Having problems with your Air Conditioners ?

Air does not work

\015 Air condition unit will not come on. replaced capacitor earlier so heater would come on. now i have no air.\015

Answers :

Hi! there, no matter what it is,so heater is the problem and replace the capacitor of fan that's it,what about the thermostat,you gonna check also your thermostat, if thermostat is deactivated the source going to your fan motor is also cut off,check resistance if there is continuity.how does you know if cacitor is busted so you also know how to work on it,so use your multitester if thermostat is good,go to control panel board and check if theres power source on the terminal of fan motor,if there is you have problem on fan motor check thr resistance of fan motor if busted replace,if good isolate the source fan terminal to control panel board if there is a relay holding supply check the contactor point.replace,check also the heating element,doing this should done by cetified a/c tech.take allnecessary precaution to avoid electric shock regards and have a nice day

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I have two compressors-one for the upstairs and one for the down stairs. Both compressors are working but the air flow for the upstairs basically does not come out. You can hear the unit running but no air upstairs. Down stairs the air is working. Is there any way to turn the airflow up or adjust it to send more air upstairs. I had the capacitor replaced in the down stairs compressor a few weeks ago and for the upstairs about 1 1/2 years ago. when the air downstairs started working a few d


Hello,Thanks for using FixYa.I suggest that you try to have the fan that routes air upstairs checked. Its possible that the motor is already going bad.I hope this helps. Thanks and good day.HotRatchet ... Air Conditioners

Our air conditioning was working during the day. when one family member turned the air up from 72 to 75 she saw the screen process what she wanted and walked away. when another family member went to turn it down, the screen was off. i have a honeywell visionPRO thermastat but no air conditioning at the moment. is my air conditioning not working because the honeywell theromastat needs to be trouble shot or is it not working because the machine that produces the air conditioning itself not wor


Open the thermostat and look for batteries, 3 AAhttp://www.heater-home.com/photos/2129-5b.jpghttp://www.heater-home.com/manuals/th8321u1006manual.pdf ... Honeywell Air Conditioners

Heating problem hello! My air conditioner stopped to heat. (there is a around 8 degrees C, outside and 16 degrees inside). It worked just fine, and now, when I switched to heating mode, there was nothing. the defrost LED ond the inside unit is switched on, but air is not comming from the unit. Cooling mode works fine. If you could please help me finding the solution for my problem. Thanks in advance. RAdan GE AIR CONDITIONER SPLIT SYSTEM WON'T WORK ON HEAT CYCLE Seems to work ok doing eve


Hi Radan, Did you get this problem solved? We have an Electrolux Kelvinator Split System and ours is doing exactly the same thing. I am struggling to find a solulution. Would be great if you can offer any advice.\015\012\015\012Thanks Nic ... Air Conditioners

I have a Mitsubishi split air conditioner; Model number: MSH-18NA. When I turn the air conditioner on with the remote control, sometimes it works normally, sometimes it doesn't. When it is not working properly, sometimes the fan turns continuously and sometimes it doesn't. No matter whether the fan is working or not, no cold air comes out. The green operation light is blinks and the indicator light is off. It looks like the outdoor unit is not working because the outdoor fan is not moving. Wha


... Mitsubishi MS12TN Air Conditioner

I have a fujitsu reverse cycle air conditioner,it wasnt working(not blowing cold air only room temp air like a fan).air con tech came over,re-gassed it,tried air con that day,worked fine.didnt need to use it for a few months,re-tried it,no cool air again,i am thinking of a leak.My question is the air con is about 10 years old,if cause of problem is a leak,is it worthwhile fixing it(i would need to pay someone parts and labour,could not do this job myself),or to just bite the bullet and get a rep


Hi,\015\012\015\012The A.C is 10 years old which is a ideal shelf life for the A.C. If there are any leaks I would never ever try repairing it at home becuase if there is a leak then that means that the entire GAS which helps in the cooli ... Air Conditioners

Wont work I have a Maytag central air thats about four years old. Once in a while it would stop blowing really cold air and would just blow mildly cool air. What I would do to fix this is flip the breaker off and then flip it back on again. When I did this the "high cool" light would come back on and everything would work just fine. This time that solution wont work. I have left it off for an hour at a time multiple times. I played with every switch and checked and cleaned every filter. We live


... Maytag M7Y15F2A Air Conditioner

Before I had the air conditioning compressor, belts and idler pulley replaced, the vents in my 1995 Oldsmobile 98 Elite were working fine, after the work was done the vents on the passenger side of the car do not put out any air the ones on the driver side work just fine. What do I do to get the air to the other vents???


I was not getting anywhere with your experts toward solving\015\012the problem, I gave up on them and sold the car, let someone else\015\012solve the problem, they are aware of it.\015\012\015\012Sorry your actions did not help. be sure I am no ... Air Conditioners

Hi, two days ago I bought a Danby Premiere DPAC13009 portable AC unit. It worked on the first day reducing the temperature from 32C in the room to 26C in a few hours. Although now there is no cold air coming out of the AC and only the fan is working. I verified the two hoses and the exhaust is working good, lot of air is blowing out. Although, no air seem to be sucked in from the intake hose. I checked and I don't see any obstruction. Could the compressor be dead already??? thank you


Comperssors have a thermal overload. If there is a starting problem or low on freon the conpressor will shut down until cooled off. Try restarting and listen to compressor. ... Danby Air Conditioners

Air Conditioner was working fine last summer but outside fna not working. Not hearing any sound at all. I can move the fan amanually and it seems fine. There is an electrical box next to the main electrical box on the back of the house with 2 fuses in it but I can't tell if they're bad. I thecked the thermostat and it apears to be fine. The air conditioner furnce kicks on and blows air out of the registers. It's just the main unit outside that's not working.


There is a relay in the outside unit. Check for 24 volts a/c at the two wires coming from the furnace. also there may be a mouse nest in the control comartment where the relay is and they tend to chew up wiring insulation and sometimes wires get disc ... Carrier 38CKC042 Air Conditioner

We are selling our house and have been leaving the air conditioner on for the last several days at 70. It has been keeping the house cool for visitors when we are at work. Yesterday I came home from work and the house was warm. I checked the air conditioner and it felt like it was blowing just air. Checked it throughout the night and still blowing just air, not cold anymore. I am thinking it ran out of coolant. I am not an expert or know anything about air conditioners. If you could give me your


It can be many things like a loose connection. It can be low of refrigerant or it can be the condenser fan has stopped working. Considering you are selling the house just call a qualified HVAC repairman and have it repaired. ... Air Conditioners

Hi, My remote won't work for my air conditioner. Batteries changed. Can't tell if it's just remote or air conditioner unit as well that aren't functioning. Can you tell me if there is a manual way of operating the airconditioner without the remote? If it is the air conditioner, what do I try to get it to work? I have taken filters out and cleaned them and that's all the ideas I had. My air conditioner is a LG Model LST 244H-2 split system. At least 6 years old. thanks for your help


Here is the main ONLINE SUPPORT page for your LG model LST 244H-2: ... LG Air Conditioners

My carrier A/C YHB243D this window unit was working find. But about one week ago only blows out cold air and sometimes only hot air but now it blows only regular air, and doesn't work nither the cool or heat air. what could be wrong with it?_a) could be- the thermostate that goest at it front with its condenser unit? b) could be the whole temperature switch ? or what else can be its problem, please help! and tell me where I can get the replacement part


... Carrier Air Conditioners

Have a Grand Aire Central Air and Heating unit a/heat pump...has been working fine. Switched it over to heat and nothing came on. Switched it back over to air, which was working and still nothing came on. Switched fan from ''auto'' to ''on'' and the fan will not come on. Used a screwdriver to push the contact in and everything runs (air and heat) as long as I am holding the contact in. Changed the t-stat, still the same problem. I really don't have the finances to call a pro in, any advice will


The fuse may be in line (red ) wire check control voltage if not present transformer (or fuse) needs replaced \015\012 the problem probably was caused by white wire (heat control voltage) has been wired to common not heat control ... Air Conditioners

Aircondition I have a air conditioner problems, the unite inside the house is working I can hear it and feels the air coming out of the vent but it's not getting cool air, the unite outside all I hear is click once and about 2 to 3 mint. click again. I have the other air condition next to and it click and then seem to locked and worked. help..


You will need an OHM meter to check the relay and compressor. Make sure all power is off. The most common types of compressor winding failures are open, grounded, or shorted. You have to know how to read a meter. If you don't find someone who can. Or ... Ruud UAKA030 Air Conditioner

Cold air not coming out. I JUST bought this the other day and it worked the first day just fine but now it will work fine for about 10 minutes and then the cold air will stop coming out. Air will continue to come out but not cold air. It is summer in New York so help please. PLEASE. Thanks in advance. This is a Haier ESA306 window unit.


Need to return this one where you got it. Sounds like compreesor or control problem. Do check outlet voltage to make sure it is not a low voltage problem first. Voltage should not drop below 10% of name plate voltage required. Voltage should be check ... Haier ESA306 Air Conditioner

AC unit blows cold air in the AM and hot air in the afternoon. Repairman has come out 3 times. 1st time added freon and worked for 1 month, 2nd time he said was compressor, a new compressor was ordered, came back with new compressor and said that is not the problem, added 2 lbs of freon again and it is currently working. He said to call him when it is blowing hot air again so he can see everything when it is blowing hot air.


That is ediculous. He can charge it, leak chk and repair in one trip. I hope he isn't popping you for a service call each time. ... Air Conditioners

Air conditioner stopped working, nothing works, breaker is on, power to air conditioner is good, It was working just fine and then every thing stopped. All the other electrical things are working just fine.


A few basic principles for air conditioner troubleshooting. For both central home air conditioner or window air conditioner,\015\012 the first thing to check is whether the unit is getting proper power. \015\012If the unit ... Dometic Rooftop RV Air Conditioner

I have a fujitsu halcyon inverter evaporator that isnt working. The indoor wall mount is blowing air, but the evap outside isnt working. The fan doesnt seem to be working. I have another 2 piece fujitsu, same exact model that is working fine, drawing air into the evap. Dont know much about trouble shooting, any tips would be appreciated because its hard to find info on these things.


... Fujitsu Air Conditioners

Hello, I have two Yokohama Split type air conditioners that work fine for cooling, but when switched to heat they just blow air at room temperature and then after about 1 minute go into a standby mode indefinately. They work perfectly for cooling. All fans work perfectly and the compressor works perfectly for cooling. Thanks...


... Air Conditioners

My Delongi Pinguine 92 typ PAC 19E can also work on water. Now the watertank is filled but he only works on air. The red light that he works on air is on. What must i do to let him work on water again?


... DeLonghi Air Conditioners

Centrex airconditioner i have two centrex aircons, the one works for a few seconds then stops working and shows an error e4 on the screen. The other one works but wont blow cold air, only warm air. Please help me.


I bought a house with one already installed. Found that it isn't switching from 'hot' to 'cold' After time the unit will beep and flash LED's on the unit itself and then switch off. Rather handy on 40 degree days. Good luck sourcing parts for the uni ... Air Conditioners

I have a suburban lp furnace and duotherm air/heat pump roof unit. duothern thermostat. 20 amp breaker kicked ( reset breaker) & furnace quit. NOW furnace fan comes on but does not light, and the front AC will not work either, when in the COOL position on STAT the unit blows warm air instead of cold. I replaced the Thermostat and a Tech guy checked the board in the furnace and it was OK. He also switched the board from the rear air with the front and nothing changed. Rear air and heat pump works


I'm not sure what the problem may be but you could try calling All\015\012Seasons RV Appliance Parts & Service. There number is\015\0121-800-344-0673 they have helped me in the past. That and there tech\015\012calls are free so it wouldn't hurt ... Dometic Rooftop RV Air Conditioner

My air conditioner will not turn on. (See below for a more detailed description.) I recently bought a used Kenmore Room Air Conditioner Model 580. 76129. It worked well for about a month (running almost continuously, usually on either energy saver or cool). About a week ago, I walked out of my room when the air conditioner was on, and it was off when I walked back in about an hour later. (The display was unlit, and it was not making noise.) The power button still does not work. The outlet


If you have a GFCI plug on A/C unit it may need to be reset at the plug. ... Kenmore 76129 Air Conditioner

We had our furnace replace this winter, our air was only about 8 years old and working fine so we didnt change it, well now , the air coming out of the vents are cold, but the condenser NEVER shuts off and the thermostat never reads what it is set on, it stays 2 or more degrees higher, the company that installed the furnace checked the air and said everything is working fine, and leaves me high and dry and HOT... the freon level is good, the pressure reading is good, but the house is hot and the


Hi, if the new furnace they put in did not have the right size coil to match the outdoor unit, it would run all of the time and not cycle off. Lets say if it is a 3 ton condenser, the indoor coil must be a 3 ton coil as well. If they put a 2 !/2 coil ... Air Conditioners

At 30,000 miles my then 8 or 9 month old chevy 2500hd 4wd pickup truck air conditioning started blowing hot air on the driver side (the passenger side was still cold). I turned the truck off and back on and it began blowing normally for a few days and then it would do it again. A year or so later the heat on the driver side went out totally (passenger side worked properly). So now the driver side blows cold air constantly. A few months after that the blower quit working all together. Now at 185,


What year truck is this? This is actually a very very common problem on those chevy trucks. Most times it is the door blend actuator that has failed. and the default for this failure is driver side blowing hot. There are a million posts out there on ... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"