Fan on heat pump not running, unit is froze up

\015 Last week it had a noise like a marble rolling around in it. All this week it would run when outside temperature went up. Now it doesn't run at all.\015\012Is there an inexpensive way to fix?\015

Answers :

I called a repairman. As I was told by AARP, this was a free site, not advised of any fee to find a solution since I know I am not the only one with this problem.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

This is a heating and cooling through the wall heat pump. It works normally when heating is selected - the heat pump runs and both speeds of the fan blow warm air. But nothing runs when cooling is selected. In other words the unit works normally when "High Heat" or "Low Heat" is selected but nothing runs when "High Cool", "Low Cool" or "Fan Only" is selected. The position of the Fan Cycle Switch has no effect - behavior of the unit is the same in both positions of the Fan Cycle Switch.


You have a bad board or bad switch. I would say board. You can have service tech check this out. There is only so far you can go without knowledge of Controls ad electricity. Russ ... Air Conditioners

Friedrich YM18 230 volt heat pump. The unit has heated and cooled well for about 5 years. Just started heating mode recently and the unit no longer heats. Fan runs OK. Was able to get the heat strip to run for a few minutes (smelled the dust accumulated over the summer burning off). Now, no heating whatsoever. When in the "Money Saver" mode, nothing happens. Fan will not come on and unit will not heat. With "Money Saver" mode off, the fan runs.


... Friedrich Air Conditioners

Fan on heat pump not running, unit is froze up


I called a repairman. As I was told by AARP, this was a free site, not advised of any fee to find a solution since I know I am not the only one with this problem. ... Air Conditioners

I have an LG mini split ac / heat pump system ( LAN096 ) that is only 4 months old was working great in all ways until suddenly it quit heating. I am sure it happened quickly because I was nearby when very warm air changed to cool ( unheated ) and hasn't heated since. When I shut it down and restart it the indoor fan runs right away, which is not normal and the outdoor unit will run for a minute or so then shut down and stay off. The indoor fan will continue to spin as though it is set in a 'fan


... LG Air Conditioners

I have a Rheem heat pump/air handler; it draws 2.9amps with only the fan running, 13amps when the heat pump is running and 38amps with the heat strips on. My question is why the unit draws that many amps when in heat pump mode? Isn't all of the work being done by the compressor outside?


You gave us some good clues, and figures to work with-- THANKS!!To answer your question: Your unit switches the one compressor, from cooling, to heating, by reversing some valves-- Same compressor-- just routing the refrigerant i ... Air Conditioners

I have a 2 year old Duo Therm 15,000 btu Heat Pump AC unit in my RV. The compresser will not come on or even try, in either cool or heat mode, the fans runs in either auto or on position. I have a wall thermastat, all wires & connections at the thermastat and the controll box look good. The units was running fine, with no prior symptoms and then it just stopped cooling. I have a strong electrical background with all the meters, I am just not famaliar with RV AC units. Bud De Fore don


Hello Bud,First of all, is your wall thermostat a digital thermostat, like a 4 or 5 button Comfort Control Center? Is the ambient temperature under 40 degrees?Is your fan still able to run, are you able to control ... Dometic Rooftop RV Air Conditioner

My indoor unit on my heat pump will not shut off. The electric heat keeps running, and the fan keeps running. It only happens when it is really cold, like 25deg or below, above that and it functions fine. The outdoor unit shuts off, but the indoor stays running. I do HVAC work, but I have never seen a problem like this. I have switched the stat out, and its just so strange. I figured the relay may be stuck, but if I turn the stat off, it turns off shortly after which tells me it may not be the c


I would venture to say your stack relay is getting stuck. either that or you have a short in your low voltage wiring somewhere that is not always making contact....or it may be making contact through another median...like ice or frost. Remember ele ... Intertherm P3RA-036K Air Conditioner

I have a Toyo Aircon split unit Airconditioner/heat pump. 12000 Btu. When in the heating mode, I get the code E8 after it runs for 5 to 15 minutes. At that point it seems to run (at least the internal fan), but the heating aspect seems to be marginal (about the or just above room temp), keeping the room several degrees cooler than what is set. I have been unable to find any source for support of these units. The warranty phone number says it is not connected. Thanks Ed


You might want to refer to the unit manual, which has a fault code section (if the unit has a manual), look up the fault code E8, in the manual and it will tell you what fault it is. Depending on where the unit was manufactured, you may not be able t ... Air Conditioners

I have a rheem electric furnace with 2 speed fan, seems like the fan runs full bore when its on, even when i just cycle the blower control to ''on'' and its supposed to run at reduced speed. I have to experience with central heating and air, was wondering if it would be the circuit card with the dip switches. Unit was installed in 2003 with a heat pump.


If it is a variable speed blower most likely the dip switch settings. Check the installation manual to see how to slow it down. ... Air Conditioners

I have a dometic heat pump a/c basement park model unit. The fan is not working. The compressor runs, but no air inside or out. I have power into the run cap. but not on the brown wire to the fan from the run cap. I also have no power to the fan high or low off of the relay board. Where do I go next to isolate?


... Dometic Air Conditioners

The outside unit on our Ruud heat pump won't turn on. The inside fan blows but the unit outside sits idle - no fan turning, nothing. It was cooling earlier today, but when I came home from shopping, the house was warm, the inside fan was blowing, but the outside unit is silent, not running.


First look for red button neer the copper line set if has one push it second inspect thermostat wires for weed eater damage check disconnect for fuses check breaker at main panel pull disconect and remove cover check stat wire connections look at the ... Ruud UPMC036 Air Conditioner

I have an Interthem / Nordyne heat pump model E2EB-015HA. On the outside unit the fan does not turn on when the unit comes on. If I spin the fan it will come on and will run well. With the unit off the fan blades spin easily. I suspect the capacitor, but can not find a part number for it. The capacitor itself is rusty and any writing is unreadable. Please help.


Not sure what Country you're in but the Part No for the Run Capacitor is 1499-4461 and can be purchased from the following link.\015\012\015\012htt ... Air Conditioners

I have an American Standard Heat pump. The unit is one piece is is outside. The problem that I have is that sometimes when the unit kicks on cool, the fan motor will not start. The compressor will run, but quickly freezes up. I can put unit in off and wait for thaw and then put back in cool mode and fan will start. Any ideas?


Definitely a low voltage problem then i would look for the obvious like loose connections good luck you might have to call a tech ... Goodman CLQ36AR49 Air Conditioner

Bryant air conditioner - outside unit will not run - before it quit running, air temperature in house rose from 65 degrees to 75 degrees. Inside fan continued to blow - air smelled like a car air conditioner that ran out of Freon. Bought Freon - need to know where to add it. The heat pump model # BF-163S bi directional but also coming from unit is another line that runs same direction with same type of valves. Air conditioner model # 697CN030 - B


... Air Conditioners

Have a Grand Aire Central Air and Heating unit a/heat pump...has been working fine. Switched it over to heat and nothing came on. Switched it back over to air, which was working and still nothing came on. Switched fan from ''auto'' to ''on'' and the fan will not come on. Used a screwdriver to push the contact in and everything runs (air and heat) as long as I am holding the contact in. Changed the t-stat, still the same problem. I really don't have the finances to call a pro in, any advice will


The fuse may be in line (red ) wire check control voltage if not present transformer (or fuse) needs replaced \015\012 the problem probably was caused by white wire (heat control voltage) has been wired to common not heat control ... Air Conditioners

I have a rheem 030jaz (heat pump) that has been affect by lighting that hit the house. I have change the transformer, zone board, and what I thought was a bad fan. What happens now is where it gets crazy. The unit will run for about 30 minutes then the cold side of the compress will begin to freeze. When this happens the fan will turn off and the compressor still runs. The evaporator is clean enough to eat off of. Pressure readings for freon stay consistent through out the freezing stage. This t


Hello Sounds like the reversing valve is not changing over during the defrost cycle.The R/Valve selonid coil could be damaged. ... Air Conditioners

RUUD UBHC-17J14SFA HEATING PROBLEM. Is there a way to make the Return fan run slower, The noise is driving me crazy. The Unit pumps way more air than required. On a previous unit i Had -- all that was required was moving one of the wires onto another Contact and it reduced the fan speed. Many Thanks Barry


... Ruud UBHC Air Conditioner

I have a Coleman 5T 13 Seer Heat Pump. When the unit is running there is a lot of vibration (outside unit) and I hear a tinny sound (possibly like the fan hitting something). This seems to be worse during the hottest part of the day. When the unit had its last service they said it was low on freon and recharged it and it seems to be since then that the problem has occurred. Is it possible that the unit is overcharged? And if so is this dangerous, i.e. could it cause permanent damage or immi


I have a coleman mach roof air on the RV. It keeps blowing the 3amp fuse. Why?? ... Coleman Air Conditioners

I have a Kewanee model#1736 hot water boiler furnance which is gas fired.I had to change the heat pump and the heat pump switch.The heat system is wired through a Webster Heating Contol unit which has three settings,Run,Auto,and Off.Normally when the heat control unit is in the Auto position the furnace and heat pump will start and run automatically until it reaches the desired thermostat temp. Then both the pump and the furnace would shut down at the same time until the thermostat falls below t


The thermostat turns the Boiler and the Heat Pump on simultaneously???....That doesn't sound right...normally the Thermostat brings on the heat pump first and if the temp continues to fall (Its Cold out) then the Boiler would kick in about 2 degrees ... Air Conditioners

I have a Lennox model CB19-51-1P air handling unit with HP19-511-1P compressor heat pump unit. I just turned the heat on for the first time this season. And I am getting low heat volume. The heat pump unit is running for long periods. I am getting enough heat to maintain the 70 degrees setting with constant cycles, shutting off for short periods, running long periods. When the thermostat is turned to a cooler temperature, the unit shuts off as it should. Could you please help trouble shoot po


First thing you need to check is if the reversing valve is working you maybe running your A/C with the heat strips on depends on the t-stat your using some heat pumps will bring the strips on with a high d ... Air Conditioners

Haier hsu 18 heat pumps . I have 6 of them , all intermittently come up with e17. otherwise sometimes they will just blow fanned air ( compressor not running ) all day . The power source is fed to the indoor unit first, with the main power and data then fed along the same standard 4 core cable to the outdoor unit. I have fitted one of these units which had this problem to another site , and instead of wiring it as per the above way (as per instructions) I put the data cable seperate to the oth


... Haier Air Conditioners

Air Conditioning I have a ruud system with the air conditioner outside and the air handler upstairs in the attic. My systems appears to be running, and I can feel cold air at the vents, but I can barely feel it. Like there is no flow. The fan outside is running and the unit in the attic is running. I have no clue what the problem is. The large coil coming from the heat pump outside is cold and has condensation on it. It also seems to have a little ice. It has been extremely hot here in Ge


Open the access panel on the air handler in the attic and take a look at the evaporator coil. If you have no airflow, and you just changed the air filter, then you probably have a buildup of airborne crud on the coil that's blocking airflow. \015\01 ... Ruud UAKA030 Air Conditioner

I have a Rheem A/C Heat Pump split with gas backup. The gas unit is mounted in the air flow directly before the A/C HP coil. Should the gas unit be wired as stage two heat, or is it OK to wire it as just aux/EM heat? There is no other heating unit. What is the difference between stage two and aux? Please note that the aux gas heat cannot come on if the heat pump is running or it may hurt the heat pump due to the gas heat units location.


Stage 2 is okay as long as there is a fossil-fuel kit accessory wired in the field control wiring. EM heat would only allow gas furnace operation if the thermostat is set for EMER HT mode.......this is not ideal and not recommended. Dual-Fuel applic ... Air Conditioners

Ge ptac zoneline AZ52H07DABM1 cannot find any literature on this unit. Fan speed is constant low speed (regardless of setting) Guest complaints on this room are piling up, and I need some literature to properly t-shoot this unit. I did see a reversing valve, so it must be a heat pump model, but the compressor will not run in that mode. Outdoor air temp is 55 degrees. Can you steer me in the right direction? BIG THANX IN ADVANCE. Tom in Okemos, Mi.


Hello Tom ,   I'm sure i can help you with this.... I work on these units everyday. unfortuneately im not there to put my hands on it but i will explain as clearly as possible.    The most common problem I tend t ... GE Zoneline Deluxe Series Cooling & Electric Heat Unit AZ25E07D3B

The fan on my outsie unit of my grand air heat pump won't turn on. The compressor hums. If I manually turn the fan it will run but very slowly.


Your description is possibly a bit vauge for the problem it could be, but starting from the compressor, question is "can you hear the compressor running"? If you can then switch off quickly and check the cooling fan capacitor. almost certainly it ha ... Goodman CLQ36AR49 Air Conditioner

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || www.ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.1393 seconds