Ruud 12 seer heat pump not heating

\015 Inside house fan runs constantly, but the outside unit fan won't kick on unless you go and hit the reset button\015

Answers :

It sounds like the unit is tripping off from high pressure. Check you filter and indoor coil. You may have low air flow inside that is causing the refrigerant pressure to be to high.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

RUUD 13 SEER HEAT PUMP MALFUNCTION 2009 MODEL


Unsure how long ago you purchased this unit, I can only respond to what I have read. I, as a homeowner, would not PAY a contractor until such contractor has properly INSTALLED and successfully TEST-OPERATED said unit/system in ALL MODES to the comp ... Air Conditioners

New Ruud 16 seer central air and heat pump - very noisy


A few things to check\015\0121) Is the unit mounted on metal brackets attatched to\015\012the house, is so I would probably put rubber pads\015\012between the unit and the brackets to absorb the\015\012vibration.\015\012 ... Ruud Matching Split Air Conditioner

RUUD 14 seer heat pump makes loud squeeking noise after cycling.


Your problem is the TXV. I just had person with the same problem. Replace TXV no problem Rusty ... Ruud UAMB Air Conditioner

2 month long issue...RUUD Achiever 1.5 Ton 10 Seer Heat Pump


Rather than have him replace the control board first, ask him to remove all the freon and weigh it. He then can reuse the Freon that came out of your system put back in at the exact charge that the rating plate calls for. He will add a bit more to co ... Ruud Matching Split Air Conditioner

Ruud 5-ton 10 SEER heat pump compressor turns off after 20 minut


You may have cottonwood on your compressor. Before you spend any money, do two things. Rinse off your compressor to clear any cottonwood, and check your filters, they may need to be replaced. Hope that helps! ... Air Conditioners

Hello all I am about at my wits end....We had a 2 ton 14 seer Ruud heat pump installed at the end of last year. The biggest problem I am having is in heat mode when it goes into defrost it makes a loud almost helicoper sound for about 20-60 seconds, wakes you up that's for sure. When I have had the company that installed it come out I can never get it to do it for them and I even tried recording it. We have had a multitude of problems I believe mostly stemming from the company that installed it.


It is most likely due to a scroll compressor. these are very noisy and hard to get used to. if it does not have a compressor jacket it would be worth installing. a hvac company would have to get it for you and it put it on. labor should be minimal si ... Air Conditioners

Ruud 12 seer heat pump not heating


It sounds like the unit is tripping off from high pressure. Check you filter and indoor coil. You may have low air flow inside that is causing the refrigerant pressure to be to high. ... Ruud Central System Air Conditioner

New 14 seer split ruud heat pump makes very loud knocking noise


Well you may want to have a tech come out and check the freon level, but mostly when going into defrost, some units make alot of noise, the freon is reversed in the unit by way of the reversing valve, it makes a whooshing sound like freo ... Ruud UAMB Air Conditioner

Ruud Achiever 10 SEER heat pump: no cooling. Fan wasn't turning; cleaned humming noise contacts and tapped on relay. Fan turned again, but no AC. CatchAll C-083-S filter looks old; can it be rep


Try changing contacter and capacitors. the c-083-s drier can be replaced if you pump system down. kind of expensive. ... Ruud Matching Split Air Conditioner

A/c on 3 ton 13 seer ruud heat pump not cooling


You have condenser issue. check at outside unit for 240 volts to contactor and 24 volts to contactor coil. ... Ruud 3 Ton Split System Heat Pump

High pressure cut out control module is locking out the restart of condensor, if you hit reset button, condensor will start up, changed air filter.system is a ruud 12 seer heat pump with scroll inside


You need to pull the condenser shroud and hose down the outside unit really, really well and I can't stress that enough. The pressure switch helps protect the outdoor unit. There are only two things that will cause this to trip.....dir ... Ruud Central System Air Conditioner

I have a Ruud Model RQNA-B 13 Seer heat pump and it has shut down during this cold snap. It does this everytime it turns extremely cold and in the summer when it is extremely hot. Help, the service men can't get out due to the weather. It acts as though it is froze up?


If the outdoor unit is not operating and the electric heat is working, more than likely the outdoor thermostat is keeping the unit off.\015\012\015\012This is an adjustable setting, doing it at the outdoor\015\012unit. Typically the ... Air Conditioners

After replacing my Run and Start capacitors at the advise of this website, the problem continues. The compressor chatters loudly, then the fan comes on and the chatter stops. The unit is a RUUD Heat Pump 12 SEER about 6-8 years old. I have two the same age no problems on the other unit.


If I were there I would do a pressure check on the system.Then a locked rotor amp draw on the compressor.Then a amp draw on the fan motor.I would compare these figures to the specs on the service plate and look for a variance. ... Ruud Handle Air Conditioner

What is the seer rating and HSPF for a ruud heat pump model upmc030JAZ?


... Air Conditioners

I have a ruud rcha 36a2g heat pump from 2004. What is the seer rating and tonnage of it? Also inscribed uhbc-17jo6nfh


Hi,\015\012The unit is a 3 ton or around 36,000 BTU\015\012It also is around a 10 SEER could be a abit more depending on the maych up of the coil and airhandler or furnace combination...\015\012\015\012Heatman101 ... Ruud Matching Split Air Conditioner

Ruud heat pump question


Does the air handler take a minute or two to start, this would be normal so that it doesn't blow cool air into the house before the unit is warmed up. If not could be the fan relay is weak and needs replacing. As far as the outside unit it sounds lik ... Ruud Air Conditioners

Am having a Tappan Split system heat pump installed. Proposal was for a 14 SEER system including a FTBD042K heat pump and a BCS2M48C variable speed air handler. However Actual equipment installed is FT4BD-042K and B5BM-X49K-C. The Yellow Energyguide shows SEER 13.0 & HSPF 8.0 Am I getting ripped off, with an installation of a cheaper less effecient system?????


I dont think so that variable speed air handler is a nightmare when(not if) that motor goes bad its 700.00 to 900.00 the regular 3 speed one your getting 125.00 and it will last 10 to 15 years ....... if you realy want fun install a 17 seer system ... Air Conditioners

Ruud Achiever Heat Pump - Air Handler Thumps before Starting


... Air Conditioners

Heat pump goes str8 to heating strips compressor does not run in heat mode pump was manufactured in 03 installed in 07 and has sat dormant till now could it be wired wrong it is a ruud split unit with digital non-programable 2-stage heat and cool t-stat


I think that you have the right idea. The wiring is probably wrong. If you can trace the low voltage wires to the air handler. make sure that the Y1 wire on the t-stat is going to Y1 on the hair handler and then to the condenser. The Y2 wire should b ... Air Conditioners

Aux heat always comes on in heating (Ruud heat pump)


What type of system is it, if it's it Rheem the o/b needs to be set for B, if not check the freon charge, or thermostat, there will be a point where the aux. heat comes on when you turn it up, poss. only 4 degrees, is it a mercury stat or digital ? ... Ruud UAMB Air Conditioner

Ruud Heat Pump blows room temp on Heat and AC setting


A "Heat-Pump" is also known as a reverse cycle air conditioner, this means on heat the outdoor unit acts like the indoor section and vice versa. So in all probability you need to have it leak checked and recharged. ... Ruud UBHC Air Conditioner

I have a new 13 seer rheem 4 ton heat pump system the heat pump won't turn on in heat or in other words it is only working in cooling mode I wired it according to the schematic


On a heat pump the difference from heat to cool is the reversing valve.\015\012In cooling or heating the Y1 terminal will always be energized, this is the contactor.\015\012Depending on brand the reversing valve will either be energized i ... Air Conditioners

How maney btus is a ruud heat pump model upka-025


... Ruud Matching Split Air Conditioner

Problems with a new Ruud heat pump "wiring"


Hello and welcome to FixYa!,It sounds to me like there may be a fault with the Furnace or that the Furnace is not compatible with the Heat Pump.It may also be a faulty Heat Pump.Hope This Helps, --P3NGYJ03 ... Ruud UBHC Air Conditioner

I have a ruud heat pump that tries to run aux heat


Hi, This sounds like it is cold enough, the ambient temperature outdoors and is bringing on the aux heat to help even at 1 degree. Nothing to be concerned about the energy you may use will be next to nothing.In the program of the stat as ... Ruud UBHC Air Conditioner