Having problems with your Air Conditioners ?

Thermostat I have a RV with a coleman unit, unit run fine, but the thermostat blows the 2.5 amp fuse, I change to a 5. amp and it still blow the fuse, it will run for two day some time a week before it blows it out. What can I do.


Answers :

Several things cause fuses to go. But you ace in the hole is that it works for sometime before it goes out. This suggests that a relay or contactor is not pulling in as it should. I would try replacing the fan relay (if so equipped) and definitely the compressor contactor. If either of these try to pull in and are off center internally the result can be blown fuses intermittently.

DO NOT GO ABOVE 5 amp fuse or you may burn out the transformer.
The other things that can cause a blown fuse intermittently where your describing (although less likely unless subject to rodents and or high or low voltage spikes)
1 a temporary short in the control wiring (wire to or from the thermostat).
2 A short intermittent on the control board (if so equipped)
3 A relay on the control board or the SS circuitry is not operating with in design parameters.

I would really like to know what you discover the problem is.

If this helped you understand your system or problem please rate me as high as you can and thank you for using fix ya. Good Luck.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Thermostat I have a RV with a coleman unit, unit run fine, but the thermostat blows the 2.5 amp fuse, I change to a 5. amp and it still blow the fuse, it will run for two day some time a week before it blows it out. What can I do.


Several things cause fuses to go. But you ace in the hole is that it works for sometime before it goes out. This suggests that a relay or contactor is not pulling in as it should. I would try replacing the fan relay (if so equipped) and definitely th ... Coleman Mach III Air Conditioner

Air conditioning unit not running but fan keeps running even though thermostat is turned to off, auto, and temp set to highest position 90degrees. 3 amp fuse keeps blowing on the circuit board in the blower compartment. I replaced it 3 times then installed a new thermostat. no change. I can usually figure it out if I got a little input or direction. Any help would be deeply appreciated. I would much rather have a trained expert easily repair my hvac unit but I can only call the professionals in


If the fuse is blowing then this is generally indicative of a short in the low voltage wiring, isolate the wires on the thermostat and the unit ends, use an ohmmeter to verify that there is no path for continuity with no wires touching, if there is t ... Air Conditioners

When i tunn on my AC unit at the thermostat it blows the 3 amp fuse in the air handler when it call for cool when i switch the t stat to off and just turn fan on the fuse does not blow and blower runs


Sounds like the compressor is or a electrical component directly linked with the cooling operation/ outdoor unit running.Possible short to earth....cheers ... Ruud UBHC Air Conditioner

Our inside unit Coleman EB20B (outside unit Goodman GKL 49-1) keeps blowing the in-line 3 amp thermostat fuse. We've rewired the wires in the wall, rewired the contactor wires, and the contactor was broken so we replaced it. We're still blowing the fuse. Could we have reversed the thermostat wires at the contactor? Or could the short be in the Blend Air box-this box is coupled to the thermostat wires? Thanks Ken Rohm


Hi,Mark\015\012 all your wires using tape or by writing it down to ensure you will be \015\012able to hook them back up exactly the way you found them. Remove all the\015\012 wires from your board again. Tape off the ends so you don ... Coleman Air Conditioners

The Coleman Mach thermostat in my 5th wheel blows its 2 A fuse a couple of times today and am trying to figure out what is causing this. Please help. I am unable to get the furnace to run even with a good fuse in the thermoatat. When I bypass the thermostat to run the Atwood furnace (red tied to white wire). THe furnace blower comes on and the burner sounds it lights for 5 seconds and then goes out. 15-20 seconds later it reignites and goes out and continues to cycle -- the blower motor


Hi\015\012\015\012Its blowing fuses because of short circuit inside the coleman mach or due to two wires being shorted with each other. You'll need to open up your thermostat system to look for the short circuit and also shorted wires.Ple ... Air Conditioners

A/c will not continue to cool.. Starts fine, runs fine.. but shuts down cooling ( comp shuts off but fan still runs) after anywhere from 5 min to multiple hours. No circuit breakers or fuses blow. CAN usually reset by cycling wall thermostat if that does not work can unplug 12v. connection to thermostat and it will most often start cooling again when asking via the thermostat. Have replaced computer board in a/c unit on roof and wall thermostat


One amateur test is to place your hand on the compressor and see if it\015\012is too hot to hold your hand on it. You may have a restricted condenser coil \015\012If it is too hot then the condenser coil is restricted inside the unit ... Dometic Rooftop RV Air Conditioner

I have an old RUUD central AC unit that started blowing hot air. I set the thermostat to off and set the temp gage higher than air temp to turn the unit off and save money, but inside blower unit runs constantly. I'm trying to save money to have it serviced, but noticed my electric bill was higher that last month when the ac was working. The bill was about 4 times higher than the winter when ac is off and the gas heat kicks in. Can the blower running constantly cause this power usage and what is


HelloOkay did you check your thermostat to see if you have the fan switch on auto? The switch must be on auto or the fan will continue to run. If the thermostat fan switch is on auto then there is a malfunction in the thermostat probably ... Air Conditioners

I have a Carrier 38tra048340 ac 4 ton unit outside, heater in attic. Thermostat is Totaline P374-1100. Power went out than back on after a few hours due to vehicle crashing into power pole. AC was running at time of power outage. Power came back on, ac would not come back on. Checked house circuit breakers, none tripped off. Turn ac 40amp breaker and heater 20amp breaker off and back on. Voltage ok. Checked fuse box by ac unit on wall, fuses and voltage ok. Went into hot attic to check for powe


Blank screen sounds like a fried thermosat. Abrupt outages can affect certain types of thermostats. Make a jumper wire and jump across R and G. See if you get any action from anywhere. If a fan or compressor kicks in you know you have a burned out th ... Carrier Air Conditioners

Bryant 583b not running blows 5 amp fuse


... Air Conditioners

A/C not coming on. The thermostat is set properly to cool, the temp to 67. However, on the interior fan runs and it does blow cool air but seem weak. I went outside to the A/C unit, and nothing is moving. I checked the circuit breaker and the exterior fuse box, but nether are tripped. The A/C unit is a Goodman SSX 16 series.


Hi,You can use this link.(inspectapedia.com/aircond/aircond1123.htm).Hope it helps. ... Goodman Air Conditioners

I have a goodman furnace and ac unit the fan and heat work but every time i turn the ac on it blows the low voltage fuse ive replaced all low voltage wires to outside unit and thermostat i also replaced the board in the furnace and transformer


Look at the contactor on the condensing unit, remove the low voltage wires to the contactor and turn on the system. If the low voltage fuse doesn't blow, replace the contactor. ... Goodman CLQ36AR49 Air Conditioner

We have had a coleman central air system for 5 yrs. It stopped blowing cold air into the house about a week ago. You can still here it running but no air is coming out. my husband replaced the fuses and over night it did the same thing so when my husband went to check out the unit outside he said that the line had ice on it. Is there a filter within the central air unit that needs replaced?


Ice is an indication that the refrigerant is not flashing off correctly in the evaporator coil. In most cases you can simply turn the unit off (until it completely thaws inside and out) and replace the filter. Make sure that all the vents in the hous ... Coleman Air Conditioners

Kenmore 73089 AC keeps blowing the control board. (Doesn't respond or light up in any way when power button is pressed. Outlet power is good.) A repair tech replaced the board last summer. It blew again this July, and I replaced it myself. It just blew again, six weeks later. Runs great otherwise. Seems to blow after a period of prolonged usage, though this time it popped during the night when load was reduced. The fuse on the board seems okay, shows continuity on multimeter. Any idea what


... Kenmore 73089 Air Conditioner

The fuse on the control circuit on the inside unit keeps tripping One side of the fuse goes to the thermostat the other side goes to the control board the fuse blew about a week ago let the unit sit for a week while we were out of town. put another fuse in it ran for 5 days fuse blew again let unit sit for 2 hours then the fuse held not sure what to check


Its hard to say without being there but here are somethings to check. Outside check the thermastat wire onthe condensing unit. I have this problem a lot down on the gulf coast. The wind blows and cause the Tsat wire to rub against the unt and it shor ... Air Conditioners

I have a Ruud air-conditioner/heat pump and it blows 5 amp fuse.


It sounds like the thermostat wire going to the condenser is ground, It either got pulled loose and is touching the housing or as in most cases the wire got cut or was chewed by an animal. You need to turn electric off to both devices and physically ... Ruud UBHC Air Conditioner

Borg warner Is the old round York Borg/Warner thermostat incompatable with a Honeywell? I just replaced my old round mercy switch thermostat with a Honeywell RTHL111 thermostat. The air conditioner service man says it is hooked up right, but the fan on the unit will not run on auto (it must be in the on position on the thermostat [thus the fan runs all the time]). He also replaced a relay switch inside the unit. We are using air conditioning only on this unit. Red to R (strapped to Rc), gree


... Air Conditioners

My Dometic rooftop rv ac runs for approximately 5 minutes. During this time the fan blows cold air. However, after 5 or so minutes, the unit stops completely except for a humming sound. I turned off the thermostat for a few minutes and turned it back on. The same thing happens repeatedly. Do you have any suggestions?


Thermostat or relay module ... Dometic Rooftop RV Air Conditioner

5 amp fuse in central Airconditioning unit keeps blowing, I keep replacing, somtime is good for long time and sometime for really less than a day


You have an intermitent short in your low voltage wires. You need to trace the wire all the way to the A/H and then to the condensing unit. I bet you will find a bare spot. Check where the wire goes through the brick to the condensing unit. Ground sq ... Bryant 462AJC021BA Air Conditioner

HAVE A COLEMAN MODEL DRHSO601CB --- THE UNIT WILL RUN FINE FOR SEVERAL HOURS WITH GOOD COOLING AND THEN PERIODICALLY THE TROUBLE LIGHT WILL COME ON THE THERMOSTAT AND THE UNIT HAS SHUT DOWN. TO RESTART - YOU MOVE THE THERMOSTAT TO OFF WAIT 5 MINUTES OR SO AND PUT IT BACK ON COOL -- IT WILL RESTART ALMOST EVERY TIME AND RUN FOR SEVERAL HOURS. IN THE PAST IN THE PAST I REPLACED THE DEFROST CONTROL BOARD BUT WHEN I DID THAT THIS TIME IT STILL SHUTS DOWN - WHAT OTHER PROBLEMS ARE YOU AWARE OF ON TH


You may have a low pressure or high pressure switch tripping out the board as well. You might try cleaning both the indoor (evaporator) coil and the outdoor (condensing) coil. Be sure to turn off the power source before servicing this. ... Coleman Air Conditioners

My comfortmaker heat pump blows the 5 amp low voltage fuse after a few minutes of heating time.


... Comfortmaker C4H436GKD 3 Ton 14 Seer R410A Heat Pump W/ Air Handler

I recently had a new outdoor unit installed on my central heat and air conditioning sytem. I have had the installer out 3 times and the system still does not operate correctly. Sometimes when it cycles (every other time or every third time) the unit does not blow cold air. Sometimes the unit comes on not blowing cold air and the compressor fan is running but not the compressor. Sometimes after 15 minutes of this the compressor will come on. What is the problem.


It sounds like the compressor needs starting components installed on it. All a/c units have a run capacitor for the compressor and another one for the condenser fan motor. These motors use these capacitors all the time when the motor is running. H ... Air Conditioners

Constanly blowing fuses in thermostat


U have a short some place jumping the fuse wreck the transformer controls good luck Tom ... Air Conditioners

3 amp fuse blowing in York central A/c


Hope things are working for you now. In any case, Keep a couple of things in mind. The control (thermostat) is low voltage.A not so simple,simple switch that obviously senses ambient temperature and at a preset time will Or temp will switch on a sec ... Air Conditioners

I have a dometic duo therm rooftop a/c on my camper. On initial startup, the unit performs fine and cools until it reaches the setpoint of the thermostat. A few minutes later though after the thermostat calls for a restart, the unit will run for a short time and then the breaker will trip. On occassion, I can reset the breaker and get the unit to keep running. This appears to occur randomly though. I'm thinking it's one of the capacitors?


Possible capacitor, but I'd check what else may be drawing power at same time in trailer. Try running everything possible on propane rather than hydro so that there is no other, or minimal current draw besides AC, and see if that makes a difference. ... Dometic Rooftop RV Air Conditioner

Goodman a/c j41 fan not running, turned off and on at fuse box, took a look at the box next to a/c unit and opened the box on the wall and pulled the plug and pulled the plastic panel off, there is no fuses. So i put back together and turned the a/c unit on, now at thermostat the snowflake is no longer flashing, some cold air coming out of vents, but outside a/c unit fan still does not run.


First you need to disconnect all power. Try spinning the fan blade, if it spins freely, then try moving the shaft from side to side to see if there's any side play. If not then the bearings are OK. If there seems to be some drag when your spinning th ... Goodman CKL42AR42 Air Conditioner