Goodman forced air gas furnace not firing

\015 No heat this morning.When I opened top of unit up the Hot Surface Ignitor was glowing & main blower fan was running.Power vent not running.24vac supply good.Fuse OK.Red light on circuit board illuminated & steady. (no trouble flashes)Gas valve will energize if 24vac applied to it (with circuit wires temp. disconnected!!)Main Blower fan is running continuously & ignitor glowing with no heat request, (thermostat wires unhooked.)My guess is bad Auto. Ignition circuit board.If circuit board is problem, is there an online source?No air conditioning unit installed\015

Answers :

If your power vent moter is not running you should not have have glowing ignitor.Frist the vent moter must close an air prove switch in series with the idnitor .seems you have a stuck air prove switch.Its the one with a hose attached

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Goodman forced air gas furnace not firing


If your power vent moter is not running you should not have have glowing ignitor.Frist the vent moter must close an air prove switch in series with the idnitor .seems you have a stuck air prove switch.Its the one with a hose attached ... Air Conditioners

I have a sears forced-air furnace that automatically lights. It will go on when I first turn up the thermostat. It burns and produces heat for about 10 to 15 minutes. Then the burner goes out and it starts blowing cold air. At that point it goes into an endless cycle of the igniter firing, no gas being supplied to the burner, and then igniter firing again. I have changed the filters... Larry


You probably have a bad Thermo-couple . It is a copper looking rod that sets in the flame of the pilot lite It also has a copper wire that goes to the main valve and connects with a 1/4-3/8 nut or a metal clip. The purpose of this part is to tell th ... Air Conditioners

Need schematic for ge gas fired forced air furnace model blu055e936b1


... GE Air Conditioners

PLEASE ...schematic for a trane gas fired forced air furnace model blu120E936B1


... Air Conditioners

I am trouble shooting a Bryant Hi-bred system that uses an air cooled heat pump with high efficiency gas furnace for backup and low ambient operation. How does the system decide whether to use the air cooled heat pump or the gas fired high efficiency furnace. It appears to be outdoor air temperature related, but I can't find the setpoint for it. The main zone Bryant thermostat appears to control the system, but it doesn't always bring the backup heat if the heat pump doesn't function.


If you are using honeywell vision pro 8000 t-stat you need an outdoor sensor program on t-stat would have to look up ... Bryant Air Conditioners

Our Furnace doesnt seem to be working correct. We an: Air Pro BGM075128 and is Natural Gas. It will turn on when we turn up the thermostat.. but we never get any heat through the vents. There is a switch on the side that is "on" and one that is "fan". If we turn on the "fan" only cold air gets blown through. It looks like this is for cool air. So, if we leave the fan off and the "on" swith on, we get the furnace firing up, but no heat ever comes through the vents. I tested out the thermo


Sounds like the blower motor is not working, if the furnace is actually lighting up and the burns are ignited. You should set your thermostat to auto, as if it is on fan then the fan runs all the time until you take it off of fan. I am a little confu ... Air Conditioners

I have a 1985 Bryant central air Furnace model 395BAW048095 with a White Rogers 36E gas valve. The flue is metal and there is a fan within the furnace to create a vacume at the base of the flue pipe conection that turns on when a call for heat comes from the thermostat at startup to ignition. The spark fires but no gas is released by the valve for the pilot to lite. Added information: The blower fan is set to continually run, I replaced the pressure switch (306621) and the limit switch (HH12ZB18


... Air Conditioners

Furnace problem I Have a 2005 Montana3295RK with a duo-therm air conditioner,suburban sf35f furnace and a dometic thermostat with remote. The problem lies with the furnace. It will not turn on, and in the rare event it does it will not turn off unless you either pull the fuse, turn the switch to the off position on the furnace or turn the gas off at the tanks. I can force the furnace to come on by pulling the fuse and then putting it back in and the thermostat does not have to be in the on posit


The problem is most likely in the control module of the roof air unit. Dometic uses the thermostat to activate and deactivate a relay in the control board of the roof ac unit whiich is just visible when you remove your air intake screen. The two blu ... Dometic Rooftop RV Air Conditioner

My son has a Goodman Manufacturer Corp Heat Pump/air conditioner. Forced air I believe. The air conditioner quit. A repairman indicated that in order to replace the air conditioner the furnace will have to be replaced also. The air conditioner unit outside is Model No. CPE30-1-AB. Any thoughts?


I don't see any reason to change the furnace unless it's an air handler and not a furnace with a coil on top or bottom. And then, the only reason to change the inside unit when you change the outside unit is because it's a R-22 system and your going ... Goodman CKL30AR30 Air Conditioner

I have an AMANA GUCA/GCCA/GULA gas fired warm air furnace. When the unit turns on the the blower turns on igniter glows but when the relay kicks to supply gas I get no gas. Is this a problem the the integrated control module. Is there a fuse associated with the module.


... Amana Air Conditioners

Goodman GKS9 gas furnace: (1): Dusty room above basement furnace unit near cold air return. (2)) Furnace filter doesn't fill up or collect much.


... Goodman Air Conditioners

My Amana Gas Fired Air Furnace (80) failed to come on with warm air. Blower works but cold air only? Is there an obvious problem here?


If you can look into the viewing port and see if there is a light blinking write down how many times it blinks. Next remove the access panel from the furnace. On the wiring diagram, you will find a diagnostic code chart. Match up the bli ... Amana Air Conditioners

I have a Goodman Furnace model#GDS80703AXBC.The unit is one year old and ran fine until the gas got shut off accidently outside at the meter.Unit was cycling with no gas for 2 days.we turned the gas back on and the unit is showing one light blinking for over cycle trys.The unit did eventually start up but it does not fire up after each time the thermostat is calling for heat.The unit has been running like this for about 10 days now.I have replaced the Diagnostic computer, glow igniter,flame sens


The only part not replaced so far is the gas valve. Because the gas valve is getting power does not mean it is opening.You could also have gotten trash(corrosion/scale) in the valve orifice and or the burner orifices.Is there a drip ... Goodman Air Conditioners

Amana gas fired warm air furnace. Blower (fan) works fine when thermostat set simply to "fan". When selector is moved to "heat", burner fires nicely but teh circulatior blower fan does not kick-on. Any suggestions?


Either bad run cap on motor or bad blower motor ... Amana Air Conditioners

Have a Rite Boiler Model No. 325 Serial No. 8419237 has dual draft with a balanacing damper and forced air exhauste. Problem: gas pressure is correct, but low fire first 2 burnrers fire but the other 12 does not. So i have gast going out to exhaust email me at: [email protected]


If it has only one ignition source then it sounds like a crossover is plugged or maybe one of the burners is not set correctly. If it has multiple ignitors then I would suggest that a circuit board or relays are faulty.Either ... Air Conditioners

Goodman GMS81405DNA. 3 Blinks indicate a Pressure Switch Problem. Usually water in the hose, but not this time! When I remove the hose, and draw air through it myself, the furnace fires. The Recirc Motor feels like it's BLOWING air out, and not drawing it in! Any ideas? Mark


Id say your flue exhaust pipe is restricted. ... Air Conditioners

I have american standard freedom 90 gas furnace that continuously blows cold air and doesn't shut off until we unplug it. we have changed the ignitor several times to no avail. it still will fire up in the beginning, then click off and when it clicks back on, it blows cold air and continues blowing until i unplug it. very cold.


The igniter must have failed. replace the igniter. ... American Standard Air Conditioners

I have a carrier natural gas forced air furnace that stopped working, it won't light. It is displaying three error codes: 31; 11 & 13. The filter was changed, but the blower fan has been sqeaking for a while and I had to temporarily disconnect the combustion air. I'm guessing one or all of these things are the cause, but don't know how to reset the panel.


To reset the panel disconnect the power for 5 minutes and put the power back on.If you need more help troubleshooting please post back ... Carrier Air Conditioners

Intertherm MGHA-075BFC-01 gas fired furnace - air runs but heat will not fire. Pilot light is lit, no click tho from thermostat when increasing temp. What or where is the most likely culprit? Thanks, KevinH


Probably the limit switch is open. ... Air Conditioners

Air pro gas furnace model #g8c07512mub11a The combustion fan comes on the igniter glows red the gas fires in the burners for 5 seconds the it shuts down. Any suggestions would be helpful.


I would suggest you change the flame sensor. It will be a small diameter probe extending into burner compartment,usually over or inbetween burners. If your furnace is lighting the burners but they won't stay lit That Is what I would do first.. I also ... Air Conditioners

Furnace not firing: I have a Haier model HGA 080 N3H furnace that is blowing air but not igniting the burners. This was happening this time last year, but the problem was a dirty filter that was making it overheat right away. That is not the case right now. The filter is clean, the gas line is open, the led light that indicates problems is functioning normally, the ignitor is switched to on, all cables attached between the ignitor and the burner are solid, and the thermostat is telling the h


... Haier Air Conditioners

My Goodman GMS 90703BXA gas furnace started making higher then normal pitch sounds yesterday. The noise seems to come from the forced draft fan and it only happens in say 3 out of 10 starts so far. The fan vibration does not seem excessive. Is this a sign of an upcoming problem? I've had this furnace running without problems since mid 2004.


The fan in my gas furnace is making a loud screeching noise! Is it going to blow up or is the motor/fan broken? ... Air Conditioners

Humidifier on gas, forced air furnace, won't work. carrier furnace. humidifier is aprilaire model 440.


Is it the humidifier or the furnace which is not responding? Or both? Thermostat/control module model? ... Air Conditioners

I have Rudd hot air gas furnace. The ignitor sparks and lights the fire but as soon as the ignitor goes off the fire goes out, flame light doesn't go on. What could be the cause?


Hi, Check the flame sensor next to the pilot. It should be a ceramic rod with a metal tip that rests in the pilot flame. It may be dirty. Clean the tip with steel wool real good and make sure it is in the pilot flame good. This will cause that condit ... Ruud UBHC Air Conditioner

Have a 1984 trane heat and air gas furnace unit ..always freezes up...repair people always come and put freon in it over and over.. and of course blows out pipe. Had new outside unit put in this is a "goodman" in 1996. ...still freezes and repairmen come over and over again to repeat same thing.. The inside coil is in attic.. behind a wall. no one has gone up in there since we've lived here in since 1992.. is this the problem?


Could very well be.\015\012Seems to me when they replaced the outdoor unit in 1996 someone should have found out that there was a leak when a vacuum was supposed to be pulled and held on the existing line set and and the unit in the attic for a ... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || www.ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.1599 seconds