Air condition. not cooling the house

\015 There is cool air coming from vents, not strong. and the fan is working outside. set thermostat on 70 and it shows it is 85. have to set thermostat on 60 to barely get it to 75, it never quits running, to stop it i have to turn unit off or set thermostat to 90 is it my thermostat ( it is the older ones with the mercury) or does my unit need to be charged?\015

Answers :

There is a possibility that though the outdoor fan is running, the compressor inside the condensing unit is NOT running. That would also explain continual operation without a satisfactory drop in indoor temperature.
\012
\012It could be low on refrigerant which can cause the compressor to overheat and shut off on its internal overload but the outdoor fan would continue to operate normally fooling you into thinking the compressor is running.
\012
\012It could be a burnt wire on either the compressor or on the contactor that's not allowing the compressor to start or it could be a 'shorted' or 'open' capacitor that's caused the compressor to overheat.
\012
\012If the outdoor coil is impacted with dust, lint, grass clippings or other debris it could be restricting the airflow across the coil causing it to overpressurize and shut the compressor off on a 'manual reset' high pressure switch.
\012
\012And then, another cause could be a low refrigerant charge requiring a leak test, repair and recharge.
\012
\012...and like the other good suggestions, a good cleaning of all components will never do any harm.
Both evaporator and condensor, indoor and outdoor coils need good airflow thru them for cooling. The outdoor coil can be hosed clean with water. The thick copper line that returns refrigerant gas to the compressor should get cold, sweaty cold. If the coils are clean and the return line to the compressor is not cold, then it may need recharging with refrigerant after leak checking.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

We have just purchased a new heating and air conditioning system in our house the air conditioner is putting so much humidity in the air that it does not cool the house, we purchased a 2 1/2 ton unit for a 1650 sq ft. house. what needs to be done to get the humidity out? the old unit worked better than the new one.


Is there a humidifier on the furnace? ... Air Conditioners

I have a hunter programable thermostat model number 44422 and the condenser outside will not kick on The fan is working inside but I have no cool air(air conditioning) I do not understand why the outside condensor will not start to cool It is so hot in the house Could the thermostat be programmed is so how do i deactivate it to so the condensor will work Thank you


The outdoor unit has failed in some way. This is probably not the thermostats fault. You can check the breaker for the outdoor unit by turning it off and then back on. If this does not work, the problem is most commonly one of the following issues. A ... Hunter Air Conditioners

My carrier air conditioning unit does not cool below 72 degrees. I was continually running to the point the outside unit connection to the house was frosted. I turned the unit off and let sit for a few hours. Turned it back on and the Thermostat seems to be working; however the unit can not cool the house below 72 when it had in the past. Am I looking at a leak or re-charge???


The unit has lost part of it's charge, and will need recharged. For that reason a leak must be found and repaired or it all will reoccur again. ... Carrier 38CKC030 Air Conditioner

Aircondition I have a air conditioner problems, the unite inside the house is working I can hear it and feels the air coming out of the vent but it's not getting cool air, the unite outside all I hear is click once and about 2 to 3 mint. click again. I have the other air condition next to and it click and then seem to locked and worked. help..


You will need an OHM meter to check the relay and compressor. Make sure all power is off. The most common types of compressor winding failures are open, grounded, or shorted. You have to know how to read a meter. If you don't find someone who can. Or ... Ruud UAKA030 Air Conditioner

My air conditioning units work. They are cooling. The thermostats say 76 degrees. The problem is the hot dry smelly attic-like air that is constantly circulating and blasting down on me from the air vents. I have dry red eyes, a raspy dry throat, stuffy and bloody nose. (I am not sick. This happens every afternoon, all summer long.) This all happens during the hottest time of day, past noon and into the early night. I have had A/C techs out here to check the units and check the flow in the house


The techs probably checked the units operation,but did they get in the attic to see that the duct work on the return air side of the unit is tight and not sucking in the attic air. ... Air Conditioners

The air condition heat pump will not keep the house cool we have it set at 73 degrees and it is 83 degrees in the house The unit is about 4 years old and i haven't had this problems before , the technicion says he can't find anything wrong with it.Ihave a 1400 squire feet house and a 3 ton unit


Hi,Here is a tip about trouble shooting your air conditioner... ... Weather King Air Conditioners

My air conditioning unit is not cooling as it should and I had a person come over to my house and he told me that I might have to much gas in it so they took some out. But it doesn't cool very well anymore. What is the exact amount of gas that it should have?


The exact amount of gas you need in the unit is usually right on the label of the unit. By the model and serial nuber you will find the refrigrant type and the charge amount in oz. It also will specify the amount needed if the lineset is over XX numb ... LG LS-K1830CL Cool Mini Split Air Conditioner

Carrier 38CK036330 Hi,  I totally know nothing about air conditioning. It's getting so hot in LA and we really need help since our house has a 18-month old child. We have a Carrier 38CK036330 central unit, and it's not cooling the house as we'd like it to. It's already about 13 years old and we are looking for a new one to replace it. The question is we cannot find this model anymore, or do we have to replace it with the same model?? What model or brand would you suggest for a 1350 square feet h


The model numbers change.You have a 3 ton system.The make and model that you replace it with is not nearly as important as a quality install.Do your homework on picking a contractor that you can trust.Have them do a load calculation to make sure a 3t ... Carrier 38CKC060 Air Conditioner

How many tons is my CKL 36-1K air condition? The data plate was removed by someone over time and my house doesn't seem to cool efficiently so I thought maybe the unit wasn't big enough, my house is 1564 sqft.


3 ton unit the 36 in the numbers means 36 thousand btu 12 thousand btu per ton ... Goodman CKL36AR36 Air Conditioner

Air condition. not cooling the house


There is a possibility that though the outdoor fan is running, the compressor inside the condensing unit is NOT running. That would also explain continual operation without a satisfactory drop in indoor temperature.\012\012It could be low on ... Coleman Mach III Air Conditioner

Hi My Danby 6000 BTU window air condition is not cooling. I set thermostat to maximum cooler level as 8 but still not cooling room. I clean all the dust with wire brush. Fan is working fine and I can feel lots of air comming through the air condition but no cool air.


... Danby DAC6003D Air Conditioner

After a cooling cycle, when the thermostat call for more cooling, it take up to 5 minutes after the air handler starts for the compressor motor to restart. The top fan operates on the outside unit, but since the house is not circulating cold air, only the room tep air the house heats up about 3 degrees before the compressor comes back on and cool air begins to come from the ducts. Yes. I know there is a safety feature to protect the compressor, but can the cycle be shortened?


No, this cycle cannot be shortened due to the simple fact that this feature is in place to protect your system. Even if it could be, I wouldn't recommend it.Mat ... Coleman Air Conditioners

I have a Rheem CLassic 10 Seer Heat Pump Model Number is RPKA-035JAZ I'm not familiar with certain terminology, but basically, it seems as though the unit is not cooling down the house anymore. It is just blowing air. The thermostat is not on "Fan", it is on "Cool". The central air system is not on "Auto" but "On" for continuous cooling. The temperature is on 65 degrees but not change has been made. It's not hot in the house but it certainly isn't cool and it feels as the there is less air p


Hello my name is Heath it will be my pleasure to assist you. The auto or on switch is the fan switch put this on auto. Then on the thermostat set it to cool and turn the thermostat down and the outside unit should come on and the house should cool d ... Air Conditioners

I have a Carrier Model 38EN036320. The air conditioning runs, but the house isn't cool. We've replaced freon twice. It runs cold for a few weeks after freon input and then returns to warm. Any suggestions???


Hello Casey, it sounds like you have a cracked flair nut or the flair is not made correctly. I recommend that you best get a qualified person to do the ends of the pipes over. it must have a huge leak and should be easly detectied with soap water. ... Air Conditioners

I would like the instruction manual to understand how to use the evaporative, Cool Breeze CO Series air conditioning system in my new house!


HelloWhat is the Brand Name and Model Number of your AC? Without these detail, how anyone can post a solution to your problem. Provide me these details please. ... Air Conditioners

My outside air conditioning unit keeps starting for a few seconds, then stops, then starts again and then turns on. The house is cool but it keeps doing this all of the time.


Constant starting is going to run up your electric bill a lot. Have the unit checked out by a professional repairman. It could be as simple as a weak relay, or your outside coils could need cleaning. Definately check the inside coils, there are coil ... Air Conditioners

Which picture do I need to cool the house with a fujitsu ducted air conditioning. The picture of the sun ( for summer.) or picture of the snow, to make cooler?


The one that looks like a snow flake. ... Fujitsu 24C1 Air Conditioner

New heating and air condition unit installed but not cooling properly, some parts of the house are are cooler than others. What may be the problem?


Even cooling of the various rooms is the resposibility of the ductwork. Each duct has to be the right size for the room it is serving. There is usually some adjustability in the delivery grilles. Partially close the grille in the coldest rooms. T ... Amana Air Conditioners

I have a Payne air conditioning unit and I noticed today that the fan was not running and it was not cooling my house. I manually turned the fan and it kicked on but the compressor just clicks and does not cut on. I was trying to find out where the condenser reset button was but can not find it. Please help quickly got kids and its very hot!!


Are you sure there is a condenser reset button?If there is,the condenser is on the opposite end of the tubing where the compressor and evaporator are.You may have to remove a panel but if there is a reset,it may be right on the condenser itself.Knowi ... Air Conditioners

Air conditioning unit not cooling


The problem sounds like a defective capacitor its located on the condensing unit outside, also a contactor that is used can be defective also. ... Carrier 38CKC036 Air Conditioner

Plentiun air conditioning coils are icing up after running in cooling mode. is there a timer relay circuit in the air conditioning unit that turns the cooling pump on and off to keep the moisture on the coils from turning to solid ice and stoping air flow?


Ice forming can be the results of dirty filter, dirty coil, low refrigerant charge. ... Carrier 38CKC036 Air Conditioner

We are selling our house and have been leaving the air conditioner on for the last several days at 70. It has been keeping the house cool for visitors when we are at work. Yesterday I came home from work and the house was warm. I checked the air conditioner and it felt like it was blowing just air. Checked it throughout the night and still blowing just air, not cold anymore. I am thinking it ran out of coolant. I am not an expert or know anything about air conditioners. If you could give me your


It can be many things like a loose connection. It can be low of refrigerant or it can be the condenser fan has stopped working. Considering you are selling the house just call a qualified HVAC repairman and have it repaired. ... Air Conditioners

AC Out. Two year old house. Goodman A/C, two units one for upstairs. Cleaned coils of both outside unit, replaced filters, re-set breakers. Upstairs is cooling. Downstairs unit is running outside, not circulating air inside (inside temp 87). Vents inside are cool to touch, no air. Outside unit fan is pulling, but air exhaust is cool. Compressor ? Should air be circulating even if compressor not functioning. Is there anything in attic exchange that would affect downstairs circulation. Thanks.


Assuming that the 2 systems are isolated, that there isn't any cross over between the systems...It is normal for an air conditioner system, from window unit to central, to be able to circulate the air, even if not cooling. This is known ... Air Conditioners

Air conditioner runs for a few hours and it works - it cools the house. Then it stops cooling - the fan still runs but it doesn't blow out cool air any more. It seems like it's overheating or something. It will blow out cool air if it has not been turned on in a while but once it's on too long it stops. I was told it could be the fan motor and the a/c guy changed the fan motor today but that didn't fix the problem. Now he says it might be the compressor or that I need a new system. I'm jus


The things I would check:\015\012Is the system properly charged with freon? Sytem may be overcharged.\015\012Is the compressor out on internal overload at the point of failure? If the overload isnt tripped and the compressor is having tro ... Air Conditioners

My mother in law has a Ruud 10 Seer air conditioner. She's had it since 1998. The air conditioner runs fine but it will only cool the house now during early morning and evening hours. It no longer cools the house during the hot part of the day. Her power bill more than doubled this past month which is when the problem started. We changed the filter but that did not solve the problem. What else could it be?


I would shut off power to condensor and wash all the fins out as good as you can. I prefer to do this from the inside of the unit but that will require some disassembly so you can wash them from the outside if you want. If you have acess to the a-coi ... Ruud Matching Split Air Conditioner