My AC unit outside will not turn on

\015 My AC will not cool. Upon inspection I noticed that the fan in the unit outside is not spinning. I have a Ruud model # UALA-036JAS. What can I do to fix it myself. I have 4 small kids and no money for this. Can someone please help.\015

Answers :

Only thing I'd add to peyton is that you should kill the power to the a/c unit b4 you open it up. You can do this either outside at your disconnect switch or inside at your electrical panel by turning off the 230 volt circuit breaker that feeds the a/c.
\015\012hope you find your issue.
\015\012Glenn
Can you hear anything at all running in outside unit? ruud units have a hi pressure switch located between the 2 tubes going to inside of unit it normally has red button but sometimes the red overing over the button comes off so just look for a piece sticking out that you can push in. \015\012
\015\012If you do hear other things running in outside unit most lkely you will  have a bad motor or motor capacitor. I would reccomend calling a service company unless you have the tools and meters to check this stuff out. If you do have the tools necessary message me back and I'll try to walk you thru troubleshooting. thanks Peyton

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Had a ac tech service central heating unit for the fall. Tech left and I left to do some errands . Now AC unit is not cooling its blowing warm air. I turned the circuit brks off and on inside and outside. I have also checked to see if unit was left on heater. thats not the problem. If I turn theAC on the fan does not turn on outside and there is no sound coming from the unit outside HELP!!! AC was working properly before this.


It may not help but it sounds like the tech took a control wire for the cooling circuit loose at the indoor air handler/furnace so that he could bring the heat on to check it, and forgot to hook it back up. That may not be the case, but if it is it w ... Air Conditioners

We have a new house and it came with central air. I have turned on the air and turned on the circuits and noticed that the outside fan on the outdoor unit was spinning round (good) now, I checked and the fan is not turning. Turned the unit on and off, still no turning and checkecd the circuit breakers...Any help please. Model is Aire_Flo Outdoor unit AFAIR12B30-A P I hear a low hum to the unit outside. I see trouble here.


First check to be sure the circuit breaker for the outside unit is not tripped. Turn the two pole breaker all the way off all the way off and then back on. If the outside unit still does not run you may have fuses in a disconnect box by the outside ... Air Conditioners

My unit is 4 years old. I always turn it off when I leave for work in the am and turn it back on when I get home in the pm. Last night I turned it on at 7:30pm. When I went to the front of the house about 45 minutes later, I noticed the unit outside was trying to turn on but would immediately turn off. I checked the breakers in the garage, turned them off and back on but still had the same problem. The fan inside the house is running but unit outside will not kick on. I looked for a magic


It could be a few things.. It could be the capacitor - which the most economical to replace first..\015\012\015\012If you are not really very mechanically inclined - get a trained pro to come out.. It is very dag ... Air Conditioners

My breaker trips when the outside unit tries to turn on. The inside furnace runs. I cut the inside unit off and the breaker doesn't trip. I manually turn on the outside unit by depressing the cont


Hello, there is a short to ground somewhere, check all the wiring from the inside un it to the outside unit and make sure nothing is touching metal. ... Goodman Air Conditioners

My 38CKCK24330 Unit stopped running, it will try and turn on every 10 or 15 mins you can here it outside buzz, I looked outside at the unit and the fan is not running. The system has power, the breaker switches are working, the furnace turns on fromt he attic. What do I need to trouble shoot, someone told me to check the switch on the unit by pressing it in to see if the fan will turn on once the button is pressed in. I did this but the fan did not turn on. Any help would be appreciated it, I


Hi angelagaddy,With the fan not running and you are hearing a buzzing noise outside this is more likely that the fan motor needs to be replaced or the capacitor ... Air Conditioners

Outside unit will not turn on. Inside fan works fine. This intertherm unit is an upright, 6yrs old. Model number unkown. Fan will turn. No hum coming from unit. inside condenser sits on furnace model # E2EB-015Hb. Freon charging is outside on the lines coming from outside unit.


Hi! You may want to start on having the power supply checked. Good cause why the unit won't power up. Have the compressor checked too just to be sure. ... Intertherm Air Conditioners

Carrier 38CKC042300. oUTSIDE UNIT FAN WAS TURNING REAL SLOW. ac UNIT IS OFF BUT FAN TO OUTSIDE UNIT IS STILL TURNING. sHOULD NOT BE TURNING AT ALL WITH AC UNIT OFF


The outside fan may run if the unit is in defrost mode this is normal for most heat pumps it is there way of trying to keep the outside unit from staying iced over so the next time the unit runs it will have air flow through the coil and the ice will ... Carrier 38CKC042 Air Conditioner

I have a 1993 Model SRHF48U01A (The 0 might be a O (zero) When the thermostat calls for cooling, the inside unit (fan) starts up and continues to run but the outside unit wants to start (it comes on for a second and then trips the breaker that is located behind the outside unit. I can turn the breakers off that are inside the house and let them stay off for a short time and then reset the outside breaker and then turn the inside breakers on and the unit starts and continues to run until the te


Well the trouble is surely at the compressor side. Dont know what kind of repair man you invited. He should have atleast diagnosed the problem. Following can be the causes\015\012\015\0121. Capacitor is slightly faulty (As you said). If t ... Amana Air Conditioners

The outside unit on our Ruud heat pump won't turn on. The inside fan blows but the unit outside sits idle - no fan turning, nothing. It was cooling earlier today, but when I came home from shopping, the house was warm, the inside fan was blowing, but the outside unit is silent, not running.


First look for red button neer the copper line set if has one push it second inspect thermostat wires for weed eater damage check disconnect for fuses check breaker at main panel pull disconect and remove cover check stat wire connections look at the ... Ruud UPMC036 Air Conditioner

My air conditional unit outside ,fans turns on but the unit compressor wont turn on,just stopped working this morning.i turned the thermostat to 72 but only the fan on the outside unit comes on and it is hot inside the house..


Somethings aperson cant fix without a service tech. First it could be wire burnt of capacitor going to compressor. Second it could be bad capacitor. There is a dual capacitor on the ouside unit one side says herm that runs the compressor. Turn pow ... Emerson Quiet Kool 12HT13 Air Conditioner

My fan and heater work fine, but today I turned on my air conditioner for the first time this year. It did not feel like it was getting cooler so I went outside and noticed that my outside unit was not working. I went and checked the breaker and noticed it was tripped, so I turned it off and turned it back on (the breaker). Then all orf the power went off to my house. I then reset my whole breaker box and I heard what sounded like my outside unit explode. I ren over to it and it sounded lik


You had a refrigerant release. Probably two lines rubbing together in the outside unit. I have repaired several of these with this problem. It involves repairing the lines by silver solderingthen pulling a vacuum/ purging with nitrogen an ... Carrier 36KCARMS Air Conditioner

The control for the compressor is not turning on when the remote is set on cool, but the indoor fans turn on. This is a C4822N outside unit and a RS 2422A twin indoor unit. there is 220 volt being sent down on black and white to the indoor unit but nothing comes back to the outside unit on red


... Sanyo Split System Air Conditioner

My air conditioning unit stop working (outside unit). When I turn the unit I notice a buzzz sound comming from the unit. I have pressed the reset button on the unit to see it that would help but nothing happend. I check to see if there was electricity with a voltemeter and the unit is getting current all the way to the capacitor. I turned the power off to the unit to check if the capacitor had a charge and it did. What other things should I be checking? Also, the fand do not turn on! model numbe


Hi, what is happening is, you have power to the outdoor unit. I am glad you have a volt meter. This system is a split unit,condenser outside and indoor unit. This is what you need to check, and what the buzzing is, and why the fan and compressor will ... Ruud UAMB Air Conditioner

Looked on unit outside and it has about 1/4" of ice buildup on unit. i turned off thermostat for about 7 minutes and outside unit never turned off. I have noticed a lot of condensation at the base of my air duct in the basement. I'm not sure what's going on...


Sounds like your contactor is stuck shut. ... Amana Air Conditioners

The airhandler turns off but the outside unit keeps running . the unit runs fine but the airhandler turns off before the outside unit.


It sounds like the contactor or cooling relay is sticking or stuck. ... Whirlpool ACQ158XL Air Conditioner

The fan on the Ruud furnice unit runs all the time but the Ruud ac unit is not kicking on . I know nothing about any of this but would like some Ideas what I might check. I went outside and could not find any kind of breaker on the outside unit. I do have a breaker inside and I turned it off and waited then turned it back on ..no change...


Some Ruuds have a red rubber cap reset button on the bottom of the unit or inside. Usually the fan quits and trips the switch. Or look at the metal run cap with 3 leads on it, if it looks bulged(concave on top) and not flat and sunk in, replace tha ... Ruud Central System Air Conditioner

Earlier this week, I noticed that the house felt "stuffy" but the thermostat showed everything to be cooling as expected. Last night, the house was definitely warmer than expected when we got home. My husband did some checking and found that the outside unit was running as normal, but there was no cool air coming through the vents inside the house. turning the a/c unit off at the thermostat did NOT turn off the outside unit...was only able to do this at the circuit breaker. It seems that the fan


If both fans runs (inside and outside), check if the compresor runs , if does probably the unit is low in freon and needs to be recharged after the freon leak has been fixed (remember this is a seal system and it shouldn't leak), but if the compresso ... Ruud UBHC Air Conditioner

Earlier this week, I noticed that the house felt "stuffy" but the thermostat showed everything to be cooling as expected. Last night, the house was definitely warmer than expected when we got home. My husband did some checking and found that the outside unit was running as normal, but there was no cool air coming through the vents inside the house. turning the a/c unit off at the thermostat did NOT turn off the outside unit...was only able to do this at the circuit breaker. It seems that the fan


Nope, nope, sounds like a stuck contactor in the electrical compartment of the condenser, but there are actually several things that could cause it. ... Air Conditioners

The outside unit is no0t able to start the fan spinning on its own. I have been able to manually engage the outside fan by turning the unit off, turning it on, and then manually spinning the fan when it starts up. The unit will then engage the fan and runs fine until the next cycle when it cannot start the fan on its own again. Can you tell me what part needs to be replaced and about how much it will cost?


Hi!!\015\012\015\012The part you need is called STARTING CAPACITOR and it is located in the same compartment where the electrical connectors are in the outside unit. MAKE SURE THE POWER BREAKER IS OFF before opening the compartment. and befor ... Air Conditioners

Hello, my outside unit was freezing up so I turned it off to let it thaw. When I turned the unit back on, the outside unit didn't come back on. I checked the breaker and it was fine. Can you give me any ideas as to what may be wrong? Thanks, Erich


Hi, \012 \012Here is a tip about troubleshooting your air conditioner...\012There are many things that can cause your air conditioner not to cool… ... Goodman Air Conditioners

I have a Goodman CPLE42-1 split system. I had a power outage and my first floor unit would not cool anymore. The air handler/blower in the ceiling is working fine, but the fan outside is not turning on. When I went to look for an overload reset on it, I switched off the breaker on my second floor unit by accident, and now it is doing the same thing. Both fans on the outside will not turn on. Both thermostats will turn on the air handlers in the ceiling. Seems like I re-created the same exact pr


... Goodman CPLE24-1 Air Conditioner

One of my AC units froze up. I cut the unit off. after it defrosted I turned it back on soon after we smelled wires burning. I turned the unit off. Now when I turn the unit on the outside comp. goes on but the air handler will not turn on , I checked the low volt fuse it is fine and ther is no reset switch, what could have happened there are no burnt wires inside the air handler.


You may have a couple of problems now. The original issue of icing up is most commonly due to low refrigerant in the a/c. For this you will need a professional to correct.The second problem sounds like it may be a bad capacitor for the in ... Air Conditioners

I have a Goodman A/C unit, Inside unit P/N A42-15, my problem is inside blower won't turn on when in A/C outside unit turns on and the copper pipe going to inside unit gets cold, but no blower to circulate air, can some times get blower tot turn on by reseting inside units circuit breakers, also heater works fine.


What about the blower time delay relay: http://americanhvacparts.com/Merchant2/merchant.mvc?Screen ... Air Conditioners

I have a Frigidaire cooling and heating unit. Last night we had freezing rain and ice. I heard a weird noise coming from the unit then smelled a burning smell. I turned the unit off. The top vent outside was covered in ice blocking air flow. I cleaned off the ice and turned the unit back on and it just makes a humming noise. No air is blowing and I looked inside and the fan is not turning.


Sounds like the motor burned up when the ice blocked the air which it was not able to cool the motor it will need to be replaced. (the motor) ... Air Conditioners

I have a goodman cpk j42 -1b ac unit on the outside and a central heat and air unit inside. the ac unit come on and runs fine but when it hit the temp the thermastat clicks and the fan outside goes of but the one inside stays running and will not turn off unless i hit the breaker. is it he fan relay at the outside ac unit?


Hello BWOOD Check the thermostat FAN button is in AUTO position not ON position.That might be it .The relay is in the blower unit but they RARELY become frozen/welded stuck on. ... Air Conditioners