Furnace lights but flame goes out almost immediatley

\015 The burner comes on, you can see a flame but just as fast as it comes on it goes out. I've changed the thermostat and that didn't help...\015

Answers :

It's the limit switch that is located on the fire box. There are two wires that go to a disk about the size of a penny and in between the two wires is a very small button. This button resets the limit. If this switch is tripped, the flame will immediately go out to protect you from carbon monoxide poisoning and possible fire. If it will not reset, then take the two wires off and use another piece of wire to jump the switch. If it lights, then you know that the limit is bad. If not, then there are a few more to find. There could be 2 to 3 of these on the fire box and there is usually one near the inducer or on the inducer.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Furnace lights but flame goes out almost immediatley


It's the limit switch that is located on the fire box. There are two wires that go to a disk about the size of a penny and in between the two wires is a very small button. This button resets the limit. If this switch is tripped, the flame will ... Weather King 10AJA1801AH Air Conditioner

I am looking to buy a house in forclosure. It has a Tappan gas furnace about 9 years old and there is no manual. Can you advise as to whether the following problem is serious and estimate what the cost of repair will be? Exhaust blower is always on; red light on circuit panel is constant. Then gas flame is ignited and burns for a couple of seconds; yellow light on circuit panel comes on. When blower motor begins, gas flame goes out, yellow light goes out, and red light repeats sequence of 2


HelloSounds like the flame sensor is bad.Or possible photo eye.Worst case would be a new circut board.Anywhere from $100.00 to $300.00 depending.Legally a home you purchase has to have a heater that works and a hot water ... Air Conditioners

I have a ruud furnace/airconditioner Model:UGPN-07EAMER, Serial: FU5D302F390401344. When the thermostat calls for heat, a little motor (within the furnace itself) or something kicks on, the burners ignite a few seconds later, then the blower starts. It's at this time the flame goes out and the blower is just sending cold air throughout the house. There are two green lights (power and ok) lit normally and the orange(ish) blinking "flame" light on the main board. When the flame goes out, the


Hi, this motor is the inducer motor, which is the first thing to start on a call for heat. Everything seems to be going through its sequence of operation just fine, but then shutting down on a safety. Look on the panel for a chart that should tell yo ... Air Conditioners

My bosch 21E (infinity style) hot water system has an intermittant fault where the flame does not appear to be able to stay on (or properly light). Once water is started to the unit I can hear the ignitor go on and the fan start (and I think I can gear the flame light too) but then almost immediately it sounds like the flame goes out and tries to reignite. It never actually lights properly though, just continues the same ignite-fan-flame out-ignite cycle. After a while (a day or so) it seems to


Moisture is getting into circuit board, usaully this sealed in a jell which keeps the board protected from any kind off dust,moisture etc which would comprimise the thinking side off the unit. a bosch engineer should be able to do a diag ... Air Conditioners

I bought a forclosesure this summer and not all that familar with the furnace in the guest house. I'm use to having a furnace with a pilot light(yes, it was 34 years old)now I,m trying to get a goodman furnace going. I know it was sitting around for atleast 2 years. The home inspector said everything works.The model number is gmnt040-03. The gas is turn on the outside line. When I start it she begins to hum and then the ignition light goes on. then a blowing noise but then I get no flames-after


Hi,A few things to check...Is the gas line valve on at the unit....follow the gas line back a bit sometimes the gas valve can be out of view.Also check the gas valve in the furnace... it may also be in the "off" position.... ... Air Conditioners

I have Rudd hot air gas furnace. The ignitor sparks and lights the fire but as soon as the ignitor goes off the fire goes out, flame light doesn't go on. What could be the cause?


Hi, Check the flame sensor next to the pilot. It should be a ceramic rod with a metal tip that rests in the pilot flame. It may be dirty. Clean the tip with steel wool real good and make sure it is in the pilot flame good. This will cause that condit ... Ruud UBHC Air Conditioner

The yellow light on our Gibson furnace is flashing. The furnace lights but does not get up to the temperature and goes off only to kick back on a little later and do the same thing. I know this is a low flame warning. We recently had a piece on our gas meter replaced. Could this be the problem?


... Gibson Air Conditioners

Furnace lights and then goes out. Could this be the flame sensor?


... Air Conditioners

I have a GMP100 gas furnace. I need the diagnostics table that provides the meaning of the status light states. I get flame for 20 seconds and then the gas is shut off and LED on control board blinks 3 times. The flame sensor looks clean. I wired the flame sensor lead to ground as a quick test but then the gas goes out in 6-7 seconds. Any thoughts?


Hi!!! you just answer your question.change your flame sensor cleaning it wont work..\015\012\015\012\015\012 ... Air Conditioners

Carrier furnace ,burner not staying on after 4th try shuts down completely.cleaned the flame sensor but noticed the 3rd and 4th burner has a delay in lighting by the time the 4th burner lights and hits the sensor burner goes off.do i just need to clean the orifices? how and with what.thanks


Remove them and scrub them with a wire brush. \015\012On a call for heat, the 24 volt thermostat sends a signal to the control module. The control module will indicate a call for heat with a light on the control either blinki ... Carrier XHB123D X/Y Series Heat/Cool Air Conditioner

I have a Ruud 90 plus gas furnace model UGRA-07EMAES it has a yellow and green light on board, everything comes on in perfect order, but after the flames have going for about 10 secs it goes ploohhh! And the flames are gone. Then the fan kicks on.... Any help?


... Air Conditioners

I have a goodman GMNT gas furnace Propane it lights off I have a blue flame for about 3 seconds I hear a click on the circuit board and the flame goes out this is doing it constantly. could you please help me  Danny


Hi!!! If the flame turns on then off and on then you should change your flame sensor on the gas furnace..YEs flame sensor is shorted..The flame sensor is located by the valve burners it has one wire and is white..Good luck.. ... Air Conditioners

We have a Carrier forced air furnace and it constantly recycles itself by igniting and then it heat sensor element and the furnace flame burner comes on as it should burns a short period goes out and then empties the heated air from the chamber, and then repeats the same system over and over. However; the heating element stays red hot and the LCD light constanly flashes a code. We have had atleast three different techs to come out and they only replace the heating element, and the last tech sand


Hi,\015\012\015\012First off the problem has nothing to do with the filters...\015\012\015\012The problem is that the circuit board is not getting told that the flame is present and is shutting the gas back off.....then it tri ... Air Conditioners

My ventless gas heater has an uneven flame with orange tips, the flame toward the outer edge is higher than the flame in the middle, and also,when I light the heater, it doesn't just give me a piolot light, it lights the row in back on low, flickers, and has an unstable flame and then you turn it to low, and it goes out until you turn the regulator knob a little higher, for more heat and it goes out completely, all except the piolot light


This sounds like your gas valve is weak. An orange flame has to much gas and not enough air mixture. Have you trie to ajust the air mixture. If it won't ajust then you will need to replace the valve.\015\012\015\012I hope this helps. ... Air Conditioners

Hi I have a hot air furnace and just replaced the board ith a new one from a gmp 100-3 to a b18099-13 I connected the wires as the directions said to but the staus light goes on continuous but nothing happens no flame or anything there is a terminal FS do I have to take the blue wire off the edge board and connect to this terminal its the only terminal that has nothing connected to it


What is the model number of the unit you are installing this on. ... Goodman Air Conditioners

Furance lights and goes out after ten seconds does this three times.bought a new flame sensor worked two days same thing again.goodman furnace


If it isnt the flame sensor make sure the furnace ground wire is hooked up.If the ground is bad it cant sense flame. ... Goodman Air Conditioners

Flame on furnace lights for about 30 seconds then goes out but blower still blows


Inside your furnace their are two probes one is inthe shape of a paper clip the other is a straight probe this one needs to be taken out and cleaned using emery cloth be sure not to touch this probe after cleaning or you will have to replace ... Ruud Air Conditioners

I have a Ruud Silhouette 2 gas furnace. The draft fan starts, ignitor then glows, main burners light and go out after a few seconds at the same time the ignitor goes off. I have replaced the flame sensor and seen no change. Thanks


I had the same problum with my heater to no end. I thought it was the th-sat . still don't know if it was . one of the sencers I was feeling, and the disc snapped in and the heater ran but on heat. turn off power and unplug the power cord and removed ... Ruud UBHC Air Conditioner

Jan 10, 2010 - i should probably give some more info.. it's a ruud silhouette II gas furnace that had been giving me problems with the furnace starting up and shutting down immediately.. i solved this by cleaning the flame sensor rod, although i didn't replace it.. now it starts with a very weak flame and will only light one burner sometimes.. when it does light with all 4 burners they seem to kind shrink in size every few seconds like the gas isn't steady.. this is a new issue, is it possibly


It is possibly related to the flame sensor giving a week signal to the gas valve. You really nee to have the gas pressure checked and the flame sensor checked if you have a multimeter that checks miliamps you will know if it is the flame sensor. You ... Air Conditioners

I have a Carrier Weathermaker 8000 furnace. it will not light.I tested the igniter on my upstairs furnace and it will glow and light that furnace. I can manualy light the furnace with a match. flame sensor works and furnace will run till thermostat turns it off.wires look good. Controer maybe???


If you're sure the igniter is good and the controller is sending voltage to gas valve to open, but not to the igniter then, yes, the controller is bad. The only way to know for sure is to remove the igniter's molded plug from the board and test volt ... Carrier XHB123D X/Y Series Heat/Cool Air Conditioner

SW6DEA GAS HEATER UNIT FLAME WILL NOT STAY ALIGHT ! Switching gas water heater unit on inside the RV, the red light comes on and approx 6 to 8 seconds later ( normal time cycle ) the gas flame lights up OK but goes out again after approx. 6 to 8 seconds with the red light going out at the same time. Leaving the unit switched on inside the RV, after a further 6 to 8 seconds, the red light comes back on automatically and repeats the start up cycle over - again without success. *4 times unsucces


... Air Conditioners

The Coleman Mach thermostat in my 5th wheel blows its 2 A fuse a couple of times today and am trying to figure out what is causing this. Please help. I am unable to get the furnace to run even with a good fuse in the thermoatat. When I bypass the thermostat to run the Atwood furnace (red tied to white wire). THe furnace blower comes on and the burner sounds it lights for 5 seconds and then goes out. 15-20 seconds later it reignites and goes out and continues to cycle -- the blower motor


Hi\015\012\015\012Its blowing fuses because of short circuit inside the coleman mach or due to two wires being shorted with each other. You'll need to open up your thermostat system to look for the short circuit and also shorted wires.Ple ... Air Conditioners

Gas furnace lights then goes right back out


You shouldn't remove it. be certain that the flamerod is positioned so that the flame blows directly across it. it must be in the flame. use steel wool or fine sandpaper. dont overdo it. you just want to remove the carbon buildup.this is if the flame ... Air Conditioners

My mother has an intertherm furnace that all of a sudden started to throw cold air. When we restart it, it will work for about 20-30 minutes then the flame goes out and only blows cold air.


... Air Conditioners

My blower on my furnace works but I have no flame for heat. If I stick a lighter in where the gas comes through it kicks in but when cycle is finished it doesn't. I think my pilot light is out and do not know where it is located. Can some one tell me where the pilot light is located on the honeywell furnace model "The Dependable 92" GMPN060-3


I think you have a bad thermocouple. The thing your lighting should be the pilot(otherwise you got a bigger problem and you should definitely call someone). The thermocouple senses heat so if it's bad it won't send the signal to the gas valve to ope ... Air Conditioners