Having problems with your Air Conditioners ?

The main fan on indoor unit gets clogged with dirt. It is hard to access and very hard to clean. Are there any tricks? MSY-A17NA


Answers :

Off all power to the unit.Use water prferably running water through a hose with some pressure and direct it towards the whole length of the fan. Most of the water would be drained out through the internal pipe but just in case it floods prepare a pail to hold the excess water.Wash till it is clean.
Sometimes the best way is to try and vaccum off as much as you can and then blow off the rest. Unfortunatly there isn't an easier way. You try and modify something that you can attach to the vaccum that can get into tight spaces. You might try some small tubing taped onto the end of the vaccum.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

The main fan on indoor unit gets clogged with dirt. It is hard to access and very hard to clean. Are there any tricks? MSY-A17NA


Off all power to the unit.Use water prferably running water through a hose with some pressure and direct it towards the whole length of the fan. Most of the water would be drained out through the internal pipe but just in case it floods prepare a pai ... Mitsubishi MS-A09WA Split System Air Conditioner

Have several ASU9RMLQ wall mount units, where circulating fans inside units have dust build-up on blades the size of rice kernals. Very thick build-up. All filters are cleaned every 30 days. How do we clean fan blades? Do we have to disasemble each entire unit to clean fan. Appears given access is very limited through the moving louvers.


... Fujitsu Halcyon ASU9RMLQ Mini Split Wall Mounted Heat Pump Indoor Unit - 9,00

Have several ASU9RMLQ wall mount units, where circulating fans inside units have dust build-up on blades the size of rice kernals. Very thick build-up. All filters are cleaned every 30 days. How do we clean fan blades? Do we have to disasemble each entire unit to clean fan. Appears given access is very limited through the moving louvers.


... Fujitsu Halcyon ASU9RMLQ Mini Split Wall Mounted Heat Pump Indoor Unit - 9,00

I know today it was 99* but my moms a/c isn't cooling?I took the filter out and man o man the fins or coils are covered with dust?can i clean them or do i need a Pro?I'm not sure i can get my hand all the way down the vents or coils but the unit is several years old and has NEVER been cleaned!! Is there a trick to cleaning this if your not a a/c tech?How much would a service call be and does one include the cleaning of these?


Call a reputable co. get it tuned up most have maintenance programs, should be checked yearly.you will be time and money ahead the out side unit needs to be cleaned to. and what you spend on cleaning the unit you would have spent trying to cool a hou ... Ruud UBHC Air Conditioner

We need to know where the main drain is located on our unit or how to access it so it can be opened and cleaned. It stopped up and the secondary overflow line running to the outside of the eve worked loose from the unit and dumped my bedroom ceiling with water. Overflow line repaired but the MAIN drain needs to be disconnected a the unit to unstop. We are elderly, both sick, repairman overloaded and it is HOT where we live. Any assistance is appreciated. Thanks in advane for your help.


Unfortunately, if you're elderly and sick, you'll need to get the serviceman back to unclog it for you. As it will require crawling on your hands and knees, to access the main drain and then running an auger or high pressure air into the main drain l ... Air Conditioners

My MSY-A17NA UNIT will start functioning normally then after about five minutes it stops blowing air and the operation led signal starts flashing. When both the operation and indicator led's are on the unit works properly. After I shut it down and start it up again the unit works fine. How can I get it to stop shutting down every 5 minutes? I'm in Hawaii and it is Hot here! Please help.


Hi,Here is a tip about Mitsubishi Air Conditioners and how to get the manuals for all of the Mitsubishi line. The manual include both troubleshooting and installation. ... Mitsubishi Air Conditioners

How do I gain access to the fan which is located on the inside of the unit of a split aircon, the unit which resides inside the house. Need to pull this part out off the unit to clean it. Thanks


Is this a split system on your wall or a cassette(a square unit in the middle of the room) like in the picture? units on the wall are very annoying to get out and if you do you will probably brake it. best to just turn of the unit and whip and spin w ... Cfm Daikin R410a Split System Air Conditioner

I have a Mitsubishi ductless mini-split AC unit (model MSY-A17NA) and a Mitsubishi Electric remote (type KM07L 0029445). Could you please tell me what some of the mode symbols mean - in particular, the 4-sided box with the arrows, and the 6-sided symbol (snowflake?). Also, does the water drop mode mean that the unit is dehumidifying only, or is it dehumidifying AND cooling. Thanks. Tanya


Google ( mitsubishi air conditioner ) you should be able to get all the help you need .. dont forget you need your modal and serial number when you call it will give them the help they need to give you the right answers you are looking for .. once yo ... Mitsubishi Mr. Slim MXZ30TN Air Conditioner

I have an 8 year old 2 1/2 ton carrier compressor unit. I have already replaced the running coil and contactor. I now want to clean the coils and fan blades on the motor. I have never had reason to remove the top grill. I looks as though the fan motor is attached, and I don?t want to do anything stupid ?if I can help it? or damage or disconnect any of the wires. what is the proper way for me to access the inside of the unit so as to be able to spray off any debris that may be on the coils. So fa


Hey Bernie, it is possible to remove the 4 screws on the grill that the motor is mounted to (not the bolts holding the motor to the grill)and pull up and twist so its upside down and have someone else hold it as to not put to much stress on the wires ... Carrier 38CKC042 Air Conditioner

I have a GE room AC unit, model number AJCS12DCBM1 which has a clogged drain line. I understand how to clean it, but my question is, where is it? I can only access the unit in the wall from indoors.


You can gwt it from outdoor, to the back of the unit the drain line goes outside with the copper lines, just follow it out and take a wet and dry vacuum and vacuum the line and prob solve.. hope everything works out ... Air Conditioners

Cleaning The vent part of my Friedrich SS10J10A window AC unit (that is, the upper part, with the movable louvers) is crusted with mildew. I would like to take it off and clean it. I unscrewed the two screws holding the piece in place but something is holding the piece in the center. I don't want to tug too hard, lest I break the plastic. Suggestions? Thank you!


My husband figured out that the grilles themselves click out--not the whole assembly. Now he is going to have to figure out how to click it back in! ... Friedrich QuietMaster Electric SS10J10AR Air Conditioner

CPLMA10000E How does the water drain? How do you access the inside of the unit to clean.


... Amcor Air Conditioners

I have a dometic, I cleaned coils and still have problem with it frosting after running unit for an hour. It also does not blow out vents hard.


Your problem is 'very little air' across the coil and assuming you've cleaned the cooling coil - then the problem has to be with your fan motor. It must be breaking down (the motor is shorted) and running at a vastly reduced speed (which I seen them ... Air Conditioners

Mr. Slim MSY-A17NA noisy interior fan


If the inside fan got loud because it developed mold, the only cure is to keep cleaning it. ... Mitsubishi Mr. Slim MXZ30TN Air Conditioner

I have three mr slim inside units...live in a very clean place, non-smoker, no pets, brand new renovation....problem is that the fans are constantly getting dirty. less than a month ago i had all three units taken down, thoroughly cleaned, drain hoses cleaned, etc. Put them back up and now they are accumulating what appears to be an abnormal amount of gunk on the fan blades. the filters are clean, the coils are clean, and the air intakes at the top of the unit are clean as well. anyone have any


Very strange indeed! The ffault is on anyway and there is a dirt that comes on to stick to the fan. So the logic is that the fan is bringing up the dust to the fan either from the inside of the unit or from the outside. if you are spot sure that ther ... Mitsubishi Mr. Slim MXZ30TN Air Conditioner

Cs-ye12mke. Panasonic Inverter A/C system How do i access the drainage tubes behind or within the wall unit. The unit appears to be sealed with little access to the internal parts. It leaks down the wall after a short period of usage. I can access the outside unit and have tried to vacuum the drainage house from downstairs, but believe it might be plugged by the upstairs unit, or a leak in the tube itself. How is this unit mounted to the wall?


... Panasonic Air Conditioners

Carrier CNPVP6024ATA I have a 2 yr old unit and was told that the evaporator coil needs to be chemically cleaned at a cost of $292. The unit was installed in new construction, and the technician said it was very dirty with construction dust, etc. and most likely the crew was operating the unit without a filter. On the A/C unit - 24ABB360A0030010 - I was told the blower wheel needed to be dry cleaned ($140) and the secondary heat exchange needed to be cleaned ($172). My builder has said there w


... Carrier Air Conditioners

I have a frigidaire window unit. i cannot recall the exact # of the unit. but, my problem is that the unit still cools, but the smell it emits is similar to that of a wet dog. i opened the unit and cleaned the filter, i noticed there was what appeared to be a second filter, but i did not see a way to get it out. after cleaning the filter, i turned to unit on and got the same results. i think the unit # is something like FAM187STA


Hi, you cannot take out the second filter because you are not a tech in that field. Many times when a wall or window a/c unit is installed the installer\015\012levels the unit.It should actually be lower on the outside end than the\015\012wall ... Air Conditioners

Condensation water is not draining properly on Goldstar AC window unit and backing up and dripping on the wood frame and floor below the unit. Is something blocked it just started happening. I am going to clean the little pipe that water drips from outside but it involves climbing a latter. Also I am going to clean the condenser coils...is there another reason or anything else I am missing and do you clean the condenser coils with little wire brushes? It occurs after the unit has been runnin


Yes,remove the ac unit from the window,and clean it out with a water hose out side,remove all debris from inside the unit,and tilt water out of unit.Make sure there is nothing in the way of the drain,and when the unit is put back in the window,make s ... Goldstar KG6000R Window Air Conditioner

Hi. We've been running our LG BP6000ER window unit air conditioner for four seasons. We've made seasonal efforts to clean the interior with a hose, but this year we're noticing a strong mold/mildew smell eminating from the unit particularly when the compressor cycles off. Short of taking the unit to a professional to be cleaned is there anything we can do to either (1.) clean it more thoroughly-- perhaps by removing certain parts or (2.) to kill the mold with a spray of some kind. We'd b


Take it outside .get the hose .buy some coil cleaner hardware store .clean the coils good.. both of them .try to be carfull of the controls not to get them to wet ..cover them if you want ..after cleaning coils tilt unit to remove most of the water l ... LG BP6000ER Air Conditioner

We had a service technician come out and work on our a/c unit yesterday. He replaced the fan motor (only 2 years old) and insisyed that the fan blade needed cleaning. Next, he said we needed freon, but that the company policy stated that they would not add freon to a unit without first cleaning the coils ($188 for the cleaning). We have never had a technician tell us this before. Sounds like a way to make more $. Can you confirm if cleaning the outside coils is absolutely necessary before a


In short, yes, you have to have the outside coils clean before adding refrigerant so that you can correctly charge the unit. Dirty condenser coils will cause a rise in pressure inside the system because it cannot condense the refrigerant correctly. O ... Air Conditioners

Want to clean evaporator coils on Goodman A/C. It's a roof unit. the Heater, A/C evaporator and condesenor, both fans, are all in this unit. No way to get to the A/C evaporator to clean the coils. How do I clean them?


There is an access panels on some package units. If you cant find the access panel then remove the top. I use a garden house. Make sure to kill the power to the unit before servicing. ... Goodman CLQ36AR49 Air Conditioner

Kenmore 580.75151500 A/C unit smells... We've had this window unit in place for 2 years. We've cleaned the front filter and coil, but we're still getting different, peculiar smells from the A/C. Sometimes it's vingar, sometimes urine-like, sometimes moldy smelling. Is there some place else that we can clean it? I've downloaded the user manual, but it's really just a parts manual - doesn't say anything about maintenance or upkeep. Thanks


Hi!!\015\012\015\012As you know, the evaporator unit (the one that the filter covers) gets a lot of condensation which is drained thru the back (outside) of the unit. That's why the unit is installed a bit tilted to the back.\015\0 ... Kenmore Air Conditioners

Burnham Oil fired boiler-burner unit Model # RS/112. Probably over 25 years old. The unit would run for 20 sec. or so and cut off. A little smoke was coming out of the little hole. Took it apart and cleaned the flue tubes/ turbulators etc. It was pretty dirty. Some of the tubes were completely blocked w soot. Cleaned the electric eye. Put it back together and it would still shut off after 20 seconds. Took out the gun assembly and adjusted the electrodes to specs. It appeared one of the electrode


Hi,\015\012The problem is the nozzle and quite probably the air adjustment is off.\015\012To be quite honest, working on an oil burner is not a DIY project. When any changes are made the air should be readjusted using a combustion analyse ... Air Conditioners

I have a GP#120CE unit from you and the problem is that the unit is blowing out hot air and i have an error message on the screen saying enactment e3. i cleaned the filter on friday thinking that this might be the source of the problem but it was fairly clean (i wash the filter every 2 weeks,What can i do.


... Goldstar Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific