Honeywell thermostat T8400c started flashing, heat/cool was off. Display flashes all icons (heat and cooling icons, temperatures, everything) and on the oppposite flash, the setpoint is displayed. The fan comes on when turned to ''ON'' but heat or cool does not when in ''auto''. The compressor can be turned on outside at the switch, but appears to have no freon. Heating & cooling worked within 2 weeks prior to this issue. Any help would be greatly appreciated.


Answers :

Based on the simplicity of this particular t-stat, I really think that it is bad and needs to be replaced. They do not make this particular model anymore. I have included a link to the operators manual for the stat. Good luck!
\015\012
\015\012http://customer.honeywell.com/techlit/pdf/PackedLit/69-1491.pdf

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Honeywell thermostat T8400c started flashing, heat/cool was off. Display flashes all icons (heat and cooling icons, temperatures, everything) and on the oppposite flash, the setpoint is displayed. The fan comes on when turned to ''ON'' but heat or cool does not when in ''auto''. The compressor can be turned on outside at the switch, but appears to have no freon. Heating & cooling worked within 2 weeks prior to this issue. Any help would be greatly appreciated.


Based on the simplicity of this particular t-stat, I really think that it is bad and needs to be replaced. They do not make this particular model anymore. I have included a link to the operators manual for the stat. Good luck!\015\012\ ... Air Conditioners

Cool air comes out when the heat turns on. When I switch to Em heat, warm air comes out. Over the summer the air worker great, however when I switched to heat on the thermostat, cool air came out. Why?


Check the following. 1. Your setting temp must be higher +3 than room temp. 2. Check heating sensor.3. And also heater element.(If it's reversal valve, checke RV is working) ... Weather King 10AJA3601AH Air Conditioner

I have 2 heil heat punps (manufactured 1989), a 3T for the lower level and a 2.5T for the upper level. The 3T unit functions normal. The upper unit functions normal if each spring, when switching from heat to cooling, the technician adds 4 pounds of freon to cool properly. In the fall the tech must draw out 4 pounds of freon for this unit to heat properly. The outside and attic units are a matched set and the expansion value in the attic unit has been replaced. There's no leaks and several


Hi,\015\012\015\012To properly trouble shoot this there is much more information needed....\015\012\015\012The exact model numbers of the indoor and outdoor units...\015\012The line set sizes and the lentgh of the line s ... GE AJCH10ACB Built-In Room Air Cool Unit

Hi guys, I try to solve this problem i have with my AC unit American Standard YCC048F. Short: The heating and cooling are ok, the only problem is the fan doesn't turn off even if heat or cool turns off. Some times even if i put the thermostat is on off the fan starts running. I try to find a relay for the fan but i don't know what can be the problem. Please help, for now i am switching on/off the unit to have it run. Thank you. Costi


If the unit has printed circuit board the relay maybe in it which has probably welded contacts, must change the pcb then or try tapping it, it might help or even, try off and on power at circuit breaker it migt reset the pcb. ... Air Conditioners

Hi, I have a goldStar GA 1866VHR split Airconditioner, (5050w cooling and 5040w heating capacity). Today I noticed that compressor/condenser unit was still running after I turned off the aircond: from the remote control. The fan unit turned off as normal. I had to turn off the isolation switch to turn off the compressor/condenser unit. After about 2-3 hrs I turned on the isolation switch and the compressor/condenser unit came "on" stright away without the fan unit. Went inside and turned on fro


Thanks for your detailed information. But solution is very simple. The compressor contactor in out door unit. Struck. And hence, when you power on, without indoor commanding, the out door starts running. Replace same type Contactor relay ... Air Conditioners

My intertherm heat pump has freon but will not heat is it posible that the reversing valve is stuck in the middle and will not let it heat if so where can i get a new one. My heat pump cools good and when I switch to heat the lines to the coil inside are very hot but coil is not. Is my coil stopped up and if it is how is it cooling?


You can't replace a reversing valve (must remove ALL refrigerant first), unless you are EPA certified and have the equipment to recover the refrigerant and to braze the old valve out and the new one in. That said, it's probably an electrical problem ... Air Conditioners

I have a Lennox pulse 21 furnace. It will not turn on when I turn it to cool or heat. I checked the main computer module and the LED light is off. I had reset the furnace by using the switch next to the furnace, and this will not turn on the light. Is there anything else I need to check before I call a service tech to look at the main module? The switch to turn on and off the furnace with the removal of the bottom door may be bad. Is there anyway to check this?


The switch you are talking about can be checked. Turn power off to unit. Disconnect wires on both terminals of this door switch. Next use a meter that will show Ohms or just connectivity to see if switch is closed when pressed all the way in. You cou ... Air Conditioners

My Towerchron 2000 timer appears to be faulty. It is about 20 years old but has always worked well. The problem is - the central heating will often not come on without the hot water. In the evening when the hot water switches off, the heating turns off. I have to turn the water on again to keep the central heating on. The room thermostat is high enough (18-20C). I suspect the timer is faulty and needs replacing.


... Air Conditioners

Indoor fan motor continue to run even if the thermostat is in auto position with the cool and heat switch in the off position. The furnance don't have a fan on and off switch in the furnance like most. The only way to turn the fan motor off is to turn off thr high power switch. I change indoor fan relay but the problem still exist.


Try this, disconnect the fanwire (green) on the furnace, if it shuts off then the hot wire from the thermostat is touching the green wire or bad thermostat. Thank-you-very-much! ... Intertherm Air Conditioners

Our Furnace doesnt seem to be working correct. We an: Air Pro BGM075128 and is Natural Gas. It will turn on when we turn up the thermostat.. but we never get any heat through the vents. There is a switch on the side that is "on" and one that is "fan". If we turn on the "fan" only cold air gets blown through. It looks like this is for cool air. So, if we leave the fan off and the "on" swith on, we get the furnace firing up, but no heat ever comes through the vents. I tested out the thermo


Sounds like the blower motor is not working, if the furnace is actually lighting up and the burns are ignited. You should set your thermostat to auto, as if it is on fan then the fan runs all the time until you take it off of fan. I am a little confu ... Air Conditioners

A/C turns on and cools but Heating system does not turn on when switched fron a/c to heat. All I hear is a click form the heating system.


Depending on whether you have a gas or elec. heating system it could be a fan control module or a heat sequencer. It's not the thermostat since it is clicking calling for heat. It's not the blower motor because it comes on d ... Amana Air Conditioners

I've installed a Hunter 44550 thermostat. When I programmed it to cool and turned it on, the heat came on. I then switched the two wires I had running between the RH and RC switch and now nothing comes on: not the heat, not the fan, not cold. I know I just have the wires mixed up, but am not sure which ones to switch. I have a 5 wire setup.


Do you remember how the wires were hooked up before replacing the thermostat?\015\012Do you have make and model information for both your air handler and your outdoor unit?\015\012Is this a heat pump or straight air conditioning?\01 ... Air Conditioners

I have an electric furnace and heat pump that will at times blow only cold air during the heating season. I have checked the filter and don't believe that to be a problem. I usually have the temperature set to 74 degrees. When the outdoor temp. is extremely cold the axillary heat indicator will be on and still no heat. I can turn the heat pump off by switching to emergency heat and will get some heat from that but not as warm as I think it should be and even that will at times only blow cool


You are losing operation to your heat strips.\015\012\015\012In heat pumps, there is a secondary heat source. Usually electric heat strips. (Sometimes a gas furnace, this is known as a "dual fuel" system)\015\012\015\012The he ... Carrier Air Conditioners

Reversing valve Model: PHJ030-1A Seral: 9705062008 The reversing valve is not reversing to heat. I found a small hole at the condenser coil, with oil residue around the "U" shape joint. When the heat stop, the condenser froze up. I think the a/c part will continue to cool with low pressure. Could low freon keep the reversing valve from switching. Reversing valve need more pressure to work. I check coil, the ohms is 17.6, and I do have 24 volts going to the coil, but I did not check it in cool fo


The first thing you need to do is fix the hole in the coil. It will only get worse no matter what you do. The reversing valve is controlled by the thermostat, then to the defrost board, as it has a timer, sensor ... Air Conditioners

Amana PTH153A35AB when I turn the switch to ''fan only'', it works. When switch turned to heating or cooling the fan cuts out and nothing happens. What is the issue?


You may have a bad thermostat ... Air Conditioners

Reset button for Ruud Achiever 14 heat pump/AC compressor? My Ac/heat thermostat was blowing fan on and would not turn off. I switched it off at the circuit box, and bought a new thermostat RTH221, wired it and it would not blow cool air when on cool nor warm air when on heat. Called the 800 number for Honeywell and tech said I had wired it correctly, to check outside and see if the compressor was running. It was not. This Ruud unit is only 8years old so I'm wondering if a reset button has


... Air Conditioners

We live in southwest Florida. Our HVAC system consists of a air conditioning system with heating coils when it is cool. Yesterday morning we tried the heat nothing come on. Later in the day I tried the air nothing. I tried turning in just the fan nothing. I just checked the breaker I have power where the wires are connected. I went out to the outside unit and pulled the cover. Pushed in a spring loaded plastic switch the fan on outside unit works and shut off when I released the switch. But noth


Hello. Sounds like you do have power. That spring loaded plastic switch is a 24v contactor. It pulls in when energized. If you push it in manually everything shoud run normal. Ck your 24v transformer. On one side (feed) you should have 115v or 220v ... Air Conditioners

A/C need hlep with a carrier model # 40aq030-300bb. just bought a house with this unit inside but outside different unit, think its a Goodman. When turned to heat everything ok, but when turned to cool it still puts out heat. Think reversing valve is bad or switch controlling it may be bad. Not to familiar with the system and wiring diagram is gone. Somebody made a mess of the wires anyway, need some help if you have any. Thanx and... GOD Bless


Orange or O terminal on Tstat energizes valve in colling cycle. Go to outside unit jumper red to orange and see if Reversing valve energizes. If it does . Problem inside possible Tstat. You shoulf here the valve click. Have someone inside switch fro ... Air Conditioners

Sharp Air Conditioner AC09RLCSYS isnt cooling properly. Very moderate to low cold air from unit. At one point small bits of ice came out of indoor unit when on auto cool. Unit was switched off immediately and then turned back on after a few minutes with no additional problems, however still is not cooling properly. Unit is only eight months old. First used for cooling with no problems and great cold air, then for heating during winter. Now back to cooling and not getting the cold air like p


Unit may be freezing up if blowing ice crystals. Let thaw 24hrs try again. Make sure condensation drain line is cleaned out. ... Air Conditioners

We gave a Goodmn Hertz 60 Phase I heat pump - installed this summer....worked great for cooling..now that temps are dropping we are needing heat. When we turn it on it comes on but never heats. Think it was not programmed to switch to heat....is that something we can do?


If you changed the unit but didn't change the thermostat it is possible that the thermostat that you have will not work with that unit. I see that the unit you installed is a heat pump, you may have a straight cool T-Stat. If you put the T-Stat in th ... Goodman PHKJ048-1 Air Conditioner

Goodman GSH130301AB heat pump with Braeburn 1200 multi-stage thermostat - both less than 1 year old and installed in new construction. Heat can be set at 60, fan on AUTO, with room temp at 70 and heat will kick on and stay on. When this happens, turning thermostat to OFF does nothing - system continues to blow heat - and I can only shut it off by flipping the breaker. This only happens now and then - typically works fine. All wiring appears to be correct though reversing valve for cooling is


The reversing valve wire needs to be on the o terminal.nothing will be on the b terminal on the thermostat ... Goodman Air Conditioners

I have a GE Zoneline 5500 PTAC that doesn't throw any heat. The electronic display appears normal during operation, I hear a clicking when the unit is turned on and the fan kicks on but it just blows cold air. The unit was set to the highest heat setting and the air filters were cleaned and unplugging and restarting but still no luck. I haven't tried using the override dip switch to bypass the heat pump, becuase there is a total of 3 of these units in our condo; one in each bedroom and one in th


Hi,\015\012Just for giggles and grins I would switch that one to coll and see if the compressor runs in cooling... that will tell you if it is the compressor or the reversing valve that is bad...It may also jog the reversing valve and get it to ... GE Air Conditioners

Turned on the a/c for the first time this year and no fan. The compressor turns on but no fan. The fan works when turned to heat and t-stat cranked up. This is a BDP CO. 2085C02135. Is there a relay or limit switch that only works with cool?


Depending on the thermostat you have, there may be an issue there. Some stats have a subbase that controls the fan for AC. I would like to know the model of your stat ... Air Conditioners

I have a Goodman Model number AR24-1 unit and the blower moter will not start with it turned on to fan or cool or heat. I have checked the thermostat and the unit runs outside. Just no blower. Can I jump the blower motor as I replaced the capacitor today. Hear are some numbers that may help. Part Number #15212-50 Volt 208/240 Amp 1.5 HP 1/5 No heat Kit It has a Goodman switch board # B1370735 that I can check with my meter if needed. I have checked the thermostat in the attic also. Seems like


... Air Conditioners

American Standard unit quits cooling. unit is running but it does not cool. Can turn it off overnight and it works the next day. It then will work for a few days and the problem re-appears. Suspect low Freon ? What do you think?


Pls it can be also check may need cleaning or a bad contact ( wires connection) due to vibration ... American Standard Air Conditioners