Having problems with your Air Conditioners ?

I have a Maytag M6Y18F7A Air Conditioner window unit & am having problems w/ the thermostatic control not dropping below 75o. Originally, the unit switched to 67o which wasn't really a concern, but 75o just won't cut it. The +/- switch is working, it's just that now the t/stat won't go under 75o. Looking forward to your reply. Thanks-


Answers :

This sounds like the control board has malfunctioned. You might have to have it replaced. When you have it on, does the unit switch off at 75o or does it continue to run? Also check the temp of the air leaving the unit, it needs to be below 55o's.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I have a Maytag M6Y18F7A Air Conditioner window unit & am having problems w/ the thermostatic control not dropping below 75o. Originally, the unit switched to 67o which wasn't really a concern, but 75o just won't cut it. The +/- switch is working, it's just that now the t/stat won't go under 75o. Looking forward to your reply. Thanks-


This sounds like the control board has malfunctioned. You might have to have it replaced. When you have it on, does the unit switch off at 75o or does it continue to run? Also check the temp of the air leaving the unit, it needs to be below 55o's. ... Maytag M6Y18F7A Air Conditioner

10yr Vulcan Central Heating unit. Had tech come out and said main fan unit was faulty. I replaced myself and still not working. I discovered the O/Temp manual switch had cut off power. When I reset the switch the unit comes on and all works except for my fan which then the unit heats up and cuts off.


I have the same problem, heating unit will not ignite, it trips out, i go into the roof cavity and remove the top of the unit (4 screws) and there is a motherboard, it has a Green light flashing what tells you the type of fault it has, mine has 3 Fla ... Air Conditioners

Hi. I have an LG Neo Plasma Air Conditioner. Some time ago it started cutting out (switching itself off) and giving a C6 error message. When this happens, the remote does not work and the unit needs to be switched off and on at the fuse box. What appears to be happening is that when the unit needs to idol, this is when it cuts out. I still have some success using the cool setting, until it starts to idol. I have no success with the heat setting as it won't idol to warm up...it just cuts ou


... LG Air Conditioners

I have a Tempstar 9000 airconditioning unit and while I was weed wacking I accidently cut a wire to the unit. I replaced the wire but now the unit wont turn on and also my furnace blower wont work even in the "on" position. I have a energy saver unit attched to the a/c unit as well. One wire connects to the a/c unit and the other to the energy saver. If I push the connector on the unit with the panel off the unit will run. Cansomeone tell me how to connect those four wires?


Hello TLOEKS You blew the transformer FUSE inside the blower unit! It should be a 5amp blade fuse like the one that goes in a car.It is located at the curcit board at the blower compartment.Replace that to restore low voltage power and every thing wi ... Air Conditioners

Have a Grand Aire Central Air and Heating unit a/heat pump...has been working fine. Switched it over to heat and nothing came on. Switched it back over to air, which was working and still nothing came on. Switched fan from ''auto'' to ''on'' and the fan will not come on. Used a screwdriver to push the contact in and everything runs (air and heat) as long as I am holding the contact in. Changed the t-stat, still the same problem. I really don't have the finances to call a pro in, any advice will


The fuse may be in line (red ) wire check control voltage if not present transformer (or fuse) needs replaced \015\012 the problem probably was caused by white wire (heat control voltage) has been wired to common not heat control ... Air Conditioners

Wont work I have a Maytag central air thats about four years old. Once in a while it would stop blowing really cold air and would just blow mildly cool air. What I would do to fix this is flip the breaker off and then flip it back on again. When I did this the "high cool" light would come back on and everything would work just fine. This time that solution wont work. I have left it off for an hour at a time multiple times. I played with every switch and checked and cleaned every filter. We live


... Maytag M7Y15F2A Air Conditioner

My air conditioning unit wont start we usually start it with the remote but its not working it. it keeps flashing a symbol up the top when i try to turn it on but it wont start it. how can i fix the remote because i really need to get it started. the remote control unit model is: AR-DB5.


... Fujitsu 36CS Air Conditioner

My indoor unit on my heat pump will not shut off. The electric heat keeps running, and the fan keeps running. It only happens when it is really cold, like 25deg or below, above that and it functions fine. The outdoor unit shuts off, but the indoor stays running. I do HVAC work, but I have never seen a problem like this. I have switched the stat out, and its just so strange. I figured the relay may be stuck, but if I turn the stat off, it turns off shortly after which tells me it may not be the c


I would venture to say your stack relay is getting stuck. either that or you have a short in your low voltage wiring somewhere that is not always making contact....or it may be making contact through another median...like ice or frost. Remember ele ... Intertherm P3RA-036K Air Conditioner

My LG art cool units stop frequently and show a code of C8. I turn the unit on and off again and then works until the next time....This has been going on for several years now, is annoying/concerning, but each time I have a professional come to visit they tell me the same thing....that the C8 means the internal fan is blocked, but if by turning it on and off the problem is solved then the fan is not really blocked and I should not be concerned. I have two art cools and this happens on both of


... LG Art Cool LA121CNP wall/window Air Conditioner

Since we had a new consumer unit with trip switches fitted with 100DP isolator and 30mA RCD, our Smeg 90cm Duel fuel cooker trips it when the main oven is on. The top oven and grill work fine, but as soon as the main oven reaches it's required temperature, it trips the box, we flip the switch to return the supply and it then can do it a couple of times more . We are going to get the main cut-out fuse upgraded from 80A to 100A and the meter upgraded to 100 amps from 40amps. Do you think that thi


Someone should check the current draw by the appliance. Then compare it with the name plate to determine if the problem is with the appliance or external power supply. ... Air Conditioners

Panasonic CS aircon. Timer light flashes. Seems outside unit does not work but inside unit does. Air blows but is not really cool. Switches off randomly.


... Panasonic Air Conditioners

There is a switch on my 1 1/2 ton Ruud furnace/Air handler that is not working properly. The unit would not turn on, even though the thermostat was working. I took the panel off of the air handler and found that a switch had been duct taped into the on position on the unit. Apparently, the tape had shifted and the switch was no longer in proper position. when i moved the switch, two green indicator lights lit up. When i turned the unit back on, the A/C worked. Clearly, there is a problem w


Helllo, this switch is called a door interlock switch. ... Air Conditioners

I replaced my outside unit with a 3 ton goodman heat pump unit. My old unit was a 3 ton bryant and the compressor burned up in it. I left the old unit under the house since it seemed to be in good condition. the pump worked fine on ac to start off. But then you had to switch it in heat and back to ac for it to work. So the tech replaced the expansion value and put filters in both lines. I still have to switch it back to heat to get the ac to work. The tech told me that i would have to repla


You said it had rwo filers on the line. I know one is a liquid line drier. If you have one on the suction line it need to come out ASAP. The trash in the line can be removed by running in cool.pump down unit replace drier. While the unit is pumped ... Air Conditioners

E1 error message on wont turn off tried powering off from fuse board when switched on again e1 message back and unit not working


Hi ; Please save Yourself some greif and google the manufactors phone number and they will send You a owners manual so You can look up code. Sometimes the manufacturer will solve Your problem on spot...alpharome416 ... Haier hwr10xc6 Air Conditioner

Panasonic inverter air conditioner remote control wont work, it will not turn on and there does not seem to be an override switch on the actual unit?


To replace your battery have 2 AAA batterys and slide down the front cover and pull the cover of the remote you will find the battery compartment underneath the slide. ... Panasonic Air Conditioners

My honeywell focus pro 5-1-1 wont shut off..its showing off on programmable thermostat but its still blowing cold air and i have it set to 90degrees...my problem indicator light on my unit is blinking 4 time meaning something is wrong with my "OPEN LIMIT SWITCH"...what should I do..really not a ac/heating guy...please help!!!!


Turn the power off at your furnace. Take the top front cover off at the furance. The high limit switch is right in the middle of the unit above the burrner tubes. Two low voltage (24 volts) wires are going into it. It is about 2.5-inches high and ... Air Conditioners

Heating problem hello! My air conditioner stopped to heat. (there is a around 8 degrees C, outside and 16 degrees inside). It worked just fine, and now, when I switched to heating mode, there was nothing. the defrost LED ond the inside unit is switched on, but air is not comming from the unit. Cooling mode works fine. If you could please help me finding the solution for my problem. Thanks in advance. RAdan GE AIR CONDITIONER SPLIT SYSTEM WON'T WORK ON HEAT CYCLE Seems to work ok doing eve


Hi Radan, Did you get this problem solved? We have an Electrolux Kelvinator Split System and ours is doing exactly the same thing. I am struggling to find a solulution. Would be great if you can offer any advice.\015\012\015\012Thanks Nic ... Air Conditioners

I have an intertherm rpbmb030k combo a/c and heat. Had frion put in the unit over the summer and a new digital thermostat. Unit has worked great until we needed heat. Unit works great on aux. heat but keeps switching to to defrost mode when standard heat is on. Switched out the defrost board on the unit to no avail and an a/c guy checked to ensure the new thermostat was wired correctly.


Hi, if the unit had a leak in it, was the leak located and repaired? Did he check the pressures in the unit now? If it switches to the aux mode ( Heat Strips ) is normally caused when your primary unit, compressor and freon are low on charge. I would ... Intertherm P3RA-060K Air Conditioner

I have a Westpoint SPG131HP. The remote control cannot switch the indoor unit on and no beep is made (remote controller is fine b'cause it works on other units). The a/cond works if switched on from indoor unit on 'Forced Operation' mode.


The receiver was tested on another indoor unit and it didn't work. Problem was therefore located. Replaced the 'eye' on the receiver in the indoor unit. ... Air Conditioners

This is about a 15 YEAR OLD Trane XE1000 30,000 BTU A/C unit. The A/C was not working, but right after I called to have someone come fix it, it started working again all by itself. When the unit was not working (for about 18 hours). The house got up to about 80 degrees with the thermostat set on 70. When the HVAC tech got here (next day), he told me the compressor is shot because the thermal limit switch inside the compressor is overheating. The area where the thermal switch is getting warm, but


You can wait just buy a capaciter start system theat will override the old start capaciter, this is a common problem for all ac systems. just bu the ac start replacement and yo should be good to go for a couple more years. and if you want a reference ... Air Conditioners

I have a 2005 Pilgram 27 foot 5th wheel. My Duo Therm AC unit makes a ticking sound from the ac unit itself when it's not running. Shutting off the Duo Therm analog thermostat does not stop the ticking sound coming from the AC unit, nor does cutting the AC breaker (20 amp), nor cutting the ac power to the entire RV. I had to cut disconnect the rv battery AND cut the ac power to the RV before it'd stop ticking. When running however, the ac works beautifully. When it reaches it's intended temp


It's obviously on the 12voltDC circuit of the AC unit. Sounds like thermostat, or a relay in control box is faulty or bad connection. If you remove cover on ceiling assy., you should be able to hear it in the control box. There should be a model numb ... Dometic Rooftop RV Air Conditioner

Airco Indoor unit SC 12 ZKG Samsung After a while, 2 seconds to several hours the unit switch off. Lights on the unit green and yellow blink for several seconds. The switch off time is increasing shorter. Started with several hours now a days it only last a few seconds to switch off. In this country (Mozambique) is not sufficient kwowlegde to repair the unit. It was working for about 4 years. What can be wrong? Beste regards, Cees van Perlo - Electronic engineer [email protected]


... Samsung Air Conditioners

Still working on our ac inside unit Coleman EB20B outside unit Goodman CKL49-1. We had a short in the thermostat wiring that we repaired. Now the AC is working when the fan switch is on run. It doesn't run with the therm switch on the cool cycle. Have we crossed wires somewhere or is our thermostat bad? Thanks Ken Rohm


You could have either situation. You could also have a bad thermostat sensor, as it talks about in this blog:\015\012http://hubpa ... Coleman Air Conditioners

Heating problem hello! My air conditioner stopped to heat. (there is a around 8 degrees C, outside and 16 degrees inside). It worked just fine, and now, when I switched to heating mode, there was nothing. the defrost LED ond the inside unit is switched on, but air is not comming from the unit. Cooling mode works fine. If you could please help me finding the solution for my problem. Thanks in advance. RAdan


The LG>LW5200ER AC is not listed as a heat providing unit. Click on link and this will give you the spec's\015\012\015\012 \015\012\015\012 ... LG LW5200ER Air Conditioner

When Unit is switched off . The outside part turns on = off as if working, I have just been up to check, found compressor is also runningas is fan motor. we just switched A/C back on to cool , all working OK. Could it be the Stat unit inside at fault.If so here are No.... Electra-teck 50-00402-C ..Stat3176955.065 ... 3107612.024 Duo-Therm, Domestic Thank you Terry Email . [email protected]


The easiest way to see if it is the thermostat is to write down what wire goes where and pull all the wires off. If it still does it, it's not the thermostat. If it stops, you'll need to get a new thermostat. Let me know what you find out. ... Dometic Rooftop RV Air Conditioner

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific