Heating element came on in low cool high cool then off position

\015 Zonelite 2100 the heating element is on and the only way to turn it off is to unplug the unit. what parts need to be replaced. thanks john\015

Answers :

Either you have a thermostat (if the elements run directly off of it, or if it pulls in a relay it could still be the fault.
To see whats controlling the element(s) trace the 2 wires that\015\012power it. 1 will go to the power - line with a lot of other wires. The\015\012other one will go to the thermostat or the relay/contactor that turns it on and off.
A thermostat will have a "bulb" a small tube attached and going into the air stream of the air coming to the unit.
If it has a relay to turn on the elements check the relay points and the coil power at the relay with temp set at lowest (coldest temp). If you have power to the relay and on to the elements and the room is warm, the thermostat is out. Pull a wire off the thermostat and it should stop the element(s). This removes power to the relay or contactor coil. (contactor is just a heavy relay). The element should be off. If it is still on some relays / contactors have an open face and you might be able to see the contacts and they are welded shut or the spring has been dislodged. Remove power to machine and with a small pick or screwdriver separate the points (if it has this relay/contactor).
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
Thermostat wired direct to element
L1 Thermostat Element L2
________/._________/\\/\\/\\_________


OR
Thermostat wired to Contactor coil with a relay points:
L1 or L2 is also feeding the relay on 1 side
L1 Relay points Element L2
Contact points
\015\012________/._________/\\/\\/\\________________
+
+ < L1 jumper
+
L1 Thermostat Contactor coil L2
\015\012________/._________/\\/\\/\\_______________

Your thermostat control is bad. It is an electronic control.
\015\012The fan comes on through a different circuit when heat is sensed. That is why the fan cycles no matter what you select. Because the right hand switch is defective.
\015\012There are 2 switches on the face of your controls.
\015\012Heat---Fan-- and Cool.
\015\012The other is for temperature.
\015\012Replace the right hand switch and thermistor.(all one part)

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Heating element came on in low cool high cool then off position


Either you have a thermostat (if the elements run directly off of it, or if it pulls in a relay it could still be the fault. To see whats controlling the element(s) trace the 2 wires that\015\012power it. 1 will go to the power - line with a lo ... GE Zoneline AZ38H12DAD Split System Air Conditioner

This is a heating and cooling through the wall heat pump. It works normally when heating is selected - the heat pump runs and both speeds of the fan blow warm air. But nothing runs when cooling is selected. In other words the unit works normally when "High Heat" or "Low Heat" is selected but nothing runs when "High Cool", "Low Cool" or "Fan Only" is selected. The position of the Fan Cycle Switch has no effect - behavior of the unit is the same in both positions of the Fan Cycle Switch.


You have a bad board or bad switch. I would say board. You can have service tech check this out. There is only so far you can go without knowledge of Controls ad electricity. Russ ... Air Conditioners

I am trouble shooting a Bryant Hi-bred system that uses an air cooled heat pump with high efficiency gas furnace for backup and low ambient operation. How does the system decide whether to use the air cooled heat pump or the gas fired high efficiency furnace. It appears to be outdoor air temperature related, but I can't find the setpoint for it. The main zone Bryant thermostat appears to control the system, but it doesn't always bring the backup heat if the heat pump doesn't function.


If you are using honeywell vision pro 8000 t-stat you need an outdoor sensor program on t-stat would have to look up ... Bryant Air Conditioners

We have this air conditioner in our sunroom. From the beginning, the temperature set is not maintained. When the unit is set to cool, no matter how high a temperature I select, the unit cuts on approximately every 10-15 minutes, and cools the room to about 66 degrees. When set to heat in the winter, no matter how low a temperature I select, the heat cuts on about every 10-15 minutes, and the room will heat to a much higher temperature than selected. Any idea what the problem is, and how I ca


Change thermostat. ... Amana PTH153B50AM Air Conditioner

Zoneline 2100 does not get very warm, it stays the same low warm temp in low heat or high heat and also turns on by itself after being swithched to stop position


... GE Zoneline AZ55H09D Air Conditioner

Sharp Air Conditioner AC09RLCSYS isnt cooling properly. Very moderate to low cold air from unit. At one point small bits of ice came out of indoor unit when on auto cool. Unit was switched off immediately and then turned back on after a few minutes with no additional problems, however still is not cooling properly. Unit is only eight months old. First used for cooling with no problems and great cold air, then for heating during winter. Now back to cooling and not getting the cold air like p


Unit may be freezing up if blowing ice crystals. Let thaw 24hrs try again. Make sure condensation drain line is cleaned out. ... Air Conditioners

GSH13 Goodman heat pump split system is running a long time in cooling mode and will not cool below 74 degrees. A lot of condensation generated. The low side pressures 78 to 81 and high side pressures are 180 to 200 psi. Energized and deenergized the reversing valve several times.Pumped down the sytem (pumped down well) and checked the flowrater for any type of obstruction. Have a sight glass on the system - will get clear then bubble up. System is in the second cooling season with clean air fil


Check sub cooling and super heat. the New ac units are very critical to charge. There is a charging chart on the inside of the cover to the unit outside. Check temp difference across coil. Should be 18 to 22 degress. If you have an ampmeter. Check th ... Goodman CLQ36AR49 Air Conditioner

Heat pump shut off 1 to 2 minutes, service yesterday for same problem told low on freon. Added freon, worked fine until it went thorugh first defrost, now back to same thing. Tech says compressor not getting signal from thermostat. After resetting T-stat, unit came on. Unit works on cooling and Aux heat, but no heat pump.


It is possible that you have one or a combination of a few different problems here.If your heat pump will not come on but the air handler works, the first thing you want to check is that the circuit breaker and disconnect for the heat pum ... Carrier Air Conditioners

Duo Therm Quick Cool A/C fan motor cycles from low to high


My RV ac works find when started up, blows plenty of cold air.after awhile ,it would seem to bog down, and blow very minimum cold air.the compressor will not shut down, possibly because it can't the cooling level that it was set for. model # 59136621 ... Dometic Rooftop RV Air Conditioner

2005 Dodge Ram...... A C unit is cold but the air on high is like its on low, the sound changes with each setting like it wants to blow harder but not that much comes out, it does blow a little harder on high over the lower settings but in the heat of the day it cant cool the cab.


It could be the connectors on the high pressure switch above the a/c compressor..or the A/C might need gassing...could be a fuse...wouldn`t think it is a hose ..also you could check the inlet/outlet pipes on particle filter..(p ... Air Conditioners

Indoor fan motor continue to run even if the thermostat is in auto position with the cool and heat switch in the off position. The furnance don't have a fan on and off switch in the furnance like most. The only way to turn the fan motor off is to turn off thr high power switch. I change indoor fan relay but the problem still exist.


Try this, disconnect the fanwire (green) on the furnace, if it shuts off then the hot wire from the thermostat is touching the green wire or bad thermostat. Thank-you-very-much! ... Intertherm Air Conditioners

I have an intertherm electric furnace FEH-A020, with multispeed blower installed when A/C added. My problem is blower operation. at the end of the cooling season with fan set to auto operation the fan ran continuously. Now that I've turned the unit back on for heat the blower will only function with the switch in the on position (continuous operation), in auto mode the heating elements come on with the signal from the thermostat (Honeywell CT3400), but the fan does not. I checked the fan relay p


The model of T-stat you gave comes up as a discontinued model on Honeywell's web site, but it looks to be a manual stat that type of stat would have to be wired with a summer winter switch with electric heat, allowing it to turn on the fan with a cal ... Intertherm P3RA-048K Air Conditioner

Ac problems posted by couuntrygirl on Aug 20, 2008 Report abuse The unit will not cut off when it reaches it temp. in camper. I have replaced the Thermostat, control board, and the compaster on the top. I still have the same problem. It will not cut off with the switch heat off cool you have to use the hi low switch and its all wired right. Very confusing. When you move the temp control handle on the top to a different degree it makes the fan go from high to low it will not cut off. when it reac


Sounds like the switches are in the wrong locations , rotate! Thank- you- very-much! ... Dometic Rooftop RV Air Conditioner

My ac unit doesn't blow cool air. The fan works on both high and low and heat and cool. However, the compressor doesn't come on. I can hear the relay click when I move the tstat up or down. Please help...


... Dometic 57915531 Air Conditioner

My train air unit cools at night but during the heat of the day it takes all it can do to keep the apartment around 80 degrees the maintnance man at work said the low pressure was at 80 and the high was at 350 which he said was a little high but he dont know why he did mention something about a txv some kind of valve but i really think hes lost please help


The pressures arehigh no doubt about it.\015\012\015\012help your tech out then if you think he's lost.\015\012go to the store and buy a couple of cooking thermometers.put one in the supply vents, the ones that blow.put the other on ... Air Conditioners

A/C Problems The unit will not cut off when it reaches it temp. in camper. I have replaced the Thermostat, control board, and the compaster on the top. I still have the same problem. It will not cut off with the switch heat off cool you have to use the hi low switch and its all wired right. Very confusing. When you move the temp control handle on the top to a different degree it makes the fan go from high to low it will not cut off. when it reaches like 70 and its set on 70 the fan will go from


It's not wired right! bottom line! ... Dometic Rooftop RV Air Conditioner

High cool and low cool not working


Hi,\015\012 Pls check the following....\015\0121) Fix the wire connector to Reversing vale \015\0122) Check the Capacitor if this a low capacitance or (open) not function using Multi-tester.\015\0123) Check the Selector switc ... Amana PTC093B50AJ Electric Heat Air Conditioner

I have a 8 years old window ac. It's working quite ok. I just want to know which mode is safer low cool or high cool when humidity is high but temp. is about 32-34 degree celcius. Technican advised me to run in high cool mode for some time n then switch is off, but i want long hr. running in low cool mode which is quite comfortable. Kindly advise.


Its not a mater of safety. Its only a matter of witch is best for you. If you want to maintain the temp then leave it on low temp. If you want to save money then you can switch it to power saver mode on high to bring the temp down. Hope this helps. G ... Air Conditioners

Amana heat pump was working fine. Inside blower still working, outside condenser has 230 at contacts and 24 volts at time delay. unit will run if contacts pushed in by hand. high and low pressure switches are made. not sure about time delay, defrost board or defrost relay. i can by pass all the controls and it operates in cool mode for now. what five devices is most likely to be defective?


Time delay bad Tom ... Air Conditioners

Lennox HP13-036-230-01 heat pump with CB30M-471-49 air handler and ECB29-20CB-4-P coil starts in cool mode and runs for a few minutes with colling. High pressure remains but low pressure drops. Frosting after TXV and at capillary lines. Replaced filter/dryer and TXV (with 37J6901). Specs list 56J20 as replacement? Same exact thing. Flter new. All installed 02-2009. Could it be defective new TXV or incorrect replacement.


Hi,Being that you had the same problem before I would guess that it is not the filter or TXV that is the problem...You may have another restriction in the system...Did it work in heat mode???Do you have adequate air flow??? ... Air Conditioners

I HAVE A GOODMAN PACKAGED AIR CONDITIONER M/N PCO30-1 B REV. E C/W 9.8 K.W. ELECTRIC HEATER INSTALLED IN A MOBILE HOME. WHAT WOULD YOU RECOMMEND FOR A BLOWER FAN SPEED? CURRENTLY IT IS SET ON HIGH SPEED , HEATER AMPERAGE IS CORRECT, BUT THE DELTA T IS TOO LOW. MY CONCERN IS , SLOWING THE BLOWER SPEED FOR BETTER HEATING MAY BE TOO SLOW FOR COOLING. tHANK YOU.


Hi,\012Many have sepaarate speeds for heating and cooling....check it out there should be a heat relay and a cool relay and the motor taps are hooked to each so maybe you can just do a bit of switching wires.....\012\012But, really ... Goodman Air Conditioners

We had a new Carrier Weathermaker Infinity Gas Furnace installed in our home on 9-21-99.The Carrier people said the furnace was in good condition this past October.But prior to that as of April 2010 the furnace started sending up really cool air. Was told by the Carrier serviceman that the Controlboard was running on high and low at the same time also found the Board fired.Then NO HEAT. Got a new Controlboard installed,that didn't work Still NO HEAT.Was told furnace needs a model Plug that was


... Air Conditioners

Amana PTAC ''Auto'' setting doesn't work. I turned on ''Heat'' and then ''Cool''. I can get the ''Low'' and ''High'' settings but not the ''Auto'' Please help


Sounds like ur board is gone out and needs replacing if u dont no about these units i dont advise trying to do this trust me save urself some money and headach and call a tech ... Amana PTC093B50AJ Electric Heat Air Conditioner

Carrier 58RAV095-16 will process thru the test sequence properly: inducer fan, ignitor, blower high, blower low, all ok. fuse checked good on controller board. when commanded to supply heat by the thermostat controller in the living space the unit runs with fan only, no gas, no ignition. changed thermostat controller, no joy. Comments: Jan 31, 2010 - thermocouple/ignitor is ok and positioned well. It tests ok too. I changed it last year. I am not getting gas flow so I suspect gas control va


Go to the furnace and turn off the power take the door off you must have a multimeter inhand with the cover off the furnace and access to the gas valve put yor meter leads on the wires going to the gas valve turn the power on and after the ignitor gl ... Air Conditioners

1994 corolla-I charged the air cond., and it was cooling fine. After about a mo., it was not cooling very good. I assumed it had a small leak. I put my guages on it and the low pressure was running 15 to 20. The high side was reading about 150.I put a can of stopleak and detector in it. Then I put a can of freon in it. While I was putting the freon in it the pressure started to drop on both the low side and high side. Now the low side pressure is running about 15 and the high side is running 0.W


Hi\015\012\015\012\015\012Thanks for using FixYa. This has happened because of the low side pressure on your AC pump isn't kicking on, because when the pump is off, the pressures equal out and the low side shows a high ... Air Conditioners