We have a rheem furnace we replaced the igniter but still getting no spark what else could them problem be the fan works but getting no spark or heat why


Answers :

Is it a true spark igniter or is it a hot surface igniter? You need to use a volt meter and call for heat. Check to see if you have voltage going to the igniter. If its a spark igniter and you are not getting a reading then it is the module that is the problem. If it is hot surface, then its the control board.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

We have a rheem furnace we replaced the igniter but still getting no spark what else could them problem be the fan works but getting no spark or heat why


Is it a true spark igniter or is it a hot surface igniter? You need to use a volt meter and call for heat. Check to see if you have voltage going to the igniter. If its a spark igniter and you are not getting a reading then it is the module that i ... Air Conditioners

Amana AC model MBR2000, installed mid May 2009. When outside temp gets above a certain level the AC does not cool. fan keeps running and it keeps trying but not work. When outside air gets cooler then starts to work again. Tech here twice. 1st time when AC was working - could not find problem, 2nd time when problem was occurring. 2nd time found burnt wire and replaced. Same problem started again 2 days later. AC unit is large enough for our house, is 18 Seer 2 stage. Any suggestions as to proble


Hi it sounds to me like what actvates the 2nd stage of the compressor is not turning the compressor on when the ambeint temiture reaches the point that it calls for the 2nd stage to start it may be an out door thermostat or a ambient senser and I wou ... Air Conditioners

I'm having a problem with my heating and air system, my heat only works on emergency heat ( and run 24/7) if i turn it to regular heat it only blows cold air. i dont think my outside unit fan is turning( i could be wrong about this one) how can i fix this problem so i dont have to run my emergency heat all the time


If your Heatpump's fan isn't running but your compressor is, your fan motor is out. If nothings happening at all ensure your getting power to heatpump (ex: breaker tripped, fuses blown on outside power switch, or fuses blown in breaker box?) ... Air Conditioners

My carrier A/C YHB243D this window unit was working find. But about one week ago only blows out cold air and sometimes only hot air but now it blows only regular air, and doesn't work nither the cool or heat air. what could be wrong with it?_a) could be- the thermostate that goest at it front with its condenser unit? b) could be the whole temperature switch ? or what else can be its problem, please help! and tell me where I can get the replacement part


... Carrier Air Conditioners

I have dimmer switch controlled ceiling fan. What happens is the dimmer switch seems to works for a few weeks. Then it doesn't behave like a dimmer, but only as a switch - meaning that the fan gets on only at the maximum position of the dimmer. If dimmer is even slightly lowered from the maximum position, the fan gets off. This happened to a previous dimmer also and I have changed to a new one - but still same problem. What could be the cause?


It is better to switch over to the stepped switch type dimmer as the potentiometer( the control ) in these types wear off very easily.\012So when the carbon track loses contact the varation of the resistance to feed the SCR does not happen but ... Air Conditioners

I have a vokera 20-80 flowmatic boiler the pilot light works and the fan works but the boiler will not fire up my corgi heating engineer cannot fix the problem and has walked out on me after 3 weeks of trying. Do you have any idea what the problem could be


Hello it may be a faulty flame safety device that touches the pilot flame or it could be you need a new control board and also check the flue isnt blocked hope this helps ... Air Conditioners

I have a Jantrol heat pump & A/C. It is approximately 10 years old. For the last 3 summers the compressor unit will freeze when the air handler fans fails to come on. It worked fine for 2 weeks this year before it happened. I've be able to thaw it out and restart the unit and it works from days to weeks before this occurs again. The last time it happen, I had a problem getting the air handler fan to come back on, but it did eventually. I've been thinking it may be the sequencer, but now I'm wond


Hi,\015\012\015\012If you can safely check the supply to the motor when it should be on, then this is the best method to check it.\015\012\015\012Check the fan turns very freely - oil the bearings if it doesn't.\015\012 ... Goodman Air Conditioners

Ihave a Day & Night Furnace M/N:58GS050-3 Series 301 S/N:Z33A65482. My problem is with no wiring whatsoever landed @ terminal strip fan runs @ high speed constantly.With stat wired up & a call for heat I get no spark,just fan(fan switch -auto). 24vac is present into circuit board from transformer, but drops out to 15.xx @ R & C.If I apply 24v directly to R along w/other wiring,fan stops,but after ignition main burners light,fan never runs.


... Carrier Air Conditioners

I have a ruud model no. ubhc-17j11nfd and i am having a problem with my heat. when the heat does come on, the thermostat says it is on auxilary heat. the blower in the inside unit does not run. i changed the capacitor and now i get a really loud humming noise. the motor still does not spin. but when i spin the motor by hand then it seems to work fine.(the humming goes away) this happens every time when the heat goes off then back on. the only way to solve this is to keep the fan on constantly.


... Ruud UBHC Air Conditioner

I have a Dimplex XL5N storage heater. When i first moved in it worked. Now i am getting now heat i've rang up Dimplex they told me to put the input switch on maximum and the output minimum in the night. Then switch output to what heat i want in the day. but still no heat, the fuse is ok. What else could the problem be & how much will it cost?


... Air Conditioners

I have a fujitsu reverse cycle air conditioner,it wasnt working(not blowing cold air only room temp air like a fan).air con tech came over,re-gassed it,tried air con that day,worked fine.didnt need to use it for a few months,re-tried it,no cool air again,i am thinking of a leak.My question is the air con is about 10 years old,if cause of problem is a leak,is it worthwhile fixing it(i would need to pay someone parts and labour,could not do this job myself),or to just bite the bullet and get a rep


Hi,\015\012\015\012The A.C is 10 years old which is a ideal shelf life for the A.C. If there are any leaks I would never ever try repairing it at home becuase if there is a leak then that means that the entire GAS which helps in the cooli ... Air Conditioners

I have a GE ZONELINE 5100 hvac unit when unit is turned on the blower works but it will not generate heat when set on heat selection nor will it blow cold air on cold air selection it just blows air out like normal fan what could be the problem


Check the selector switch to make sure that the controls are transferring from heat to cool. Then if the control is working you would have to check power to the valve that changes the flow of refrigerant from heat to cool. This unit may be heat ... Air Conditioners

My maytag airconditioner is approx 4 years old only used about 6 mths out of year and this year it is not cooling properly. I can hear compressor cut on and it gets really cold and then I hear it shut off and it sounds as if only the fan is runnning. When fan isblowing it is not cool at all. Could my problem be a thermostat? Please help it is 85 degrees in our house at 10 pm and my children are not dealing with the heat very well.


Maytag has one of the best warratys in the business call a maytag repair man and it should be under warranty ... Air Conditioners

Hello, I have been having problems with my fujitsu split system. In the summer, the cooler part worked wonderfully so I was looking forward to being cosy and warm in winter! What happens is that it gets to 16 degrees and then shuts off :( it then comes back on once it has dropped below 16 degrees. Could there be something wrong with the heat sensor or could it just be as simple as adjusting something on the remote control? Please help, I am tired of being freeeeezing. Kate


You didn't say how cold it is outside your home, which is important when dealing with a heat pump.\015\012\015\012If it's colder than it's been previously, you might just need to 'move your thermostat up a couple of degrees to make up for ... Fujitsu Air Conditioners

Heating problem hello! My air conditioner stopped to heat. (there is a around 8 degrees C, outside and 16 degrees inside). It worked just fine, and now, when I switched to heating mode, there was nothing. the defrost LED ond the inside unit is switched on, but air is not comming from the unit. Cooling mode works fine. If you could please help me finding the solution for my problem. Thanks in advance. RAdan GE AIR CONDITIONER SPLIT SYSTEM WON'T WORK ON HEAT CYCLE Seems to work ok doing eve


Hi Radan, Did you get this problem solved? We have an Electrolux Kelvinator Split System and ours is doing exactly the same thing. I am struggling to find a solulution. Would be great if you can offer any advice.\015\012\015\012Thanks Nic ... Air Conditioners

I have a problem with my central heat / air unit. As it is getting cold now, I am using the heat. My problem is that I must turn the thermostat to the on position to get the unit to come on. In the auto mode, nothing happens. I can get very cold but not ever kick on until I move the switch to the on position. In the on position it works fine. Thinking that my problem was with the wall thermostat, I replaced that. I do not remember having this problem with the A/C. What should I look for to fix t


Look on your thermostat one switch (for the fan) will say off/on/auto. The other switch (for operation mode) will say off/ac/heat. The switches should be set at fan auto and mode heat. Some have an auto for the heat/ac if that is the case your thermo ... Air Conditioners

I have a Tappon furnace DGUF 106 02 EF Serial 77D18453 The unit has an intermittent problem, It will cycle at will, thermostat is good I can sometimes get it to come on by heating the unit above the control valve(the one with the spark plug wire looking wire from the bottom) OR cycling the main valve removing the Yellow wire several times. this is not working well now . any Ideas?? Thanks Ted


... Air Conditioners

Our Furnace doesnt seem to be working correct. We an: Air Pro BGM075128 and is Natural Gas. It will turn on when we turn up the thermostat.. but we never get any heat through the vents. There is a switch on the side that is "on" and one that is "fan". If we turn on the "fan" only cold air gets blown through. It looks like this is for cool air. So, if we leave the fan off and the "on" swith on, we get the furnace firing up, but no heat ever comes through the vents. I tested out the thermo


Sounds like the blower motor is not working, if the furnace is actually lighting up and the burns are ignited. You should set your thermostat to auto, as if it is on fan then the fan runs all the time until you take it off of fan. I am a little confu ... Air Conditioners

No heat I have problem with a carrier heat pump / AC the fan inside work and the air is circulating but no heat is coming out, only heat with the emergency heat come on, also the fan outside works, I change the thermostat by noting change.


Your compressor sounds like isn't working? And the problem is if we are lucky you just lost the capacitor. turn off the breaker to the ac/heat pump unit. Open the electrical panel on condenser locate the capacitor if it is swelled up like puffed u ... Carrier 38BRC048 Air Conditioner

My heat isnt working now but in the summer time my ac works. but last year my heat woulodnt work but then one day started working. then the summer time my ac wouldnt work then one day started working an now that it is cold out again my heat wont work. what could be the problem. i already tryed replacing thermostat. an the heater core is working cause both lines are hot.


What kind of air con is it. it would be a sticky reversing valve either from inside the valve or the solinoid pulling it siting on the valve. http://t3.gstatic.com/images?q=tbn:SMSfcwrA_p4i6M:http://www.daviddarling.info/images/reversing_valve.jpg&t= ... Air Conditioners

We have a GE Zoneline Heat / Cool Model 2800 (with Heat Pump Model 3800). The blower works but no heat. The A/C works fine. My brother works for Marcone Appliance parts. He removed the housing to the control board, and suddenly the heat started working. It stopping the next day. We replace the control board, but no go...it still won't heat. What could be the problem?


... Air Conditioners

My hotpoint eg900x fan oven has a problem. the fan oven no longer heats up, fan is working but no heat. oven works in normal mode


... Air Conditioners

Have a Grand Aire Central Air and Heating unit a/heat pump...has been working fine. Switched it over to heat and nothing came on. Switched it back over to air, which was working and still nothing came on. Switched fan from ''auto'' to ''on'' and the fan will not come on. Used a screwdriver to push the contact in and everything runs (air and heat) as long as I am holding the contact in. Changed the t-stat, still the same problem. I really don't have the finances to call a pro in, any advice will


The fuse may be in line (red ) wire check control voltage if not present transformer (or fuse) needs replaced \015\012 the problem probably was caused by white wire (heat control voltage) has been wired to common not heat control ... Air Conditioners

I have a packaged heat pump., but getting intermittent heat. All components of equipment is operating properly except the indoor fan motor. the fan motor is drawing 12 amps (nameplate ampr 3.2 A) & and the fan cuts off approx. every 10 minutes for a while. I get 2 ohms reading on the run windings and 12 ohms on the start windings and a infinite reading on the ohmmeter fo the capacitor. where is my problem?


Hello,The fan motor is going off on thermal overload(saftey).The motor cools & it resets automaticly,runs again and will overheat again.The berings are probbally tight and it is time to replace the motor.There is a sticker on the old motor with r ... Honeywell Air Conditioners

Heating problem hello! My air conditioner stopped to heat. (there is a around 8 degrees C, outside and 16 degrees inside). It worked just fine, and now, when I switched to heating mode, there was nothing. the defrost LED ond the inside unit is switched on, but air is not comming from the unit. Cooling mode works fine. If you could please help me finding the solution for my problem. Thanks in advance. RAdan


The LG>LW5200ER AC is not listed as a heat providing unit. Click on link and this will give you the spec's\015\012\015\012 \015\012\015\012 ... LG LW5200ER Air Conditioner

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific