Having problems with your Air Conditioners ?

I have bard central unit model# a/c ph11361 blower not running

\015 I have bard central unit model# a/c ph11361 serial#1750991338Z77-1 my problem is every thing works except blower motor the voltage going to motor is 115vlts shoulnd be 220vlts? my questions were is my voltage drop? and how can i ck to find problems cking across wires no voltage but each leg to ground 115vlts thanks\015

Answers :

If your unit is a gas unit, then its 115v and if its and electric unit 220v. If you are getting voltage to the motor, 115 to ground but the motor isn't starting then the motor is bad. The black wire is high speed, red is med., blue and or yellow is low. The wite wire is neutral. Black wire is used in heat mode and blue is used for cool. If you are checking voltages you will only use one of the colored wires with the white wire and you will only have voltage for the one that the tstat is calling for to come on. Hope this helps.
220 is just putting two 110 volt circuits together. You should read only 110 volts from each leg to ground. But you should read 220 between both legs. Measuring between two legs that are supposed to be 220 and you read nothing than you are not measuring the differences. This means you are only getting 110 volts. Check your units data plate and make sure you need 220. Usually the condenser fan on a split system is 110 volts and the condenser fan is 220 volts. Which motor are you checking?

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I have bard central unit model# a/c ph11361 blower not running


If your unit is a gas unit, then its 115v and if its and electric unit 220v. If you are getting voltage to the motor, 115 to ground but the motor isn't starting then the motor is bad. The black wire is high speed, red is med., blue and or yellow is ... Air Conditioners

Blower will not run in auto on a bryant air conditioner central unit model number fb4anf042, but will run in fan mode


... Air Conditioners

I have an old RUUD central AC unit that started blowing hot air. I set the thermostat to off and set the temp gage higher than air temp to turn the unit off and save money, but inside blower unit runs constantly. I'm trying to save money to have it serviced, but noticed my electric bill was higher that last month when the ac was working. The bill was about 4 times higher than the winter when ac is off and the gas heat kicks in. Can the blower running constantly cause this power usage and what is


HelloOkay did you check your thermostat to see if you have the fan switch on auto? The switch must be on auto or the fan will continue to run. If the thermostat fan switch is on auto then there is a malfunction in the thermostat probably ... Air Conditioners

Carrier central air 38ckc060301 problem, unit will not start, air handling blower runs, can hear hum at outdoor unit. I turn the unit off at themostat. let sit for ten minutes, turn back on at themostat, unit starts and cools. Will run through serveral cycles and then not start until I repaet process, any thoughts?


... Carrier Air Conditioners

Indoor Sanyo ductless split Model # KHS 2432 serial # 0012832, Works fan on and off functions and speeds. As soon as you set the remote to heating or cooling the unit beeps 5 times quickly and then the unit no longer responds to remote control. The blower will then run for 1 minute and then the the unit no longer will work. Power must be reset for blower operations to function again. Out door unit, has enough charge, Ambient temp 39 M#CH2432 S#0012424


... Sanyo Air Conditioners

I have a Goodman Model number AR24-1 unit and the blower moter will not start with it turned on to fan or cool or heat. I have checked the thermostat and the unit runs outside. Just no blower. Can I jump the blower motor as I replaced the capacitor today. Hear are some numbers that may help. Part Number #15212-50 Volt 208/240 Amp 1.5 HP 1/5 No heat Kit It has a Goodman switch board # B1370735 that I can check with my meter if needed. I have checked the thermostat in the attic also. Seems like


... Air Conditioners

UNIT RUNS AN EXCESSIVE AMOUNT OF TIME AND AIR IS COOL NOT COLD COMING OUT OF VENTS CARRIER 58DLA / 58DLX CENTRAL AC FAN AND COMPRESSOR ARE OPERATING BLOWER IS WORKING UNIT IS TURNED ON TO AC TEMP SET AT 76 UNIT RUNNING FOR OVER AN HOUR OUTSIDE TEMP 80 THERMOSTAT REGISTERING 77


DOES THE HOUSE FEEL DRIER IF IT IS 80 OUTSIDE WITH ALOT OF HUMIDITY THE UNIT WILL RUN FOR A LONG TIME TO REMOVE THE MOISTURE(HUMIDITY) OUT OF THE HOUSE BEFORE TEMP DROPS DRAMATICALLY IS THERE WATER COMING OUT OF THE DRAIN PIPE OUTSIDE ... Carrier Air Conditioners

Fan not running on central air unit, compressor runs. Old model, btr936a100b0 central air, the compressor runs, but the fan does not. I need to find out what to check to troubleshoot the fan motor components


... GE Air Conditioners

I have a goodman ar24-1 blower motor that will not start. I have changed the capacitor, checked the thermostat, spun the blower motor but still will not start. Outside unit runs but no blower. Any ideas? This is a central air unit that is less than 6 years old.


Check the relay or sequencer that controls the blower if it has one of those. If the fan is controlled by a circuit board then you problem may be there. If it is controlled by a circuit board then you can check for power at the fan connection when th ... Goodman CKL24AR24 Air Conditioner

Bryant furnace model 340mav. Furnace filter got extrey dirty due to updates in home. Started to freeze up. Caught it pretty early. Turned off unit. Thawed it out. Turned wl unit to off. Woke up in am. Furnace blower motor running. Code flashing red on furnace. Three quick red. Three longer red. Blower will not shut off unless I turn off manual switch


... Air Conditioners

Blower fan in the inside unit tries to turn on but wont. It can be turned manually and air conditioner comes on and runs fine. The " squirrel " cage spins completely freely and is not sticky or jammed. Is the motor bad or is it a run capacitor. Model number of inside unit is a49-15


\011Sound more like the cap, but if the motor is raging hot, it could be the motor, another thing it could is improper voltage although less likely. But Goodmans/ do have this weird fan relay issue were they just bite it some times. I wo ... Goodman Air Conditioners

Intertherm Electric Furnace in mobile home Model# MRAC 2317 SN - 79JE0501 Question: The blower stays running all the time. I have to turn the main breaker off to turn the blower off. The unit is heating when it is running. I have replaced the thermostat about 3 years ago in the summer when I had a AC problem. Would the fan switch on the furnace possibly be the problem? It has an auto & on position on the switch. It clicks when you switch to the on position but does not click when you put i


... Intertherm Air Conditioners

I have a Inter therm Model# FEHB015HA central heat & air unit that I had problems with in the summer as the out side unit would not come on but the blower would kick on but nothing on the outside unit(No cold air).Ok I fixed that as it was the the transformer that switched it down to 24 volt to go to the outside.Now I have noticed that when the heat is on it will not kick the outside unit on?It has been very cold here in Georgia but right now as I type it is 50 degree's and the outside unit is s


Hi, if this is not a gas fired split system, it is a heat-pump with aux heat strips. The outdoor unit must be on to warm you're home by way of the reversing valve. The strips in the indoor unit are for emergency and auxiliary heat only. ... Air Conditioners

I have an Amana central air/heat unit. Model PHCB10C1 Serial # A040900070 Manufacture # P1219409C, Cat # 81K95. The problem I am haveing is the unit will not kick in(heat). When I turned off the main pwer and let off for about a hour and turned back on the unit ran fine for a couple days. Now the unit will not kick in at all even after turning the main power off and on to reset the unit. I have a brand nre thermostat in the house. When I turn the fan from auto to on the fan runs and blows out


... Amana Air Conditioners

I have a Coleman roof mounted AC unit on a travel trailer. The unit model is 83338715. The unit just blows cool air not cold air like it should. I was told to replace the "Hard Start Capacitor" and "PTCR Start Device" which I did. This did not remedy the problem. Any thoughts would be appreciated. Could the problem be the "Compressor Run Capacitor"? Reason being that I hear no change in the blower sound when the unit kicks on???


Blowing 'cool air' could mean - room temperature air or it could be 'cool' because the system is low on refrigerant, and just barely doing any 'cooling' at all.\012\012To determine which is which - you need to know "for sure" if the compressor ... Air Conditioners

My compressor unit outside runs and cools Freon but the inside blower has a problem running. the model # is 2TEE3F31A1000AA. The fan control, in fan run control mode, shows a bright green for the fan LED and the CFM selection LED varies with the rotational speed of the fan. The motor tries to start showing , initially, a jerky back & forth movement. It squeaks some and may, or may not, start rotating. If it starts the CFM LED goes bright/on no flicker and the motor runs briefly (5 seconds) then


Hi, from what you have told me, you are loosing the bearings in this blower motor along with windings. This motor is rubbing the blower housing, tight when you turn it, and when it jerks when it tries to start tells me that you have burned or very we ... Air Conditioners

The model number as listed on the receipt is CKQ24. The Blower moter in the air-handler is not running. When the fan-only switch is turned on, the blower motor will attempt to spin by pulsing for about 2 seconds. It will repeat the pulsing cycle in about 2 second intervals. There is no smell of burning. When the unit is set to AC and auto, the evaparator coils do chill. The blower motor is a variable speed motor with an external ECM. How do I test the ECM and/or motor? What should I look for in


Personally I would get an exact replacement capacitor same voltage rating and microfarud rating. The capacitor will read something like 370v 5uf. I would be surprised if that's not the whole problem. If not it needs an exact evaporative fan replaceme ... Goodman CKL24AR24 Air Conditioner

I have a Arcoaire Gas Furnace (Model# GNJ100N12A1), that will not fire up. It has a White Rogers Digital Stat. First the Stat seems to be faulty, since it reads 70plus in a house that has a temp of 30 or below. I can adjust the Stat and the blower motor will run. The rollouts (3) were reset; the inducer fan would run; then the unit would cycle and shut off. Now the inducer won't run. The ignitor is good, but would never glow. A friend tested the current coming from the Stat, and found 24


Sounds like a faulty board. shut the power to the furnace off for a minute then turn it back on. Make a call for heat at the thermostat. The inducer should start and close contacts on a pressure switch . Once pressure switch closes the hot surface ig ... Air Conditioners

My central air conditioner is making a whistling noise in the inside unit when the compressor is running. It's not the blower because the noise stops after the outdoor unit shuts off. It's also not blowing any cold air and the piping is not getting cold. What could be the possible cause?


Hello,\012\012If there is no cooling (meaning no cold pipes and not blowing cold air) then check the outdoor A/C for any visible/obvious issues; breakers not tripped, no debris blocking the outside unit from passing air through it, etc. If all ... Air Conditioners

I have a rheem electric furnace with 2 speed fan, seems like the fan runs full bore when its on, even when i just cycle the blower control to ''on'' and its supposed to run at reduced speed. I have to experience with central heating and air, was wondering if it would be the circuit card with the dip switches. Unit was installed in 2003 with a heat pump.


If it is a variable speed blower most likely the dip switch settings. Check the installation manual to see how to slow it down. ... Air Conditioners

With unit set to air conditioning, the controller board will not turn on the blower motor and the cooling coil freezes up. McNutt tells me the controller board is kaput and they want $550 for it. In the meantime they have jumpered over the controller so the blower runs constantly. Was hoping someone might be able to tell me where to get it for less. It is HSCI Furnace Controller For Use With All Gasses 1012-940, model HK42FZ011


? need more info like make model and serial numbers ... Air Conditioners

I live in an apartment that has Airtemp central air. The unit blower runs but the air is barely cool. Maintenance sys there is nothing wrong with the unit. What could cause this problem?


Air temp should drop 15-20 F across the a/c coil a rule of thumb i use is air temp out of the vents 10-15 F less than room temp on thermostat if the air out of the vents isnt that cold the a/c is either leaking and undercharged or return air temps ar ... Air Conditioners

Older model intertherm split unit. Compressor runs, but blower will not come on auto. I have to press the switch inside the unit.


The same circuit from the thermostat to the indoor unit and the fan relays, etc. in the indoor unit is used to operate the indoor fan in both ON and AUTO mode. The exception is an internal connection in the thermostat/subbase itself from cool t ... Air Conditioners

Noise at Central Air blower area at furnace. Unit is a Rheem model RCBA-4882g


... Rheem Air Conditioners

Details I have a problem with a Goodman Model GSH130601AA, ( 5 Ton, 13 Seer heat pump) central air unit, installed 06/15/2006. (I know, I saw online reviews but unit was put in before I saw negative e


The fan motor is bad and needs replaced. Depending on how mechanically inclined you are, you can replace it yourself fairly easy, the hardest part being the fan blade without a hub puller. Just take your old one in with you to a local A/C supply stor ... Air Conditioners