I have a bad thermostat or the wrong one part number on ac unit is 7330-730 part number on thermostat is ap7862


If it is a programmable thermostat you can unhook thermostat and when it comes on select 3 instead of 1. As it sounds as though it is short cycling this happens in older houses with drafts. Hope this helps Tim ... Coleman Mach III Air Conditioner

My digital thermostat has shut off after a power failure. There is absolutley no display appearing. I pulled the thermostat off thinking maybe the batteries were no longer working but came to find out that the thermostat does not have batteries. I then went and bought a brand new thermostat that does have batteries for the display but when I properly installed the new one, the display worked (of course because of the batteries) but niether the heater nor the airconditioner comes on when I tried


Check inside the air handler for a small 3 Amp fuse or wire that may have come off of a terminal. ... Carrier 38CKC036 Air Conditioner

We recently had Marley Double line break interrupter Thermostats installed as we could not turn our old thermostats "off". The lowest setting was 5'F. The heaters are in our cottage and when we set the thermostat at the lowest setting, it was still too warm and our heating bills were very high. With the Marley thermostats the temperature is controlled by "comfort zones" instead of individual degrees on temperature control dial. I am not sure how to control the temperature. Is temprature lim


Hi zone controlled thermostats are controlled normally by a master control stat that is wired ( linked ) to each zone. If you had them installed, they should have left you with the sequence of operation to explain to you how these stats work, and wha ... Air Conditioners

Thermostat Connection ________________________________________ I just purchased a rheem rqpm series 4ton packaged heat pump and a honeywell pro th4210d thermostat. I had 15 kwatt heat strips installed in the heatpump as I live in norther florida where the temp might drop to 20 degrees occasionally. I am unclear as to how to connect the thermostat. The wires coming from the heatpump unit are red, yellow, blue, green, white, and brown. The thermostat terminals are as such: E Aux Y G O L R B


Jumper E to Aux, OR B + O, G--green, R----red(power), & C--------common. w2---------white, Y.....Yellow and finally the Brown-----------PRCrossed my fingers too & go for it. worst is a warning hum &/or sparking one one terminal whic ... Air Conditioners

We just purchased a brand new Goodman 4 ton 15seer heat pump, model #AEPF4260TX5N4472#-- with a Honeywell thermostat controller,model#0836. The installer is having trouble with the fan not cutting off when it meets the set thermostat temperature. The fan keeps running, even if you unplug the green wire from the thermostat, or if you totally unplug the thermostat, the fan still runs. I am thinking that he has one of the wires wrong. HELP!


If you turn the power off and then back on does the fan stay running then. It is possible that the wiring is incorrect but it could also be a faulty fan relay or limit. If you disconnect the power when it is running and then turn it back on and the f ... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || www.ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.0696 seconds