Drain Problems on American Standard A/C and Heat pump

\015 I have 18 month old 15 seer A/C Unit. I cleared the drain line that goes from the unit inside my garage to the outside. I have cleaned the drain pan and cleared anything the might clog the drain holes. Problem is it is still overflowing the water onto the floor of garage. The coils have been cleaned also just in case that might be the problem. I have run out of answers.\015

Answers :

You have a plastic condensate pan and you could have developed a crack in it. But most likely, there is still something that is clogging the drain. You may need to run a snake through it instead of using air. If you ran a snake through then it's probably a crack. Sometimes the crack can be at the outlet where something might have hit the pipe. Also, if the unit has a "draw through" coil, then there needs to be a p-trap installed on the unit to keep water from being drawn back into the unit while it is running. If it is a "blow through" coil and a p-trap is installed then remove it. The p-trap can restrict the flow of water leaving the unit and the least bit of debris can cause the unit to overflow. Draw through means the blower motor is pulling air over the coils and sits over top of the coil. Blow through means that the blower is pushing air into the coils and sits down below the coil. Hope this helps.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Drain Problems on American Standard A/C and Heat pump


You have a plastic condensate pan and you could have developed a crack in it. But most likely, there is still something that is clogging the drain. You may need to run a snake through it instead of using air. If you ran a snake through then it's p ... Air Conditioners

The heat pump stays on to 20 deg (outdoors) and the burners will not work till the temp is under that leaving the house at a max 65 deg, I beleave the heat pump should true off around 30 -35 deg ? then the furnce should run after that. How can we make this change? we have a ACONT800 Control sat an American standard heat pump with a american standard 2 stage furnce.


Remove the cover of the circuit board and controls on the outside unit. Some units have a thermostat that allows you to set the temperature at which it switches to the second stage of heat. Set that for about 34 degrees. ... Air Conditioners

American standard heat pump some body before me changed the compressor unit would not work so i pulled vaccum weight in charge started uint after 5 min. it triped on compressor overload everthing else still working it was not pulling high amps.suction an discharge seem normal if anyone has this problem email me [email protected]


... Air Conditioners

American standard heat pump problems


... American Standard Air Conditioners

I have american standard heritage 12 heat pump that makes a lot of noise especially when it gets ready to stop what could be the problem unit is 12 years old.


... Air Conditioners

NOT a problem--preventive maintenance is my goal. I kept my Payne heat pump (installed in 1985) humming nicely until this January. I only replaced it because of cost/efficiency issues ($$$) every summer. By cleaning the 230V contacts twice a year and replacing the outdoor fan motor twice, I needed service only a few times for refrigerant depletion. I hope to keep my American Standard Heritage 15 (48K BTU) way beyond its ten-year warranty, so I want to buy a manual for it while it's still a happy


By code, whoeve installed this brand new unit should\015\012have left the manual with it. Check the electrical\015\012control box or the fan compartment to see if a manual\015\012is not in there ... American Standard WCZ036F Air Conditioner

American standard 2a6h3018-060 heat pump start problem


... American Standard Air Conditioners

I have an American Standard Heat pump. The unit is one piece is is outside. The problem that I have is that sometimes when the unit kicks on cool, the fan motor will not start. The compressor will run, but quickly freezes up. I can put unit in off and wait for thaw and then put back in cool mode and fan will start. Any ideas?


Definitely a low voltage problem then i would look for the obvious like loose connections good luck you might have to call a tech ... Goodman CLQ36AR49 Air Conditioner

I have an American Standard heat pump. My heat strips in my home are automatically turning on immediately when the heat pump starts. It heats the house up very quickly, but with the strips turning on immediately it is defeating the purpose of the heat pump savings on my electric bill. My electrical meter runs very very fast as soon as the heat pump turns on. I know this is not how the heat pump is supposed to operate. I am using a lot more electricity than I should be using. Can you tell me how


... Air Conditioners

I have an American Standard heat pump. My heat strips are automatically turning on immediately when the heat pump starts. It heats the house up very quickly, but with the strips turning on immediately it is defeating the purpose of the heat pump. My electrical meter runs very very fast as soon as the heat pump turns on. I know this is not how the heat pump is supposed to operate. I am using a lot more electricity than I should be using. Can you tell me how to solve this? Can I adjust something o


... Air Conditioners

Hi guys, I try to solve this problem i have with my AC unit American Standard YCC048F. Short: The heating and cooling are ok, the only problem is the fan doesn't turn off even if heat or cool turns off. Some times even if i put the thermostat is on off the fan starts running. I try to find a relay for the fan but i don't know what can be the problem. Please help, for now i am switching on/off the unit to have it run. Thank you. Costi


If the unit has printed circuit board the relay maybe in it which has probably welded contacts, must change the pcb then or try tapping it, it might help or even, try off and on power at circuit breaker it migt reset the pcb. ... Air Conditioners

I have a Trane Model TRW036C100A0 heat pump with an American Standard Model TWE036C14FBO air handler. The heat pump outside is 20 years old and on it's last legs. The air handler is only about sev


... Air Conditioners

I have a small house with a outside package unit American standard (Trane) Model# WCM030F100BB, italso says BAYHTRN110A. When I select cold from the off position on the thermostat it immediately pops the breaker. It is heat pump equiped and if I select heat it also pops the breaker without hesitation. If I select emergency heat, then fqan to on from auto and then select heat with the top switch of the thermostat it heats the house fine using it's electric strips. The manufacture date is 01/1996,


I would check the outdoor unit, Trane uses "Sump Heaters" on their compressorsand when one fails it will blow fuses at the disconnect or trip breakers. The sump heater is a small metal pencil sized item at the bottom of the compressor ... American Standard Air Conditioners

Freon smell heater - American Standard 5000 Heat Pump Unit


... American Standard 5000 Heat Pump Unit

We need to find an owner's manual for our American Standard Heat Pump model # 4A6H6036B1000 AA. Can you help us locate one?


Please try with:\012SERVICEMANUALS @ COST\012www.mauritron.com\012Manuals at free download: ... American Standard Air Conditioners

WIRE THERMOSTAT TO HEATING PUMP UNIT - American Standard Txa048c4hpc 4 Ton Ac Up/down Uncased A Coil R22 Or R410 33373


... American Standard Txa048c4hpc 4 Ton Ac Up/down Uncased A Coil R22 Or R410 33373

Haier hsu 18 heat pumps . I have 6 of them , all intermittently come up with e17. otherwise sometimes they will just blow fanned air ( compressor not running ) all day . The power source is fed to the indoor unit first, with the main power and data then fed along the same standard 4 core cable to the outdoor unit. I have fitted one of these units which had this problem to another site , and instead of wiring it as per the above way (as per instructions) I put the data cable seperate to the oth


... Haier Air Conditioners

I have a heat pump with a ac unit. The condensation builds up in the coil area and will not drain out from the pipe? What is the problem this just started. And I'm selling my house. Help!


The pipe is plugged up. A lot of times you can disconnect it and blow thru it with some air and that usually opens it up. ... Air Conditioners

Where is the reset button on the outside American Standard heat-pump a/c unit?


... Air Conditioners

I need a wiring diagram for an American Standard heat pump condenser model #6h0024a100a1


... Air Conditioners

When I turn my electric a/c to heater it makes a repeat tac sound quite loud. An a/c tech opened the metal box on left side where the fuse is located and said that the board and relay needs to be replaced. My a/c heating unit is an American Standard made by Trane model TWV036B140A1. What do you think it might be the problem? What are the technical name or numbers of the parts the a/c tech is referring to? Where he or I can buy it and for how much? What is the guarantee? Thanks. Tommy reply2t


It sounds like the tech was referring to the blower relay. The blower relay on this unit originally had a small circuit board mounted to it. It's only purpose was to allow for delay off-time of the blower at shutdown. In other words, once the command ... American Standard Air Conditioners

Thermostat i have a lux tx9100e 7-day programmable thermostat . and a american standard heating&ac. how do i wire them up. elec heater 1ph. 2stage heater w/heat pump


My thermastat want stay set on one temperature,making my electrical bill real high what do i do change out the thermastat? ... Air Conditioners

Where can I download a manual for an American Standard heat pump? 2WCX3030A1000AA


Try Trane.com ... Air Conditioners

I have a 6 year old Carrier Performance 38yza. Having a problem with heat. First no heat at all heat pump or AUX. Found AUX heat strip were grounded out and have now been replaced. Second no heat pump, Compressor comes on for only 1 to 2 minutes then shuts down. Service call yesterday Tech says no signal from Carrier Programable T-Stat, jumper heat pump, low freon adds. Says T-stat bad, but puts back together. Heat pump works blowing 90 plus degree from vent works great all afternoon and into ni


This sounds like you have a freon leak. Most units never lose freon. So that is one problem that needs to be addressed. Here is some more solutions for you: Other things that will cause or aggravate\015\012ice are clogged filters, bad fan moto ... Air Conditioners

American standard thru-wall heater air conditioner (PTEC1501GAA) will not heat. When wall mounted thermostat is turned up for heat, the fan turns on but no heat comes out. I opened it up and checked the fuse which was okay. I suspect the unit is of mid-1960s vintage. I tried to locate a manual on the American Standard website but it was no help and mostly focuses on plumbing products. Ron


Sounds as if the heater coil itself is burnt out. These coils may be repaired if you can get an universial coil repair kit and rewire the heater coil yourself. Since the age of the unit is in question I don't know if it is possible to get a kit fo ... Carrier 52PQ307 Wall/Window Air Conditioner