Having problems with your Air Conditioners ?

Home unit 3 ton won't run

\015 The unit was running find, all of a sudden I went to turn it on but light's dim in home from compressor trying to start, 3 ton unit contact was good switch on compressor good no burn wire's 12 years old also not a heat pump, also have two capasitor big and small how do u check them, no leak.\015

Answers :

The small capacitor is for the fan motor the other for thecompresor .You can try conecting a booster (or hot start) in paralel to the comp.capacitor .If this doesnt work you have to replace the compresor.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Home unit 3 ton won't run


The small capacitor is for the fan motor the other for thecompresor .You can try conecting a booster (or hot start) in paralel to the comp.capacitor .If this doesnt work you have to replace the compresor. ... Air Conditioners

I have 2 cental a/c units in my home. The 2 1/2 ton unit cooled great until abut a week ago. Now I cannot get it too cool lower than 78-79 degrees and it runs constantly unless I turn the themostat higher than 79 degrees. The freon level is correct, the coils are clean and so is the filter. What do you think the problem could be??


I like this one it challenging first do you know the refrigerant pressure?should be at least 65 psi for r-22 has any thing changed in the ducting? is the fan turning the correct direction?dan ... Air Conditioners

I have an old Miller 3 ton heat pump. It will work fine sometimes but when it decides not to work i can go outside and press the power contactor and the unit will come on as long as i hold the contactor pressed. A friend told me the defroster board could be the problem because when its cooler than 45 outside it wont come on by itself. But when i measured voltage at the thermostat no wire had 24volts.When it runs it runs good and cools or heats the house well.


It sounds to me you need just a really good tune up maybe a new contactor retest your low voltage what do you have from common to 24 volts it should be 27 volts if you test each wire you want get 24 v it will be like 7 or so ... Air Conditioners

Unit wont shut off its a good man 2 ton its 90 right now it runs continuosly unless i pull the wall plug out 2ton good man had it put in in 2005 outside conenser and central unit and coil


If it is just the outside unit that will not quit running, it sounds like your contactor may be sticking. Remove the cover on the outside unit where the power goes in. You should be able to see the contactor. Turn the thermostat to off and see if it ... Goodman CKL60AR60 Air Conditioner

I am working on a M # GPG13420901AB. This is a 3.5 ton package unit that replaced a 3 ton package unit on 1700sq/ft single level home. Old unit was working fine but was replaced when the home was renovated. The new unit will not hold temperature in the home when outside ambient climbs above 83-85 degrees. Refrigerant pressures early in the day (70-80 degrees ambient) look fine 70 suction 200 high 9-11 degrees SH. Late in the day with outside ambients around 90-95 degrees, inside temps 75-78


It sounds like you are low on charge. I think you have a thermostatic expansion valve and you need to check the subcooling, you should have 12 to 15 degrees at 95. At 95 degrees your head should be about 280# for a 12 or 13 SEER unit or higher depend ... Goodman Air Conditioners

I have a new home that is near to completion. Two heat pumps (zoned) are installed and both are now running - house is completely closed and is comfortably warm. Only the downstairs pump is being used at the present. The upstairs thermostat is turned off. The downstairs pump cycles every 26 seconds, that is, on for 26 and off for 26. This never changes. The ext temp is about 56 and the thermostat is set to 68. The pumps are both contractor grade Carrier 13SEER, 2 ton units, and the total


Its not normal.It indicates problem with the thermostat.The thermostat is just not accurate enough, and is likely falling below the set-point and causing the system to run the minimum 26 seconds when the\015\012 timer expires. This ... Air Conditioners

Coleman CSC II cooling fan wont run mobile home unit


... Air Conditioners

Have a R-22 Rudd ait handler. Replaced the compressor with a 1.5 ton Goodman unit. My home is 1300 SF in NJ On hot days during the peak of the day the system seems to stop working for a period. The Compressor fan still runs but the compressor is not. My air handler fits the cubby hole and I am limited for space, as I considered replacing it. A tech has suggested replaceing the TSV valve with an adjustable and set it to 8. He also said there are supplemental coils that could be added to the com


If your home is 1300 square feet 1.5 tons is not going to cut it you should have at least 2.5 ton A/C unit. sounds like your system is to small. let me know if this helps you out. ... Ruud UAKA037 Air Conditioner

Bought a home with a ventmax air exchanger unplugged it and now wont turn on light on it shows power running to unit


... Air Conditioners

MY GOODMAN CPKJ24-1A UNIT WENT DOWN.TOOK FAN OUT SAW WIRES SHORTED OUT AND MELTED COMING OUT OF FAN MOTOR I REPLACED THE FAN MOTOR .THEN REPLACED DUAL RUN CAPACITOR THEN THE SWITHING CONTROL. TRIED TO START UNIT FAN RUNS AT A VERY VERY LOW SPEED AND SORT OF WISTLES WHEN RUNNING ALSO UNIT IS NOT KICKING OVER EVEN HAD CAPACITOR CHECKED WHY WONT MY AC UNIT COME ON


... Goodman Air Conditioners

Brand new unit have 3 ton inside and out but unit runs all day and will not hold temp i run my ac on 76 but as the day get hot the temp inside will not hold at 76 ARS says they dont know whats wrong but they installed the unit said i would have lower light bill but unit runs all day light bill 900 can someone help please with a solution


Call them back something is wrong if it is that new it is likely under charged. how big is your house square feet and what part of the country down south 400 square feet per ton if your house is more than 1250 square feet the unit is under sized ... Weather King 10AJA3601AH Air Conditioner

I have a Tempstar 9000 airconditioning unit and while I was weed wacking I accidently cut a wire to the unit. I replaced the wire but now the unit wont turn on and also my furnace blower wont work even in the "on" position. I have a energy saver unit attched to the a/c unit as well. One wire connects to the a/c unit and the other to the energy saver. If I push the connector on the unit with the panel off the unit will run. Cansomeone tell me how to connect those four wires?


Hello TLOEKS You blew the transformer FUSE inside the blower unit! It should be a 5amp blade fuse like the one that goes in a car.It is located at the curcit board at the blower compartment.Replace that to restore low voltage power and every thing wi ... Air Conditioners

I have an old unit approx.11yrs old.When turn on for heat,kicks my breakers off. It runs for about 1/2 hr. before shutting off. Tried running the emergency heat bu t, it continues to kick the breakers off within 1/2 hr. Were can I find parts for this unit, I just need to get through the winter. I will be leaving this home come the spring. I do not want to spend the money on a new system for a home I will not continue to live in.


Well, obviously your furnace is overloading the breaker it is on. Try this, turn off the breaker that the furnace is on and go through your house to make sure everything else still works. Furnaces are large power users and should preferably be on t ... Amana Air Conditioners

1996 Coleman Model 7333C8876. Have 2 units on our Motor Home one day it was hot so I had both units running controlled by a Electronic Climate Control system. It got cool in the evening so I turned them off. The next day when i fired them both up on high the rear was fine. But the front will only cool on Low. The fan will not run on high and you can hear a slight noise coming from the unit. But the fan will not run on high.


Check to make sure the drain tube is clear. It sounds like the blower fan is dragging in water buil-up. ... Air Conditioners

I recently bought a 4 ton 14.5 SEER Rudd Spilt system using R-410 and matching Rudd furnace. This system replaced a Lennox 10 SEER 4 ton unit. Now that it has gotten hot in Baton Rouge LA 90-93 degrees. I have a programmable thermostat see bottom. It takes the one hour to drop the temp. 1 degree so starting at 5:00pm the unit runs non stop until 11:30 at night. The Lennox was about 3 times better and it was 15 years old. The installer told me all high SEER units take longer to cool in comp


Sounds like the Unit might be low on charge.But without correct readings not sure.\015\012The new unit with 410 will actually cool better due to higher boiling point temp. of freon type.Poor air circulation could also cause problem.Such as dirt ... Air Conditioners

Air Cools well but after about an hour, water starts coming into the coach through the discharge air side. Unit does not freeze up but if I shut the unit off, the tray that holds the water drains quickly, but doesn't drain well when the A/C is running. I always run it at high speed initially, though when you put the AC on Auto fan, it starts at high speed anyhow. This unit is in a Newmar Mountainaire 40' diesel pusher motor home


Your evaporator is probably dirty and is blocking some of the air flow so the air has to move around the coil and starts coming in through the condensate drain holes. That stops the condensation (water) from draining out the holes because the air is ... Dometic Rooftop RV Air Conditioner

We had a new American standard furnace and A/c unit installed. A 2 ton compressor and a 2 and a half ton A coil. The unit is not cooling the charge was checked and it is ok. Unit is on and blower working and in cooling mode. At start up it was producing 49 degree air at the coil now it is running 68?


Make sure orfice used was for two ton unit and correct refridgerant also make sure that the elect auk heat is not pulled in check the psi on out door unit should be close to 225 hi side and 70 suction if heat pump switch the reversing valve man by o ... Air Conditioners

Hi, We have two Paragon split systems which effectively cool our large home. One system is playing up. It started 3 days ago where there is water dripping from the front of the unit and the green 'run' light is now flashing. I tend to think it's blocked somewhere, buy my husband cannot find where to check this. Our outdoor units are both under the house with very effective ventilation but the last 3 days have been extremely humid, however the other system is running perfectly. Any ideas? Thanks,


More then likely the blockage is inside the a-coil section. At the drain. To get to it easier remove the pvc drain line. As the drain line comes out of the collection pan it goes into a pvc line the 90 degrees elbow goes to floor. So cut the lin ... Air Conditioners

Blower fan in the inside unit tries to turn on but wont. It can be turned manually and air conditioner comes on and runs fine. The " squirrel " cage spins completely freely and is not sticky or jammed. Is the motor bad or is it a run capacitor. Model number of inside unit is a49-15


\011Sound more like the cap, but if the motor is raging hot, it could be the motor, another thing it could is improper voltage although less likely. But Goodmans/ do have this weird fan relay issue were they just bite it some times. I wo ... Goodman Air Conditioners

I have a Coleman Heat Pump, The unit all of a sudden just keeps running, and wont shut off. The only way to shut it off is to turn the breaker off..Will this hurt the unit by running all the time...I need help to figure out whats wrong with it..


Hi,\012Yes, that will hurt it.... the contactor has wleded shut and keeps it running...\012 \012 \012Here is a tip about trouble shooting your ... Coleman Air Conditioners

Working on a Carrier sx from 1990, has three wire bi-metal pilot with spark and 100% lockout on the spark module. Homeowner says it only fails in cold o.d. temps (less than 35 degrees). Home owner finds unit off and silent, resets 120v and unit re-lights and runs. Don't know what parts have been replaced so far but it looks like a new spark mod. and the pilot was clean but I cleaned it again. Limit switch looks old but I think limit failure would cause the blower to run. Any ideas?


Check the heater relay on the control board found in the blower part of this furnace. It's found in a steel enclosed box I'm having the same problem currently. I now have the blower running constantly set the thermostat to on not auto. until th ... Air Conditioners

We are about to install a a new central heating & air conditioning unit in the family home where my brother lives. It has a 4 ton now. Can we up grade to a 5 ton? One dealer says yes- another says too large a unit may cause too much moisture and also mold. HELP!!!


Hi, go with the 5 ton unit. 12,000 btu's are not going to cause moisture or mold!! I have done this for 33 years, do know what I am talking about and would not steer you in the wrong direction. Go with the 5 ton unit, and remember this for some knole ... Air Conditioners

Furnace trouble Working on a Carrier sx from 1990, has three wire bi-metal pilot with spark and 100% lockout on the spark module. Homeowner says it only fails in cold o.d. temps (less than 35 degrees). Home owner finds unit off and silent, resets 120v and unit re-lights and runs. Don't know what parts have been replaced so far but it looks like a new spark mod. and the pilot was clean but I cleaned it again. Limit switch looks old but I think limit failure would cause the blower to run. Any idea


... Air Conditioners

I got this A/C unit when I bought my home two years ago and do not know how old it is and whether it is worth repairing. I had an electrical surge into my home and now the A/C unit will not run at all.


Is it a window shaker unit? just toss it get a new one ... Maytag M6Q10F2A Air Conditioner

Hi, just replaced the capacitor thinking that would solve the problem but it appears it did not. The motor outside would kick on the unit inside would kick on but the blower motor inside works sometimes and wont other times. Basically, the unit will work just fine all day then we notice the house is getting warm, check the inside unit and everything is running fine but the blower motor is not circulating the air. I have a goodman a30-10 unit. I read where some people said the relay could be bad


Turn off the power to the air handler(indoor unit). Remove the access panel. From the motor,trace the wires back to the fan relay. One wire will probably trace back to the incoming power terminal. The other is the fan relay. It could be intermittent ... Air Conditioners