Water droplets on the fan coil unit in the morning after one night of operation


Answers :

If the humidity is just right in your house in relation to the temp of the unit and the temp in the room, condensation will form. Should not be of any concern. But if you continues, clean the unit real well and try again. Your supposed to have condensation on the coil it's self though.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Water droplets on the fan coil unit in the morning after one night of operation


If the humidity is just right in your house in relation to the temp of the unit and the temp in the room, condensation will form. Should not be of any concern. But if you continues, clean the unit real well and try again. Your supposed to have con ... Sanyo Air Conditioners

Rudd ugph - 07eamgr furnace will run normally during the day and then at night when it needs to work harder it will stop. banging on the outside of the unit will re start it. when I check it in the morning it is operation fine. I have already changed the pressure switch, the ifc card, and the inducer motor fan assembly.


... Air Conditioners

GSH130481CA condensor and ARUF48601ba fan coil. Server noise at intermittent times,in heat mode, usully in the middle of the night. Sounds as if from fan coil. Fan coil 50 ft from condensor. Fan operating normally with noise.


It may be your noticing the defrost cycle which can be noisy at times exspecially at nite when the unit will reverses it cycle temporarily ... Goodman Air Conditioners

Our frigidaire window a/c unit (model faa067p7a) does not seem to be operating properly. There is no condensate forming anywhere (beneath the coils is dry and no evidence of water and there is no water coming out of the tube under the coils into the styrafoam drip area). Everytime we run the unit it cools the room to a degree but the humidity also goes way up. I tried the reset button on the power supply but that didn't seem to have any effect. Any ideas?


It sounds like your unit is low on freon or the compressor is not kicking in. If the compressor kicks in you can hear it turn the unit on fan only or turn the thermostat off then turn the unit to demand cool you should hear a hum even vibration when ... Frigidaire Compact Air Conditioner

Replacing a o smith fan fse1026sv1 into York ac unit model H2RA036s06A. Old fan had two hot legs, one from capacitor, and grnd. New fan has two brown, old fan one, that go to capacitor. Tried wiring browns together put fan shut down after about 5 minutes. And it was hot all around the top above the coil. Any suggestions?


... Air Conditioners

I have a Pyrox Vulcan wall heater that frequently stops - displaying "F1 1 ERR". Many technicians have looked at the unit, the most recent has changed a capacitor (which one I don't know but I assume it was related to the fan motor), the first tech just said is was human error and that I don't know how to operate the unit. I am considering replacing the 3 yr old unit with another brand, as the support for this one is virtually non existant.


... Air Conditioners

Mitsubishi MUZ-A42ANA heat pump and MSZ-A42ANA indoor fan unit worked like a charm for over a year. Still does. But the condensed water removal operation (A wall mounted 2”x2” mini pump, Sauermann SI3100UN-23, 230v 50/60 Hz 18w, Made in France, removes water through plastic tubing from the indoor unit to the roof mounted heat pump 8 feet above) is making a vibrating noise each time it is activated, about every 30 seconds or so. Water is being sucked out, bubbles inside tubing and all, but the


... Mitsubishi Air Conditioners

Great site. I have a Simplicity SPAC 8499-5 Portable Air Conditioner and it was working fine up until yesterday (~2 years old). The unit is running and the fan operational but while the green light for Cool/Dry is illuminated that actually cooling unit for the air conditioner is not kicking in. The system is just blowing air (like in Fan) mode. I have checked the water reservoir and it is empty and placed properly in the unit so the switch is engaged but no AC.


... Air Conditioners

I have 2 kickboard heaters in the baseboards under the cupboards in the kitchen (Smith SS7's). They are run off the hot water central heating circuit. The fan in each unit is supposed to click on to blow hot air from the heat exchanger when the temperature falls. Both units have stopped working - when one stopped the other worked intermittently for a few weeks but now this does not come on either. I have bled both units and if I keep doing this then eventually hot water reaches both but the flo


Does your heating system have zone control valves? if so make sure they are opening with kitchen t-stat. sounds like the boiler pump is not able to flow water to the units. might be a zone control problem. ... Air Conditioners

Intertherm I have a package unit that has stated dropping out the cond. fan and comp, but contiues to run the blower motor. when I opened panel I noticed that the contactor will pull in and then drop out . this happens every few mins. The unit did this for the 1st time night before last. When I checked it yesterday morning I replaced the contactor and still had same problem. while checking voltages the contactor pulled in and the unit worked fine all day. then last night the problem returned. I


Check the board for a cold soldered joint. If you can move the spade that the line connects to it should be re-soldered. A cold soldered joint can give intermittent service because it can make contact at one time then loose contact by even a change i ... Air Conditioners

I have a GE Zoneline 5500 PTAC that doesn't throw any heat. The electronic display appears normal during operation, I hear a clicking when the unit is turned on and the fan kicks on but it just blows cold air. The unit was set to the highest heat setting and the air filters were cleaned and unplugging and restarting but still no luck. I haven't tried using the override dip switch to bypass the heat pump, becuase there is a total of 3 of these units in our condo; one in each bedroom and one in th


Hi,\015\012Just for giggles and grins I would switch that one to coll and see if the compressor runs in cooling... that will tell you if it is the compressor or the reversing valve that is bad...It may also jog the reversing valve and get it to ... GE Air Conditioners

I have a 57915 Duo-Therm RV AC. Working great last night, but stopped sometime in the night. Fan or compressor does not operate. When I switch on the fan, I here a click in the unit, but nothing else.


Hi Steve,\015\012Thank you for contacting Fixya. This is Anil.\015\012I understand that you hear a clicking sound from the AC. Let me try to help you with it.\015\012Steve, the first two things to check are to make ... Dometic Rooftop RV Air Conditioner

2 Years ago i had a rheem unit installed. In the attic is a handler that blows right. On the left is the coils and on the right is the fan. The pan under the unit collects alot of water and the float then shuts down the compressor. The drain pipe is clear however the insulation under the fan is soak. Can you say Why?.


Make sure there's a trap installed in the drain line from the unit. Those units will not drain without one. ... Air Conditioners

We live in southwest Florida. Our HVAC system consists of a air conditioning system with heating coils when it is cool. Yesterday morning we tried the heat nothing come on. Later in the day I tried the air nothing. I tried turning in just the fan nothing. I just checked the breaker I have power where the wires are connected. I went out to the outside unit and pulled the cover. Pushed in a spring loaded plastic switch the fan on outside unit works and shut off when I released the switch. But noth


Hello. Sounds like you do have power. That spring loaded plastic switch is a 24v contactor. It pulls in when energized. If you push it in manually everything shoud run normal. Ck your 24v transformer. On one side (feed) you should have 115v or 220v ... Air Conditioners

I purchased a Coleman model 564 cooler about june 1,2008 at Wal-mart. I used it for two trips to Canada,June and August,one week each. The fan operates spasmodically and the unit does not cool. I believe the unit will not work in a non-pristine environment, it appears a small amount of dust makes the fan inoperable.THE .35 AMP 12v DC motor made in China does not do the job.This is my 2nd Coleman cooler,model 564,the first being a model 5640. The results are the same. I have two really nice looki


I had the same problem with the fan...its junk.. don't try to replace it with the same kind of fan. I went to radio shack and got a 3.15"square brushless fan. You could go to a computer store and get the 3 &5/8" fan with ball bearings and it wo ... Air Conditioners

Sanyo Condensing unit. blower fan doesnt come on unless unit runs,but unit only runs for about one minute and shuts off. led #6on cond. unit blinks and led on evap. coil #26 also blinks unit needs to be turned offon for it to restart.


First, the condensor fan is only supposed to run when the unit is on. As for the one minute run, then needing reset...this sounds like a "safety out". The air conditioner knows something is wrong and tries to protect itself. Being low on Freon wou ... Sanyo Air Conditioners

AC Out. Two year old house. Goodman A/C, two units one for upstairs. Cleaned coils of both outside unit, replaced filters, re-set breakers. Upstairs is cooling. Downstairs unit is running outside, not circulating air inside (inside temp 87). Vents inside are cool to touch, no air. Outside unit fan is pulling, but air exhaust is cool. Compressor ? Should air be circulating even if compressor not functioning. Is there anything in attic exchange that would affect downstairs circulation. Thanks.


Assuming that the 2 systems are isolated, that there isn't any cross over between the systems...It is normal for an air conditioner system, from window unit to central, to be able to circulate the air, even if not cooling. This is known ... Air Conditioners

Last night my husband turned off our window unit because it had gotten cold in the house, we got up this morning and went to turn the unit on and it won't come on at all. The light on the plug is on and when I click the reset button it lights up everything on the front panel but it turns itself back off. We always have to replace window units every year and this is quite costly and am getting tired of this. We have 3 other units that are older than this one which is only a year old but we also p


Must be a shorted capacitor. ... Air Conditioners

One of my units is not providing cold air although the fan is blowing. My 3 zone unit was recently cleaned including coils and exterior unit. It was also correctly charged, checked for leaks, and the correct gas is in place. Two different technicians have worked on the unit.After service the unit has run for a day or two and then not provided cold air. Any suggestions?


Hi, you'll need to double check refrigerant (freon) charge. working for a day or two, could means there's refrigerant (freon) leak, if there's no leak and refrigerant (freon) charge is o/k, check your electrical, you didn't say what make or model is ... Mitsubishi MS12TN Air Conditioner

I have a Bryant split unit. After incurring some water damage that I assumed was from the overflow pan (the damage came from a poorly insulated elbow in the duct that was sweating) I opened the unit and found the condesate pan dry but the interior was completly saturated. I watched as condesate dripped off the coil and the supply fan would pull the drop and miss the pan entirely. Now I have mold/mildew forming in the unit and the insullation inside the unit is wet. I turned off the ac and left t


Most all brands of air conditioners are built along the same lines, and for the most part are equally well designed/constructed. Bryant AC's in my opinion are as good as any - and - although - I don't know all the facts about your problem - I do kno ... Bryant 463AAC008BA Air Conditioner

WATER COMING THROUG FRONT OF FUJITSU fan coil unit


... Fujitsu 12RLS Halycon Wall Mounted Air Conditioner

On my LG window AC Md. LWHD1009R, I cannot find a drain hole to let the water out. The back bottom of the pan was filled water containing a rusty sludge, but the heat exchanger coils are aluminum, so it must come from another source.( I have a wooden shutter built over my windows because of hurricanes-nails? ) Is this unit supposed to drain, because I bent down one place to let the rusty sludge and water out. Its properly mounted with the back lower than the front, and I've had no problems with


Usually in the middle underside of the window units is a hole that water drains out of, you can always drill new holes in order to make it drain, Good Luck Tim ... Air Conditioners

I have a whirlpool model ACM102xLO that seems to be dying. I cleaned the coils, and the unit seems to operate normally for a few minutes. Fan motor works, compressor motor seems to work. When I checked the amp pull on the fan motor, it falls in the normal range of 1.2A. When the compressor kicks on, the amp pull jumps to around 10 and climbs to a high of 15 or so, then the compressor shuts off and the amps jump to about 25 or 26, before cutting off completely. The amps then drop to the fan motor


... Whirlpool Air Conditioners

New panasonic heat pump inverter has shut down due to water running from outside unit . Unit had been set on 17 over night and then set on a temperature of 22 and unit had been running for approx one hour and a half when this shut down occured . Outside temp is zero.


... Air Conditioners

I have a goldstar air conditioner model R0801E that starts spraying water from the fan outlet after it has run for approximately 1 hour. I have checked the drain and it is not plugged, nor is there any obstruction to it, I have in fact drilled a hole into the 'formed' drain channel on the bottom which leads to the drain nipple located on one back corner. i have tried tilting the unit in order that gravity might assist and it still blows water enough that i can't use it or it will ruin the wall,


Seems i have the problem resolved by doing the following:\015\012\015\012increasing the thermostat setting from 25* C to 29*C, this will reduce the load on the cooling condenser,\015\012ensuring that the vent is set for 'fresh' as o ... Goldstar Air Conditioners