In thermostat when turn on to cool fuse goes blown


Answers :

You have a low voltage short from the inside unit to the outside. This is the only thing that will blow the fuse. Check your wiring, it's shorting out somewhere and usually it's outside where the wires leave the wall and enter into the unit. When they are exposed to uv light, the insulation deteriorates.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

In thermostat when turn on to cool fuse goes blown


You have a low voltage short from the inside unit to the outside. This is the only thing that will blow the fuse. Check your wiring, it's shorting out somewhere and usually it's outside where the wires leave the wall and enter into the unit. When ... Goodman CLJ30AR32 Air Conditioner

I installed a new honeywell rthl111 series in Oct. 2012. I wired the blue wire to the RC because that was how the old thermostat was wired. The heat worked all winter but when I tried to change over to cool nothing would work. I checked the schematics online and realized I should have installed the blue wire to the B. I checked the fuse in the power panel and saw I had blown it. I changed it and rewired the thermostat the correct way. I tried again and still neither the cool or heat will work. A


... Goodman Air Conditioners

I turn on the Central A/C unit with the thermostat. The attic fan unit goes on and the system cools the house. When the system shuts down the fan unit shuts off but the outside compressor keeps running. The only way the outside compressor goes now off is when I flip the 240 switch on the main box. This just started. Is it a thermostat problem? Thanks.


Could be a thermostat problem but even more likely the contactor on the unit outside is stuck. In order to change this part you will have to get in to the outdoor unit. The contactor is the automatic switch that the thermostat energizes when the t ... Air Conditioners

On My goodman heat pump, It had blown the transformer, I installed a 3amp fuse and when engaged into cool mode blows the fuse. I have narrowed it down to the yellow wire in the heat pump that goes to the low pressure switch and defrost board but cannot figure out what is causing it to blow fuses


... Goodman Air Conditioners

I installed a Honeywell TH5220d 1029 thermostat on a American Standard AC/Heat pump and the install and setup went fine. It cooles for about and hour and quit. I found the 5 amp fuse at the furnace blown. I replaced the fuse and it blew again in about 2 minutes. Have followed the wires, checked for shorted or crossed wires but it all seems OK. Tried one more time and blew the fuse right away.?? Any good idesa?


Red wire to R on thermostat red on furnace and red on heat pump Same with white except w1 on thermostat. Blue to common on thermostat common of furnace (probably brown but will be marked) and blue to common on heat pump. yellow to Y on thermostat and ... Air Conditioners

Once you turn on aircon with fan with high speed, the air blown doesn't get cold even after a while. The fan makes some wierd high pitch sound as if like metal against each other. The fan stops once in a while and makes that same sound once it start turning again. This goes cyclic through out the time it is turned on but not cooling the air from the aircon.


Your AC needs a good overhauling as the fan seems struck on the bearings or the blades are rubbing the sides. Also the compressor fails to cool as there can be low gas, low pumping pressure or a blocked condenser.\012You need to remove clean th ... Air Conditioners

Our Furnace doesnt seem to be working correct. We an: Air Pro BGM075128 and is Natural Gas. It will turn on when we turn up the thermostat.. but we never get any heat through the vents. There is a switch on the side that is "on" and one that is "fan". If we turn on the "fan" only cold air gets blown through. It looks like this is for cool air. So, if we leave the fan off and the "on" swith on, we get the furnace firing up, but no heat ever comes through the vents. I tested out the thermo


Sounds like the blower motor is not working, if the furnace is actually lighting up and the burns are ignited. You should set your thermostat to auto, as if it is on fan then the fan runs all the time until you take it off of fan. I am a little confu ... Air Conditioners

When i tunn on my AC unit at the thermostat it blows the 3 amp fuse in the air handler when it call for cool when i switch the t stat to off and just turn fan on the fuse does not blow and blower runs


Sounds like the compressor is or a electrical component directly linked with the cooling operation/ outdoor unit running.Possible short to earth....cheers ... Ruud UBHC Air Conditioner

The A/C unit control is powered from the 24 volt supply in a Ruud high efficiency furnace. The furnace fires up when the house thermostat is set for heating but there is no power in the line to the A/C unit when the thermostat is set to cool. The 24 volt transformer is delivering, and the fuse has not blown. Can you advise?


You will have to trace wiring. See where power starts and stops. Check to see if there are any fusible links in the wiring, or if there are any relays for A/C to wiring. ... Air Conditioners

My dog chewed the thermostat wire by the compressor, i replaced the chewed wire now the thermostat won't turn on, therefore; no ac.. could it have blown a fuse? if so, where are they?


Either you have blown the low voltage fuse located inside the air handler (if there is one) or you have blown the transformer feeding the low voltage control wiring.If the transformer is blown due to no fuse installed, I would recommend i ... Goodman CKL42AR42 Air Conditioner

Not cooling I have a 10AJA4201 and it froze over the other day and I let it defrost and turned it back on. Now it won't keep up and runs constant. I have thermostat set at 73 and it won't get below 76. Heat of the day it goes above 80.


Check the evap(indoor coil) if its clean and there is not an airflow issue,make sure the out door unit shuts off when the indoor fan is not running .if all is good you may have to place a service call and have the refridgerant levels checked ... Weather King 10AJA4201AH Air Conditioner

My goodman central air unit quit working after a storm. The circuit breaker is not blown. The furnace fan kicks on when ac is turned on at the thermostat but unit outside does not operate. Is there an internal fuse or capacitor on outside unit. Thank you very much, Bryan Model CKL36-IF Goodman


1 posible cause.the thermostat supplies 24 volts to the outside unit to control the contactor if you hear a ligth huming on the outside unit this is the being activated. if this is the case then\015\012\015\012 check to see if any ants are in ... Goodman Air Conditioners

My carrier furnace keeps blowing 3amp fuse when I turn thermostat to cool.


Hello, sounds like there is a short in the low voltage circuit. First inspect the wiring at the control board and make sure nothing is loose or touching metal. Also, inspect the wiring all the way to the outside unit and make sure it is not loose or ... Air Conditioners

Have a Vulcan MZ85 Gas Heater with a Vulcan Programable Thermostat T8602C originally hooked up in heat and cool system with one transformer the cooling system has since been removed and now operates the heating unit. The issue now is that you turn the thermostat on to heat it will heat up to the pre selected temperature once it reaches that temp it turn itself off it does not maintain the set temperature so you have to turn the unit off and restart to activate it have tried 2 other thermostats w


Hi, you need to wire the thermostat like this. You now have no cooling, so remove the jumper wire from RC and leave it on RH. Remove the yellow wire also. Make sure it is wired the same way at the furnace terminals also. Sounds as though you have 24 ... Air Conditioners

Furnace problem I Have a 2005 Montana3295RK with a duo-therm air conditioner,suburban sf35f furnace and a dometic thermostat with remote. The problem lies with the furnace. It will not turn on, and in the rare event it does it will not turn off unless you either pull the fuse, turn the switch to the off position on the furnace or turn the gas off at the tanks. I can force the furnace to come on by pulling the fuse and then putting it back in and the thermostat does not have to be in the on posit


The problem is most likely in the control module of the roof air unit. Dometic uses the thermostat to activate and deactivate a relay in the control board of the roof ac unit whiich is just visible when you remove your air intake screen. The two blu ... Dometic Rooftop RV Air Conditioner

19 seer infiniti system, system will run for 2 mins. and then cut off and it will not show a code to the outside unit board or the thermostat. Replaced the thermostat and the outside low voltage wiring, then went to test mode on thermostat. Turned high cooling for 15 mins, it will run for 10 mins and then cuts off. It still does not show a code. If you go to the thermostat and turn it off, and reset it to cooling it will run for 2 mins and will cut off.


This cut off is very likely being caused by a defective compressor module thermo limiter (prevents overheating the compressor), replace it. ... Air Conditioners

I have a Carrier Heat Pump model FK4CNF003. I noted that the thermostat wasn't working (no power) so I checked the usual suspects...in bound power etc. before I pulled the top housing off the interior unit. I noted lots of wires on a circuit board in the upper right corner of the unit which seems to route power and signals to/from the thermostat. Looking closely, I noted that the 5 amp fuse was blown so I put in another 5amp fuse and it blew as well. Given the fuse is blown, and I'm assuming


You should be able to trace the short to a specific componant on the board itself. the 5amp fuse protects the board itself. trace the circuitry back from the imput side. you should have a multimeter that has a audio alarm that will tell you which cir ... Air Conditioners

A/c will not continue to cool.. Starts fine, runs fine.. but shuts down cooling ( comp shuts off but fan still runs) after anywhere from 5 min to multiple hours. No circuit breakers or fuses blow. CAN usually reset by cycling wall thermostat if that does not work can unplug 12v. connection to thermostat and it will most often start cooling again when asking via the thermostat. Have replaced computer board in a/c unit on roof and wall thermostat


One amateur test is to place your hand on the compressor and see if it\015\012is too hot to hold your hand on it. You may have a restricted condenser coil \015\012If it is too hot then the condenser coil is restricted inside the unit ... Dometic Rooftop RV Air Conditioner

Earlier this week, I noticed that the house felt "stuffy" but the thermostat showed everything to be cooling as expected. Last night, the house was definitely warmer than expected when we got home. My husband did some checking and found that the outside unit was running as normal, but there was no cool air coming through the vents inside the house. turning the a/c unit off at the thermostat did NOT turn off the outside unit...was only able to do this at the circuit breaker. It seems that the fan


If both fans runs (inside and outside), check if the compresor runs , if does probably the unit is low in freon and needs to be recharged after the freon leak has been fixed (remember this is a seal system and it shouldn't leak), but if the compresso ... Ruud UBHC Air Conditioner

The Coleman Mach thermostat in my 5th wheel blows its 2 A fuse a couple of times today and am trying to figure out what is causing this. Please help. I am unable to get the furnace to run even with a good fuse in the thermoatat. When I bypass the thermostat to run the Atwood furnace (red tied to white wire). THe furnace blower comes on and the burner sounds it lights for 5 seconds and then goes out. 15-20 seconds later it reignites and goes out and continues to cycle -- the blower motor


Hi\015\012\015\012Its blowing fuses because of short circuit inside the coleman mach or due to two wires being shorted with each other. You'll need to open up your thermostat system to look for the short circuit and also shorted wires.Ple ... Air Conditioners

Earlier this week, I noticed that the house felt "stuffy" but the thermostat showed everything to be cooling as expected. Last night, the house was definitely warmer than expected when we got home. My husband did some checking and found that the outside unit was running as normal, but there was no cool air coming through the vents inside the house. turning the a/c unit off at the thermostat did NOT turn off the outside unit...was only able to do this at the circuit breaker. It seems that the fan


Nope, nope, sounds like a stuck contactor in the electrical compartment of the condenser, but there are actually several things that could cause it. ... Air Conditioners

The fuse on the control circuit on the inside unit keeps tripping One side of the fuse goes to the thermostat the other side goes to the control board the fuse blew about a week ago let the unit sit for a week while we were out of town. put another fuse in it ran for 5 days fuse blew again let unit sit for 2 hours then the fuse held not sure what to check


Its hard to say without being there but here are somethings to check. Outside check the thermastat wire onthe condensing unit. I have this problem a lot down on the gulf coast. The wind blows and cause the Tsat wire to rub against the unt and it shor ... Air Conditioners

I have a dometic dual-therm rooftop RV air with analog thermostat. When I set the thermostat to heat, the unit will hum but the fan does not turn and no air is coming thru vents in the floor. Then unit will blow cold air (hums and fan turns) when thermostat is on cool, but it won't turn off unless I shut it off at the breaker. What could be wrong?


... Dometic Rooftop RV Air Conditioner

My thermostat is set on 72....but shows it is 76 in the house. I shut it off yesterday in case it was freezing up. 2 hours later, turned it back on and it cooled great the rest of the evening. I woke up at 3:00 am this morning and was doing the same thing. I shut it off for several hours, now has cool air blowing, but not as cool as it should and still shows 76. Cool flashing on the thermostat.


It sounds as thought the coils on the unit need to be cleaned, make sure it is draining, if it still freezes up after cleaning coils and checking for draining then the unit has a leak and needs to fixed/charged. Hope this helps tim ... Air Conditioners

I have an XQ08 model - thru the wall When turned on it provide cooling for approx 10 minutes (sometimes longer) and then it stops blowing cool air. My repair man came and adjusted the sensors which he said might solve the problem. It did not. the thermostat is set to 69, I have it set on 'cool', not money saver. When it stops cooling, and I turn it down to 60, it makes no difference and no sound indicating the compressor clicks on. Any suggestions would be helpful. thank you Ms Hill


Hi\015\012\015\012To fix a cooling problem in AC you must know the cooling process that the condenser (outside unit) pulls in the house's warm air and cools it with Freon. The cold air is then forced back into your home through the duct s ... Friedrich Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || www.ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.1267 seconds