Fan will not shut off, but compressor does

\015 The fan on my trane 1000 unit will not shut off even when I turn it to off. I have the original weathertron controller for my trane unit.\015

Answers :

Hi! there, continous fan motor when unit was shutt off,since supply source was already cut off specially on fan condenser motor,the supply of your motor was came from relay mounted on your circuit board control panel,there a holding coil to hold the connection between your fan and ac source,shut off breaker for ac unit first before diagnosing ac unit, try to check this out the relay is still activated giving ac source when shut off,the contactor on relay holding your ac supply was shorted,try to check the connection the circuit activating condenser fan relay,eliminate the short circuit,using multi tester test rod,use manual diagram for circuit control board to lessen complicated diagnosing,focus on fan relay ac source then isolate checking the short circuit replace defective relay,contact point of relay are not repairable.take necessary precaution on checking to avoid shock,this a hard task i would suggest that certified ac technician w/ full knowledge of instrumentation should do this.thank's for selecting fixya and have a nice day.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

When the AC fan shuts off, the compressor appears to be stuck. It continues to make a humming sound as though it is running. If I remove power and return power it hums momentarily and then shuts off. Is it OK to allow it to "hum"? I constantly kill the power when the fan shuts off in fear of harming the motor or compressor.


Yes, not good for compressor to stay on after being shut off, and hitting the breaker to stop it is a good idea. Sounds like you have a faulty/sticky relay. Not an expensive part, and shouldn't take any longer than 1/2 hr to change. Have a technician ... Dometic Rooftop RV Air Conditioner

Sometimes, when the inside blower shuts down, the outside compressor and fan motor continue to run for some time. Other times, when the inside fan motor is running, the outside fan and compressor motors are not ... if I press the outside reset button, it starts up When both inside fan motor and outside fan and compressor motors are running, it works fine ... warm air blows out of registers. Other than that problem, both units work great!


Sounds like you have a dirty condenser. You are going to need to disconnect the power at the outside unit on the wall by pulling the fuse block out. Take a good look at the louvered covers that are attached to the outside of the unit. Remove the scr ... Ruud UAKA060 Air Conditioner

I turn on the Central A/C unit with the thermostat. The attic fan unit goes on and the system cools the house. When the system shuts down the fan unit shuts off but the outside compressor keeps running. The only way the outside compressor goes now off is when I flip the 240 switch on the main box. This just started. Is it a thermostat problem? Thanks.


Could be a thermostat problem but even more likely the contactor on the unit outside is stuck. In order to change this part you will have to get in to the outdoor unit. The contactor is the automatic switch that the thermostat energizes when the t ... Air Conditioners

My ac comes on in my RV and runs for a about 15 minutes and then the fan shuts off and finally the compressor shuts off. this happens before reaching the cooling temp. When it comes back on the fan does not come on at all and you can just hear the compressor hum


The Fan topside , Is the one working? The one that blows on the condensor? If not, your compressor can be trying to start against high head pressure. Ck the other fan, not the one that blows inside, the other one.It cools down the condensor and ... Air Conditioners

I have a whirlpool model ACM102xLO that seems to be dying. I cleaned the coils, and the unit seems to operate normally for a few minutes. Fan motor works, compressor motor seems to work. When I checked the amp pull on the fan motor, it falls in the normal range of 1.2A. When the compressor kicks on, the amp pull jumps to around 10 and climbs to a high of 15 or so, then the compressor shuts off and the amps jump to about 25 or 26, before cutting off completely. The amps then drop to the fan motor


... Whirlpool Air Conditioners

I have a Dometic rooftop Air conditioner in my RV When I turn it to low medium or high the fan run the same speed and when I turn it to AC it will run for about 5 min then the fan will shut off but the compressor keeps running I turn it off for a min or so and everythings comes back on. Turn it to the fan only side and the fan will run for 5 min then shut off a min later it comes back on then back off and on in fan only side.


Bad fan motor I suspect The windings are bad causing the motor to over heat sending the motor into thermal overload. would suggest the replacement of motor. Good Luck on repairs\015\012\015\012Dave ... Dometic Rooftop RV Air Conditioner

I have a carrier heatpump. The blower fan runs all the time. On the thermostat, I set the fan on auto, when the compressor shuts off the fan continues to run. ocassionally the fan will shut off but most of the time it continues to run.what can I do to correct this?


... Carrier XHB123D X/Y Series Heat/Cool Air Conditioner

Compressor fan Model CLJ36 - 1C Compressor seems to be running but compressor fan will not spin. Compressor shuts down when it gets to hot.


The fan should be running if the compressor is running.Check fan capacitor and check windings in fan.Check to see if fan is short to grond.If the fan is not running the compressor is no cooling off. ... Goodman CLJ36AR42 Air Conditioner

Duo-Therm Compressors will not shut down. In "off" or "furnace" the compressor keeps running. Either compressor will shut down when the 12vdc fuse is pulled. Fans on both work ok in both speeds. I


What about one for cool only, and one for heat/cool ? ... Dometic Air Conditioners

I have a 1993 yellowstone camper with a coleman wall thermostat. on the bottom of it- it has a heat/cool switch on one side and the other side has a low-high-fan switch. when we run it on low or high it gets cool but the fan never shuts off.if we put it on fan it shuts off with the compressor but it doesn't blow cool air. any advise?


Thank you so very much for your answer! I'm glad I came to this website before I began a new project. I was about to re-wire my unit based on my ex-husbands advice!!!! ... Coleman Air Conditioners

Cooling well it starts just fine cools for about two minutes then the compressor shuts off unexpectedly? i thought it might be the thermostat? i bypassed the thermostat completely but no luck? i can here the compressor come on when the unit is switched on and it does appear to cool down before the compressor shuts off and the fan keeps running.


Check if the condensar ( outside fan unit) is getting enough free ventilation. IF there is no free air flow you will mostlikely be triping the unit due to short cycling. Ie the unit is pulling its own discherge air causing the compressor to trip due ... Haier HPAC9M Air Conditioner

I have a Duo-Therm Penguin model#610115405 that cools and the fan changes speed(slower) when the room gets cooled and the compressor kicks out, but the fan will not shut down.I have the same unit fwd in my RV that works fine. I tried switching the thermostat,ptcr relay and the capacitor that is below the ptcr. Any other suggestions ? Dont see anything that else that I can easily switch to check.Still not shutting down?


Hi,\015\012the relay that is suppling the power to the fan is welded shut and is not opening. This often happens with relays, the contacts get pitted and then they heat up and weld fast. The relays that run the fan faster and slower are still w ... Dometic Rooftop RV Air Conditioner

The outside compressor and fan will not shut off. I have turned the thermostat system to Off and even to heat, but it will not stop. I went on a trip, increased the room temp to 80 on the thermostat and left. When we returned 2 1/2 days later, the coils were frozen and no air was comiing through the vents, even with the blower motor working. So I turned the unit to furnace and melted the ice on the coils, but had to pull the fuses on the outside box to get the compressor to shut off. Is there a


Sounds like the contactor is stuck. That's why nothing will stop the fan and compressor except killing the power to it. You should be able to get one fairly cheap. ... Ruud UAKA037 Air Conditioner

Compressor problem? My outdoor unit comes on with the fan blowing just fine. Then I hear a buzzing sound for about 2-3 seconds which I believe is the compressor trying to come on. (Incidentally, a couple of lights inside the house seem to dim at the same time that the buzzing sound occurs.) The buzzing sound reoccurs every couple minutes while the outdoor unit fan and the indoor blower both continue to run. I have shut down both the outdoor and indoor units for a couple hours and tried restarti


The buzzing is your compressor trying to start. It is going off on internal overload caused by heating up of the motor windings.If you have an amp meter you could check the amp draw of the comp against the locked rotor amps listed on the tag You cou ... Ruud UBHC Air Conditioner

The blower fan does not shut off when it reaches the set temperature. Compressor shuts off but fan continues to run making the air inside very humid. Temperature is getting cold.


First, forgive me, but I have to throw the obvious out there......make sure the fan switch is in AUTO and not ON. \015\012If the blower will not stop operating unless the main supply feed is shut off, you have a stuck blower relay that will nee ... Air Conditioners

My portable LG (model LP0910WNR) AC keeps shutting off the a/c but keeps the fan on. when i turn on like normal and select cold (meaning a/c on) i hear it kick the compressor on and cold air is flowing then approx, 3 minutes later ill check on it and it blowing ambient (room temp) air only. and the a/c compressor isnt on just the fan. only 6 months old


... Air Conditioners

Everstar mpk10cr grinding compressor I think.... Fan works fine, will kick into cool mode (elevated fan level) for a few seconds then it sounds like the compressor has a loose mount or something... sometimes it rattles for a few minutes (and cools) but sometimes it shuts the rattling off as fast as it starts and doesnt really ''cool'' or dehumidify.... Some days its works fine all day, others it just never really gets its ''**** together'' so to speak... Can users recharge the coolant themselve


Hi, I hear you , you have to keep her happy and cool!! First of all, no you can't buy R-22 unless you are a contractor and you have a certification card showing you are qualified to use freon. This is not your problem from what you are saying. If thi ... Air Conditioners

Condensor fan runs after compressor shuts off


If new motor is 4 wire verses 3 wire use seperate capacitor between brown wires and don't use terminal on 3 pole cap. If this motor has a white strip on one brown wire you can wire it the old way using only 1 brown wire and tape off the other. Can't ... Weather King 12AJA4801AH Air Conditioner

The fan on the condensing unit isnt working it works for awhile and then shuts off,then the compressor starts to work by itself really hard and the whole condenser heats up really fast so I turn off the breaker and start it again but the fan makes and electric humm and I have to push start the blades to get it to spin and then it will work for awhile and then the fan will stop again after about an hour and then same thing happens


Does the fan turn freely or is it hard to turn by hand? If it is hard to turn the fan motor may need to be replaced. If it isn't hard to turn then check the fan capacitor. You can test it with a multimeter or take it to a heating and air supply and g ... Goodman CLT36AER36 Air Conditioner

Ckl30-1e fan and compressor shut down after 30 min, tried new fan motor capacitor has been replaced, hard start kit was put on. Tech is suggesting fan blade angle is inncorrect but that would not cause an instant failure. so what could it be.


... Goodman Air Conditioners

The compressor on my goodman unit runs a few hours and shuts off. The condensing fan continues to run and once in a while you will hear a buzz but compressor won't start. If you then turn up stat and wait, unit may start or sometimes you have to wait longer for compressor to run. Readings are fine and unit is clean.


There could be excessive heat developing causing internal overload protectors to open when it has reached that temperature. This could be due to bearing or winding problems with the compressor. Another possibility is the capacitor if it is not operat ... Air Conditioners

I HAVE A GOODMAN CK-36-1A AC AND THE FAN IS NOT WORKING. WAS TOLD TO REPLACE THE CONDENSER CAPACITOR AND IF THAT DID NOT WORK REPLACE THE THE CODENSER FAN MOTOR. THE COMPRESSOR COMES ON BUT SHUT DOWN WHEN IS GET HOT, WAS TOLD THAT THEY WORK LIKE THAT. MY QESTION IS WHAT FAN DID GOODMAN PUT IN THIS AC UNIT SERIAL NO. 97F9895.


Goodman unit you can use a 1/4 hp or 1/3 hp cond. fan motor but it does sound like a cap. Replace cap first. Its very easy to do just open up panel and replace the silver bullet with terminals out the top. It will say on the side what size it is like ... Air Conditioners

My AC My Compressor keeps kicking off. I turn the unit on, the fan works. The Heat works but the compressor turns in about 60 sec. If I unplug the unit and turn it back on, it comes on but the compressor shuts off again after 60 sec. Can this be from dirt in the coils? They have some build up. Any other causes?


One might think so, YES the compressor is running till it gets hot and tripps on hi-temperature, and after it cools down awhile, the switch willcautomatically reset itself and back- & forth......Thank-you-very much! ... GE Zoneline AZ38H12DAD Split System Air Conditioner

My unit's compressor will intermittantly stop working. The thermostat seems to keep the intake unit working but since it can't get the temperature down it never shuts off. We have been removing the batteries and letting the thermostat reset for 20 minutes. (thermostat Honeywell RTH23110B). After the reset the compressor will work again but will fault within a day. I am pretty sure that the compressor and fan are functional as if I press the contactor down it begans functioning. I also, to he


If the air handler coil is clogh , the air won't go through and the compresor will shut off on overload because of high head pressure, also this will happend if the condenser coil (outside) is blocked or if the fan dosn't work .Also if the outdoor un ... Air Conditioners

My compressor stays running and dont shut off when the fan shuts off


Sounds like you need a new control box. ... Dometic Rooftop RV Air Conditioner