Control suplimental system with carrier infinty system

\015 I am installing suplimental baseboard heat in one room of a home that has an Infinity t-stat and Carrier furnace. I would like to know if there is a way to connect to the Carrier sustem. Thank you.\015

Answers :

Not really unless it is 24v control on the new stuff. However it is you can use the voltage from white (or W) at the tstat. You will be using the power supply of the carrier furnace. install a 3 amp fuse. and be prepare to replace the fuse in furnace while testing . The most you can get on those transformers is about 10 mpers @ 24v.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Control suplimental system with carrier infinty system


Not really unless it is 24v control on the new stuff. However it is you can use the voltage from white (or W) at the tstat. You will be using the power supply of the carrier furnace. install a 3 amp fuse. and be prepare to replace the fuse in furnace ... Air Conditioners

I have a carrier A/C system controlled by a carrier TSTATCCBAC01-B non-programmable thermostat with 4 wires connected as follow: white-W, green-G, red-R and blue-Y which I want to replace with a Honeywell T8601D programmable thermostat that has the following terminals available; C, OT,OT,R,B,W,Y,O, and G. My problem is that when I connect the wires on the Honeywell to the same terminals as they were on the carrier the system seems to work but only the fan turns on while the commpressor stays off


... Air Conditioners

We had a carrier infinity system put in place 2 years ago. A week a go we had a system failure and notification on our screen for system malfunction. It turns out that the damper control module failed because of moisture under our crawl space. I then went under our crawl space to find that our unit is sweating like crazy and their is moisutre dripping in large amounts off all of the duct work. I was really sick to my stomach. Our insulation is falling off because it has become so wet. It r


... Carrier Air Conditioners

My 53QNL009/012 CARRIER SPLIT SYSTEM, comes on everytime i plug it in, the remote control works but isn't able to turn the unit off. A soon as the power is appplied to the unit I hear 3 beeps and the system starts. It was last turned on and off yesterday but the remote. When my wife returned home this afternoon the unit was running and she was unable to turn it off. The same remote works fine on the same (but larger) unit out in the family room? Thanks Ian


... Carrier Air Conditioners

I have Carrier mod#24ANA760A300 Infinity system. 1.5yrs old. Compressor nor fan outside will start. The controller on unit flashes an error for low pressure switch open (error #32). Gas pressure is normal! My technician says that he will have to order a new compressor because of some checks he has done. What I need to know will the controller show low gas pressure if the unit has never started even though the low pressure switch is closed as it should be with proper levels (checked the switch an


No unless there is a loose connection of the wires or terminals between switch and controller ... Air Conditioners

I have Carrier Comfort Zone 2 on a York system. Everything has worked fine. After recent lightning strike, the controller is not responding correctly. It flashes E1 alternating with the current temp. No matter what the programming, it seems to start cooling when the house gets to 84-85 degrees inside and then stays on continually until it hits the programmed 76-77. How do I test to see if zone panel or thermostats need replacing?


This <a\012rel='nofollow' href="www.curthel.com">carrier</a>\012\012 has everything to quickly and safely deliver\012your <a rel='nofollow' href="www.curthel.com">car</a>. ... Carrier Air Conditioners

I have a Carrier Infinity Control System in the new house we just moved in. The Schedule button is inactive (does not seem to work) and I cannot setup a weekly schedule. Is there any setting that actives the Schedule button or is the thermostat defective?


... Carrier TSTATHCP Programmable Thermostat Air Conditioner

I have a Carrier Infinity System that has the "auto" setting which is where I usually keep it in the spring time to go back and fourth as needed for proper temp control in the house. About once a year, I get a "Sens Error" because the A/C tries to cool when it is below 60 outside. Is there a simple way to bypass or turn off this function, or do I need to call my dealer, and waste a $75 service call to get this taken care of?


There should be a setting on the control panel labeled as cooling lockout with a default setting of "none"you can switch this to a lower temperature and that should fix the problem by not providing any A/C once the temperature gets below ... Air Conditioners

Can Carrier split system 38G250H be converted to be controlled from a room thermostat rather than the return air thermistor. I have a very high ceiling ,2m above the indoor unit,and the stratification is a problem. I have already the ''Butcher'' ceiling fan installed and it is still cold at the floor level, and 27deg.C at the unit level.(2.4 m)


Yes it can be done as long as the thermostat has the capability of acting as a on-off switch.It could be bimetallic type which till today are the best way of tep control since the inherent qualities of the bimetallic strip is that any temp change co ... Air Conditioners

I own a White-Rodgers manual thermostat...Type 1F56N-444 (horizontal version). I own a 1-Heat 1-Cool single stage Carrier Electric Heat HVAC system. Pls answer two questions regarding the thermostat: 1) What is the function of the "Longer Cycles" dial located in the center of the main temperature slide control used to set the temperature. You will see it located behind the 'outer thermometer' cover. The settings/numbers on the circular dial range from ".15 to 1.2". 2) Can I use these settin


No that is an heat anticipator setting that should be set to the same amperage as the gas valve o your furnace.....do not adjust unless you can tell this or you coulld ruin the thermostat... ... Air Conditioners

Carrier 18000btu split system, internal red light flashing at 1 second intervals, no response from remote control, have replaced internal sensor but still not responding


... Air Conditioners

I have the carrier infiniti system. When my thermostat reaches the set temperature it doesn't always shut off. I shut off the main control to let it reset. It works for a while and then it starts


Carrier Infinity system is a variable speed unit that will just slow down as it approaches set point. Unless it overshoots the set temperature (you have it set on 72 and the temperature keeps rising above 72) this just sounds like normal operation. ... Air Conditioners

Operating instructions i have a 30 year old house with a carrier 4 hp ducted air cond system. is there any operating instructions i can download? on the controls it has EM/HT switch ? is that for a/c or heating? regards, ken


The em switch is back up heat ... Air Conditioners

A/C need hlep with a carrier model # 40aq030-300bb. just bought a house with this unit inside but outside different unit, think its a Goodman. When turned to heat everything ok, but when turned to cool it still puts out heat. Think reversing valve is bad or switch controlling it may be bad. Not to familiar with the system and wiring diagram is gone. Somebody made a mess of the wires anyway, need some help if you have any. Thanx and... GOD Bless


Orange or O terminal on Tstat energizes valve in colling cycle. Go to outside unit jumper red to orange and see if Reversing valve energizes. If it does . Problem inside possible Tstat. You shoulf here the valve click. Have someone inside switch fro ... Air Conditioners

Carrier Low pressure lockout - 4 hours Code 83 The system is less than 1 half years old. Will it start cooling again after four hours? Infinity control shows Fan - On, A/C - off


If the low pressure sensor trips, the least likely problem is a bad sensor, more than likely, you have a leak in the system, this will require leak location, repair and recharged.\015\012Also posible, a dirty air filter, plugged indoor coil, ca ... Air Conditioners

Does anyone have the service manual specific to my model 38brc036 that would explane what 6 flashes on the condenser control panel status light means. I very helpful gentleman provided a pdf for a Carrier but it was for R-22 system, rather than my Puron. The code listing in the unit does not reference 6 flashes.


Ok, sorry for delay but I fit this in around my regular job.....here is the manual for the 38TDB. 6 flashes is still compressor fault related. ... Carrier 38BRC036 Air Conditioner

Carrier Infinity control went completely blank. Noticed it earlier. No matter what I push there is nothing there. Have tried manual with no luck. Any ideas how to reactivate the system? Had no noticeable problems before this. Just went blank.


Circuit breaker tripped control fuse in furnace blown cause would be short circuit. lastly bad control ... Air Conditioners

Carrier infinity system, sensor error


... Carrier Air Conditioners

Carrier Air Conditioner Infinity System - Air Handler Sweating & Duct Work Condensation


If its an infinity. check and make sure you have a proper charge and no air infiltration from attic. also check blower speed on your humidity control in the controller set up ... Air Conditioners

Carrier Infiniti system, system maufunction on primary display


Call a Carrier service comapny and have them investigate further, when system malfunction comes up on the user interface usually there is a substantial problem.\015\012\015\012Either that or the User Interface has gone bad and needs to be ... Carrier Air Conditioners

The fan on my Carrier cental air system is on, and I can't


... Carrier BCA101R Air Conditioner

The fan on my Carrier cental air system is on, and I can't


The fearute that is running your fan so often is designed to provide even, consistent temperatures throughout your home as opposed to hot spots and cold spots. Some customers find this feature to be an annoyance or a waste of electricity. IF you wo ... Air Conditioners

I have a remote comfort control with 3308448.004 relay board. Press Heat button to turn unit on and it does NOT turn on. Have 115VAC to the relay board and have 12VDC to remote control reciever. Sounds like the remote control reciever is bad?? Can I switch my system to the "wired" control system without changing the relay board? I assume it is possible that the relay board is also bad. Is this a common fault with these units?


... Dometic Rooftop RV Air Conditioner

Novice here and changing a thermostat. Have a Carrier FA4ANF048 system. Changing from an old circular thermostat to a Honeywell RTH7500. First, is this a heat pump system? Wiring is attached differently if it is and (we're renting) not sure if this Carrier system is a heat pump system. Most web material makes me think it is.


Return t-stat for another with o/b terminals ... Air Conditioners

Carrier Infinity Control Programming Issue


Open the flap, and press and hold the advanced button for 10 sec. you will be in the Installer setup screen. scroll down to the setup subfolder and select thermostat and it will be in there. ... Carrier Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || www.ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.0531 seconds