Daikin split cycle air conditioner FTXD50J heaps of water coming out of interior unit 1. Do I have to unblock drain hole on the interior unit or the external unit. Also dont have any compressed air 2. Also very whistley almost drowns out the TV can I lubricate the bearings? If so what do I lubricate it with and how do I get to them. 3. roller fan on inside unit is all gunked up almost solid with dust Can this be taken out and cleaned some how or how do I get it back to a new condition? many than


Answers :

You will need to find where the unit is clogged and try and run something up through to snake it out. In regards to the whistling noise, this is usually caused when there is debris that has collected and the air is trying to be sucked through a previously open area. You may just need to do some general maintenance on the unit. The motors are sealed so there isn't any lubrication points on the motor. Follow the instructions from your owners manual and it can be found on the Daikin website. Sometimes it takes a few minutes to find the manuals but you can usually find them. I have been on the Daikin website so I know they are there.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Daikin split cycle air conditioner FTXD50J heaps of water coming out of interior unit 1. Do I have to unblock drain hole on the interior unit or the external unit. Also dont have any compressed air 2. Also very whistley almost drowns out the TV can I lubricate the bearings? If so what do I lubricate it with and how do I get to them. 3. roller fan on inside unit is all gunked up almost solid with dust Can this be taken out and cleaned some how or how do I get it back to a new condition? many than


You will need to find where the unit is clogged and try and run something up through to snake it out. In regards to the whistling noise, this is usually caused when there is debris that has collected and the air is trying to be sucked through a prev ... Air Conditioners

I have a central air conditioning unit in the apartment where I live. It is a split unit - somewhere outside is my outdoor unit (and everybody elses too). Anyway I seem to get way too much humidity in my apartment. The air conditioner I suspect is 15 or 20 years old or more. The label on the indoor part is almost unreadable. Carrier is the maker. The model might be 40AC02450052. There are also other numbers 40AC901190 ? or 40709010 ? Can anyone identify what I have? I would like to know how old


The humidity problem is from the condesation drain. It is more than likely to be clogged up keeping water in the condensation pan causing the humidity problem. This can be cured by a wet vac put onto the outside drain for the inside condensation pa ... Carrier 38CKC030 Air Conditioner

I have a shenbao mennelium aircon its gets cool after i turn the unit on but after 10-15 min it stops blowing cold air i have to shut the unit off and then back on to get cold air and also the compressor fan makes noises but still spins it sounds like it need greese


Check the fan,to make sure it is really turning fast on the high mode with ac on,not just fan.It sounds like the fan is slowing down,and not cooling the condenser,therefore cause the head pressure to rise,and producing warm air.The fan motor would ha ... Air Conditioners

I have a Goodman A/C unit, Inside unit P/N A42-15, my problem is inside blower won't turn on when in A/C outside unit turns on and the copper pipe going to inside unit gets cold, but no blower to circulate air, can some times get blower tot turn on by reseting inside units circuit breakers, also heater works fine.


What about the blower time delay relay: http://americanhvacparts.com/Merchant2/merchant.mvc?Screen ... Air Conditioners

I have a Goodman air and heating unit model#gsc130601bc and the problem is the unit comes on but the fan does not, also the unit gets hot and no cool air is coming out of vents in the house. What can I do to fix it?


... Air Conditioners

Noise I just bought the 8000 and 10000 BTU Frigidaire air conditioners just before my move and have found that they are very noisy (especially the 8000 BTU unit). The sound of the air flow is very noisy and the 8000 BTU unit also seems be have a slight irritating whining noise. I was thinking about taking out the three screws I saw on the side of the unit in hopes of getting the front off and attaching some cloth or something inside to make it quieter. Since I have now moved into New York City a


Adding cloth or any other sound absorbing material will not work. There is not enough room to add anything appreciable in the fan area. ... Frigidaire FAC107P1A Wall/Window Air Conditioner

My air conditioning unit stop working (outside unit). When I turn the unit I notice a buzzz sound comming from the unit. I have pressed the reset button on the unit to see it that would help but nothing happend. I check to see if there was electricity with a voltemeter and the unit is getting current all the way to the capacitor. I turned the power off to the unit to check if the capacitor had a charge and it did. What other things should I be checking? Also, the fand do not turn on! model numbe


Hi, what is happening is, you have power to the outdoor unit. I am glad you have a volt meter. This system is a split unit,condenser outside and indoor unit. This is what you need to check, and what the buzzing is, and why the fan and compressor will ... Ruud UAMB Air Conditioner

E9 Showing on split unit display also blowing hot air not getting cold also unit outside is still running.


It is coz of Refrigerant leakge. ... Mitsubishi Air Conditioners

My central air conditioner is making a whistling noise in the inside unit when the compressor is running. It's not the blower because the noise stops after the outdoor unit shuts off. It's also not blowing any cold air and the piping is not getting cold. What could be the possible cause?


Hello,\012\012If there is no cooling (meaning no cold pipes and not blowing cold air) then check the outdoor A/C for any visible/obvious issues; breakers not tripped, no debris blocking the outside unit from passing air through it, etc. If all ... Air Conditioners

We own this air conditioner and it is one year old. It is working find, however, when running in the air conditioning mode it omits a musty oder. Where I am allergic to mold , I am concerned especially since I keep getting a headache and stuffiness when it's running. We have run it for hours in the fan mode in the hope to alleviate any moisture in the unit, but the smell is still there. The unit also has a charcoal filter, but I don't know where I can buy them. Any suggestions you can prov


The problem is common. It is not a mold spore situation, rather it is a moisture laden problem of parts and dust that create an oder when allowed to warm and stay moist. A spray bottle with 1/2 clorine bleach and 1/2 water sprayed onto the inner com ... Amcor AF9000E Portable Air Conditioner

No cooling I received a call from my tenant that they have no ac. When i get my inspection of the unit to find an extremely durty air filter, which i replaced. Also i cleaned the a coil which was also full with dust. So i figured the time it took me to to do all that cleaning that the unit had time to reset it self. Long story short i still have no cooling at all still. through the first sequence of operation every thing seems ok . dtill no cooling


"You forgot the "first rule , check to see if everythings is working! If the filter was dirty , then you skipped the second line of defense to prevent dust from going into the vents is the squirrell cage blades. Air flows thru the filter first,,,2ond ... Goodman CKL36AR36 Air Conditioner

Is their an interior pan inside the coil??? If the drain is not clogged, the air is working great. I was told the interior pan is just tipped. Now I am told their could be a crack in another interior pan inside the coil. Come on!!! I think they just can't get the pan level. What do you think??? Of course they want to sell me a brand new unit!!!!


With out inspecting the pan its hard to say. But a secondary drain pan can be placed under the unit or the primary can be replaced. Just ask for the original part once it is replaced. ... Air Conditioners

I have a ten year old carrier heat pump unit. I recently replaced the indoor tstat. the outside contact and the transformer. Had a tech put freon in the unit also. I have to problems one is the airflow is minimal coming out of the vents it has new air filter and I cleaned the inside and outside unit coils. And the second problem is the ac with not get cold.


Two things are the most likely culprit. First check ytour inside coil with the unit running for 10 minutes or more and see if the coil is sweating there should be water running off of it. Also after one hour is there ice forming on it. These problems ... Air Conditioners

Unit runs but will not cool. Fanruns fine but when turn dial to cool the compressor kicks in for about a second or two the kicks out. Fan works on cool but it will not produce cool air at any temp setting. I have cleaned filter and removed cometic facing and vacuumed the coil face. It was pretty dirty but after all that still would not cool, Unit is installed in a RV and power is provided from house. Gen4erator is also available for power. Unit is difficult to remove from RV and space to get at


You may need to install a hardstart kit if you can get to the compressor.\012go to your nearest appliance parts store to get the part and the instructions are usually on it. If not ask the parts man.\012\012If this was helpful pleas ... Air Conditioners

My Friedrich Quiet Master window Air conditioner blows cold air for a couple minutes then switches to warm air, almost like it switches to fan mode. We also are getting water blowing in. We cleaned it, this helped a little. Could our cooling problem be with the thermostat?


Air conditioner may be too small for the room.If the air conditioner is put in too large of a room the air compressor will freeze. If you take off the filter you will see ice inside. The best thing to do is let the AC thaw out unplugged and put ... Air Conditioners

I own an armstrong air unit after about 30 minutes the unit seems to get hot and the fan quits the compressor is still running I changed the motor on the fan and it still does the same thing I have also changed the braker and put in new wiring from the disconnect box to the unit. Please Help, Thanks Jimmy Watson


Chech the fans rotation , the fan is suppose to blow air out the top, also if you changed the fan out ,check for the blade on right, its suppose to scoop the air from the inside and blows it out the top,, also replace the capicator...sounds to me lik ... Air Conditioners

I have a wall mounted Midea MSV1i-12HRDN1 Air Conditioner in my apartment unit. I keep getting a P5 Error Code. I would like to know what P5 is? I would also like to know how can it be fixed? Presentl


... Air Conditioners

On our last rv trip we kept getting alot of condensation build up on the inside ceiling grill air intake/output cover to the Dometic roof mount a/c. Also, on the last couple days we had to turn the temp. setting up to 85 to get the unit to cut off.


If you were camping at our resort, you got all that condensation because the humidity was near 100%.\015\012\015\012Your unit is operating just fine. ... Dometic Rooftop RV Air Conditioner

I have a maytag nmpeb08f2a portable ac, just started it up for the season. cleaned the filters and coils by wiping down . I also emptied bottom resevior. Im not getting cold air when on cool setting, tried lowering temp all the way. when i turn it on it will be cold for a short time, doesnt fell cold like befor, the temp will go down maybe 1 degree then, no more cool air. can i add refrigerant to this unit?


Frank, refrigerant is what it needs, but it should be done by a pro. Unless you have experience with this sort of thing, it's not a DIY project, ... Maytag Portable Air Conditioner M6P09S2A

We are unable to get pc-2h2 reverse cycle ac to heat. Unit is set on heat at 30 degrees but also displays A/C. Cold air from unit.


... Hitachi Air Conditioners

I'm getting condensation leakage from the vents in the roof. This is on a ducted system, and it's leaking from the two vents closest to the main blower unit up in the ceiling. It's very high humidity here lately, and the leak usually starts around mid afternoon. Up in the ceiling you can see the drops of condensation forming on the under side of the main blower unit, and also all along the large insulated air ducts. I've got the thermostat set to 24deg, it's usually 30 - 34 deg outside. When I


Two things may need to be done here, one is to insulate the vents in the high humidity/temperature area to isolate them from these high conditions. The second would to install a drain pan under the system to catch any condensation and drain it away. ... Air Conditioners

Hi. Just bought a new in box "LP" LWHD 1200R window air conditioner. When I went to turn it on, I got an awful loud fluttering noise coming from the front of the unit. NOT the "slinger fan" which is located in the back. The compressor is working because it will blow cold air, but the noise sounds almost like something is in there rubbing or something. Can anyone please help. It's getting warm up here! Thank you ................ Eric


Hello Eric,\015\012\015\012Let me see if this will be of any help take the front cover off and check to see if any packing material has fallen down in the air baffle. this will be towards the top of the unit on the inside. Also check to m ... LG Air Conditioners

Water dripping (almost running) out of the left corner of air handling unit. Help???


You're correct in checking the drain pipe, because it's become blocked. The only trouble is, you're trying to clear the wrong end. The condensate water is spilling out of the air handler because that's where the pipe has a clog. \015\012\015\012The ... Ruud UAKA030 Air Conditioner

Where can I find a wiring digram for the transformer it has 4 wires going into it on the hot side then to comming out on the 24 volt side.I took the old one out to replace it and cannot seam to get the wires hooked back the way they were.The unit works by pushing on the points but not from the thermostatIt is also brand new model no is PCK036-1 we only use the air side not the heat.


It sounds as if you have a multi-tap transformer. That is, the primay voltage can be 120, 208/240, 480. Most all transformers have their legends printed righ on them. Usually the 4 wires are a common and the other wires to the incoming voltage by i ... Air Conditioners

I have a heat pump system with gas as auxillary heat. What outside temperature should I switch my thermostat to "Emerg Heat" to run only gas? I also have a dial that appears to be some sort of temperature control on the lines that run outside the house to the compressor unit (currently set at approx 32). Is this for defrost control or does it tell the heat pump to shut down when the outside air gets below where this dial is set and then use only gas heat?


The dial thing you are talking about is a low ambient control that will not let the heat pump run below the set temperature should be set between 32 and 40 degrees farenheit. The heat pump is not effiecent below 32 degrees as I would reccomend only r ... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific
all rights reserved to the respective owners || www.ad-trader.net || Terms of Use || Contact || Privacy Policy
Load time: 0.2088 seconds