Fan motor comes on, however, when a/c is turned on, breaker pops

\015 The fan motor appears to work ok when only the fan is turned on, however, when the a/c is turned on and the thermostat is set below room temp....the outside condensor starts momentarily and then everything stops and the inside fan breaker pops. every thing stops running...?\015

Answers :

If the unit is working fine in heat mode and in fan only mode, you have a short in the wiring going to the ouside unit. If it were a fan relay, then everytime the fan came on the breaker would trip. But either way, there is a low voltage short taking place in the unit. If the compressor was bad, the indoor unit would run fine and would only blow the breakers to the ouside unit. I had a unit last summer that did the same exact thing. After I replaced the control wiring to the outside unit, everything worked like a charm. Good luck!

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Fan motor comes on, however, when a/c is turned on, breaker pops


If the unit is working fine in heat mode and in fan only mode, you have a short in the wiring going to the ouside unit. If it were a fan relay, then everytime the fan came on the breaker would trip. But either way, there is a low voltage short taki ... GE Air Conditioners

I have a 2002 year model trailer, it has a Duo Therm Quick Cool High Efficiency by Dometic. Because the fan motor would not start by itself, it popped the breaker after a couple minutes the first time I turned it on this year. I took the top off the unit and give the fan a little spin and it would then run. Once again after a few minutes the breaker popped. I changed the capacitor for the fan but it does the same thing. Could it be the armature in the motor causing the problem? Any sug


Does the fan turn freely? Some oil might help but it sounds like you need a new fan motor. ... Dometic Rooftop RV Air Conditioner

Have a Ruud AC unit the problem I have after installing a new condenser fan motor when I throw the circuit breaker the unit will not turn on but when I push the contacts on the contactor in manualy the fan will come on but the compressor will not.what do I need to do or order to make this unit work ? I did turn it down to 74.Can you help ? THANKS


The contactor engages from low voltage power from the thermostat as does the outside condensing unit. You may have blown the low voltage transformer or have a loose thermostat wire. Check line voltage(220 volts) to the transformer. Check load voltage ... Ruud Central System Air Conditioner

Rats ate wires in rv carrier 13.5 ducted ac. Replaced all chewed wires. fan turns on runs a few minutes When compressor kicks, Lights in trailer flicker and breaker pops In house. I have a 30 amp outlet installed jack on my house to plug trailer into. Breaker does not always pop In trailer. However there Is no ac what could be the problem? trailer mckenzie starwood bunkhouse 29 ft. It's not even 2 years old. Any advice would help. Blue wire was chewed the worst. I believe It runs from the copaci


You need an electrician be careful ... Air Conditioners

I have a Rudd AC unit Model UAND 024 JAC After installing a new codensor fan motor when I throw the circuit breaker the unit will not turn on but when I push the contacts on the contacter manualy the fan will come on but the compressor will not. need to know what I need to do or replace to make this unit work ? I did lower the temperature to 74 THANK YOU


The contactor is equipped with an overload relay and needs to be reset for the contactor to work. Press the reset button on the overload relay to reset it. It is usually orange or white colored button. But the biggest problem is the compressor not wo ... Air Conditioners

No A/C My unit will power on and the fan works, however when I turn it to the Cool mode I can hear a click in the unit, the cool light comes on for 5 seconds or less, then it will click again and the light will flash 9 times. The warranty on the unit is 4 years however only covers parts, labor is $90 per hour......Is it just a fuseable link/circuit breaker?


It seems that that the overload of compressor is tripping on and off, either your compressor overload is defective or the compressor itself ... Danby DPAC8399 Air Conditioner

I have a Sanyo Split System the indoor unit is a KHS0921 and the outdoor unit is a CH0921. When i first turn the indoor unit ON the fan will run for a few minutes and then go off. The outdoor unit never comes ON when there is a cll for cooling. The only way to get the fan to come ON again is to turn the breaker OFF and then back ON. The Operation loght will come ON when the fan is running but it will start flashing when the fan goes OFF. What should i look for?


... Sanyo Split System Air Conditioner

After pulling the unit out of storage and starting it up it appears that the fan motor is stuck and will not turn. Popped a circuit breaker


You can spray penetrating spray or maybe wd40 on motor end bells and unfreeze it, but the motor may not last long with crudded bearings... or it might ... Air Conditioners

Amana heat pump emergency heat comes on but blower will not start. The call for heat comes in and the heating element(s) glow red for a few seconds and then there is a "click" and the heating strips de-energize. The blower fan motor doesn't come on, however the squirrel cage fan spins freely. The heat pump stopped working several years ago, but I just used the emergency heat option for heating solution. The squirrel cage fan motor was replaced about 3-4 years ago.


... Air Conditioners

Breaker breaks When my Dometic roof a/c compressor comes on during a regular cycle, it sometimes pops the breaker. I replaced the breaker but think there must be some sort of timer in the unit that allows some time to go by before the compressor comes back on. If I reset the breaker and turn the unit back on immediately, it pops again. If I wait about 5 minutes it will run ok. The amps are ok. Help.


This unit may have an internal overload mounted on top of the compressor. You would have to get to the\015\012compressor to find out and it maybe faulty. That may\015\012explain why the compressor comes on later on, this\015\012over ... Dometic Rooftop RV Air Conditioner

The compressor is working but the blower fan does not come on. checking the fan motor, the shaft that turns the fan can not be turned by hand. it seems like the motor is frozen.


Look for mud dabber nest on the fan blade, the blower wheel, on in the motor itself. Use pliers to turn the motor shaft. It should get easier after a few turns. Use your hand to rotate the shaft until the shaft is turning freely. You may need to ... Dometic Rooftop RV Air Conditioner

I have a tempstar 2000 heat pump approx 5 years old. The condenser fan blades will not rotate/operate; however, I can hear the motor hummming. When the unit is off, I can rotate the fan freely. When the unit is turned on, the fan sticks. Can anyone assist me with a DIY type fix until I can have it serviced? I think I have the same problem. The unit that I have is model CA3036VKA1 (Tempstar). I changed the motor. The old motor has 3 wires. It has a red,black & brown. The new motor(GE-5KCP39LG )t


I think this is a double problem post,so I will answer the top first.\015\012The fan capacitor may be bad or the motor it's self is seizing up and will need replaced.\015\012 \015\012Second portion of ... Air Conditioners

Turned on AC was running fine. 30 minutes later began to hear a strange noise. Opened AC/Furnance closet & heard a sound best described as air letting out of a tire. It seemed to be coming from copper pipe. Minute later sound stopped & air was suddenly hot. As if AC was turned on fan not cold. Went outside & neither fan nor motor was running. Turned fan manually. Ran for about a minute then stopped. Outside unit was making what could best be described as a buzzing sound.


Hi!!\015\012\015\012This means that the condenser fan motor (outside unit) failed, this caused to build hi pressure and either activated a safety valve to release the extra pressure or blew a line and R22 Refrigerant escaped from system. ... Goodman CKL42AR42 Air Conditioner

Not as much heat coming into house as was before,went to heater unit which has 2 60amp breakers on unit and while running turned off top breaker and came back upstairs but did not feel any difference in heat temp, went back to unit and turned off bottom breaker which turned of all heat plus blower motor. what is my problem?. thank you


First what type of heat do you have and if you can find the model # it would be helpful. Also if you have filters check them. ... Air Conditioners

Have Ruud Airconditioner model UAND 024JAZ when I turn unit on the compresser and outside fan motor come on but the airhandler fan does NOT. If I switch to the heater unit the fan in the airhandler comes on and off as it should. Why does it not come on and off when the AC is on ??? Thanks


The fan in the heating mode is on a differnt relay. So the fan relay for cooling is bad. Or if it a newer unit it could be a control board that has failed. But would need a model # of indoor unit to determine that. ... Air Conditioners

I thought i smelled the ordor of burnt wire coming from somewhere in the house, which I could not figure out where it was coming from. I tried to regulate the therostat and found the a/c would not come on. So i turned off the unit for a few minutes to turned it back on and all i could hear was a loud humming sound of the motor, but no air were coming out of the vents. The outside fan is moving. I wonder what could be the problem.


Sounds like a siezed up blower motor inside your furnace if you were running your air conditioner with out the blower motor it will turn everything into a block of ice at your indoor coil you need to let this thaw out \015\012i would ... Air Conditioners

I have a 1993 Model SRHF48U01A (The 0 might be a O (zero) When the thermostat calls for cooling, the inside unit (fan) starts up and continues to run but the outside unit wants to start (it comes on for a second and then trips the breaker that is located behind the outside unit. I can turn the breakers off that are inside the house and let them stay off for a short time and then reset the outside breaker and then turn the inside breakers on and the unit starts and continues to run until the te


Well the trouble is surely at the compressor side. Dont know what kind of repair man you invited. He should have atleast diagnosed the problem. Following can be the causes\015\012\015\0121. Capacitor is slightly faulty (As you said). If t ... Amana Air Conditioners

I have a 561c central air unit. I just replaced the fan motor and capacitor 6 days ago. The unit ran great for just that long now the fan won't come on and the outside unit is hot to the touch, I can assist the fan and it starts and runs great until it reaches the thermostat temp. When it turns off it won't come back on. Is it the start relay switch?


Sounds like you need another capacitor since it will run if you turn it by hand to get it started. If you have a clamp on ammeter check the current draw on the fan motor. ... Air Conditioners

I have a dometic dual-therm rooftop RV air with analog thermostat. When I set the thermostat to heat, the unit will hum but the fan does not turn and no air is coming thru vents in the floor. Then unit will blow cold air (hums and fan turns) when thermostat is on cool, but it won't turn off unless I shut it off at the breaker. What could be wrong?


... Dometic Rooftop RV Air Conditioner

Furnace will not light burners and blower motor doesn't come on, but exhaust fan comes on immediately when turning furnace on. Turned on A/C to make sure blower operates and it does. The combustion chamber door says there is a red button to reset inside, but the only thing I can find is like a thermistor with maybe a button on it and it is not kicked. What should I try next?


The reset button should be a small round red button that you just push in to reset. If the induced draft motor comes on as soon as thermostat calls for heat then the next thing to check is the ignitor. It may be a hot surface or spark ignitor.It shou ... Air Conditioners

My wife turned off our A/C units acouple of weeks ago while we were away on vacation. Not they are both acting up. The fan is turning and moving air through the exchangers outside, the little red pressure switches are not tripped and the fans are moving air through the ducts inside as well. However, the air is not coming out cool enough to drop the house temp from either of the units. I tried the thermostat reset buttons, checked my filters, (they're clear) and my cooling coils are not iced over


Looks like the compressor is no getting ON.Check thermostat . Bye pass the thermostat and try. Check compressor relay. Compressor capacitor. If thecompressor running and there is no cooling, check the current consumption ... Air Conditioners

AC unit outdoor fan motor does not come on as it should, but if I manually start the contactor relay / coil by pressing and holding the manual button on it the fan then comes on and goes off with the thermnosat; however, the air stays cool (that is blowing outside) and warm inside. The large capacitor does not look bad though.


It sounds like the contacts of the contactor are burnt/pitted. When this occurs, it can allow enough current to operate the fan motor but not enough to operate the compressor. ... Carrier 38CKC036 Air Conditioner

I've had this maytag 10000 btu slider casement air conditioner for approx 3 years. its installed in a window & has been used possibly 10 times. the fan motor comes on, however there is no cooling whatsoever coming out, I know it takes about 3 mins. for it to kick on, however after a hour or so its sitll not cooling, Any ideas what to check for? Thank You.


Check the thermostat, does it open and close (electrically)? \015\012\015\012In the past three years, has the unit been cleaned? If the coil is plugged with dust, there may have been serious damage to the comressor. \015\012 ... Maytag 10000 BTU Slider Casement Air Conditioner

A/C worked fine last year. Turned it on for the first time this year and the outside unit does not come on. The inside unit fan works just fine. I checked the circut breaker and turned on and off. No change. I revoved the cover and do not see any burnt wires or any problem. Not sure what to do next. I have a meter... what should the voltage be where the power comes into the unit at L1 ect. please help... thx


Check and see if you have 24volts at the contactor outside.if you do you have a bad contactor. if you don't take the tstat off the wall and take a jumper wire and jump out R to Y on the t-stat if i ... Air Conditioners

AC unit had a power surges from the electrical companny and now it only turns on the unit from the breaker panel but no response from the remote control. The fan comes on only when breaker is turn on.


If the outdoor unit does not come on, there is a fuse box mounted on the wall or near the unit. Try changing out the fuses and see if it comes on. Depending on the disconnect box, the fuses are hard to see. You may have to remove a plastic cover to s ... Amcor Aire AMS241HX Split System Air Conditioner