Having problems with your Air Conditioners ?

Cycleing, ok it sound like the heater fan kicks on then off , on then off, on then off, just like that . it will do this on heat cold or in off post. the ac and heat seam to work but i dont get the on off cycleing ! its not the ac blower but like a fent fan for the heater ! had a ac tech tell me it may be my main bord! carrier modle # 58RA (VJU one of these is next not sure witch)050 board # HK42FZ009 S/N 3197A13382


Answers :

You are referring to the inducer motor that is kicking on and off. It is probably a limit switch that might be triggering it to go off and on over and over. It could possibly be the board but I highly doubt it since the ac works just fine. It can also be a short in the wiring going to the inducer motor as well or the inducer motor is going bad. Without checking it out myself with a voltage meter, it's hard to pinpoint exactly what is causing the issue but I highly doubt it is the main board. Get a second opinion.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Cycleing, ok it sound like the heater fan kicks on then off , on then off, on then off, just like that . it will do this on heat cold or in off post. the ac and heat seam to work but i dont get the on off cycleing ! its not the ac blower but like a fent fan for the heater ! had a ac tech tell me it may be my main bord! carrier modle # 58RA (VJU one of these is next not sure witch)050 board # HK42FZ009 S/N 3197A13382


You are referring to the inducer motor that is kicking on and off. It is probably a limit switch that might be triggering it to go off and on over and over. It could possibly be the board but I highly doubt it since the ac works just fine. It can ... Carrier Air Conditioners

A Nordyne air handler, model B3BV-030K, with 4 wire thermostat. Thermostat and AC works fine in "cool". Switch it to "heat" and nothing happens.No fan, no heat.(I have built in heat strips -resistors). I jumpered (on the nordyne circuit board-input from thermostat) from R to W. (24 volts from R to W, which should start the heater. Nothing. No relay "click" like when AC comes on. If i jumper R to Y, AC comes on ok. Does this sound like a relay gone bad on the circuit board? Or what? If relay bad,


Do you get heat when you jumper R, G & W? ... Ruud Central System Air Conditioner

I have a rheem electric furnace with 2 speed fan, seems like the fan runs full bore when its on, even when i just cycle the blower control to ''on'' and its supposed to run at reduced speed. I have to experience with central heating and air, was wondering if it would be the circuit card with the dip switches. Unit was installed in 2003 with a heat pump.


If it is a variable speed blower most likely the dip switch settings. Check the installation manual to see how to slow it down. ... Air Conditioners

Heater!!! Unit acts like its heating but there is no hot air. Fan turns on, heat symbol is showing on the remote, but no heat


I am experiencing a similar problem with my Mitsubishi slimline MSH09TW unit; about 4 years old; It use to give us very hot air now it is giving some what hot air; northeastern USA current temperature about 15F. You think frigid weather in Cranbury N ... Mitsubishi MS12TN Air Conditioner

Unless we set the thermostat very high, like 80 degrees, the heater will blow cold air. When the heat does blow, it will eventually stop blowing heat and the fan will continue to blow cold air.


Check and make sure the filter is clean. This sounds like a restriction in the system. If the unit has central cooling make sure ther indoor evaporator coil is clean at the furance.The unit may be cycling the burners on and off at the high heat limi ... Air Conditioners

I purchased a AMCOR portable air conditioner Model ALD12000E/EH on Mar 30 2009. This unit does not heat or cool only the fan works. When the unit was first received the heater worked fine although there was a strong odor associated with the heat cycle. I am not sure if this unit is worth the cost of repair. Can you make a recommendation?


Hi path531,Do you have any further inquiry about the system? Hope it helps.Thank you for using FixYa. ... Amcor Air Conditioners

Lg lsu242he a/c runs fine but when unit is in heating cycle ,the fan wont stay on.fan came on a split second then cut off.outdoor runs fine in both heat and cool.LCD seems like it is fluttering in this mode as well.checked defrost sensors and they both are open.


Hi, whenever this type of problem is exhibited, usually we suspect the thermostat itself, as this is what ultimately controls the fan.\015\012\015\012It still maybe a sensor, (the ONLY way to tell is by substitution with a "Known Good") althou ... Air Conditioners

This is a heating and cooling through the wall heat pump. It works normally when heating is selected - the heat pump runs and both speeds of the fan blow warm air. But nothing runs when cooling is selected. In other words the unit works normally when "High Heat" or "Low Heat" is selected but nothing runs when "High Cool", "Low Cool" or "Fan Only" is selected. The position of the Fan Cycle Switch has no effect - behavior of the unit is the same in both positions of the Fan Cycle Switch.


You have a bad board or bad switch. I would say board. You can have service tech check this out. There is only so far you can go without knowledge of Controls ad electricity. Russ ... Air Conditioners

I have a carrier a/c and Heater and the fan runs constantly a/c cycles on and off so does the heat


... Carrier 38CKC042 Air Conditioner

I have a few issues with an old probably dinosaur Coleman Presidential III 7995a-856 Heating unit. I've had 3 different repairmen look at it and they're clueless. The main pilot will light and stay lit until I turn on the heater from the thermostat. It'll click and the intense flame will begin shortly after the 3 min. delay. It will stay lit for approximately 2-4 minutes and it'll blow itself out. If I'm lucky, it'll stay lit and the fan will sound like it's starting but is tempermental. Some


Hi, look 9/10 problems are to do with either the thermistor or thermostat, Especially when the faults is intermittent, and sporadic.or perhaps the Main Controller. Always check the Gas flow & regulator diaphragm is OK..too.. \012The fac ... Air Conditioners

I have a Lg LWC122RH-2 Window Reverse Cycle Air Conditioner. It is 5 years old. The fan works fine. The Cooling and heating don't work. When I turn it on to cool setting, I can hear the compressor trying to kick in and a popping sound and can hear the unit go up and down a bit, like a humming sort of sound.


Think yu must take your compressor to the specialist so that they can check if cycling valve is operating. or may be wiring problem to the valve. ... LG Heat cool Window Air Conditioner

Goodman cplt 36-18 heat pump . not cooling. outside unit fan does not cycle on. sounds like compressor is on.any suggestions


Hello my name is Heath it will be my pleasure to assist you. The fan motor may have burned out or the bearings in the motor seized up. Try spinning the blade with something by sticking it through the grate if the fan blade spins easy you will need an ... Goodman CLQ36AR49 Air Conditioner

The heater was working fine when we went to bed but in the morning we got up to find it had stopped working even though the thermostat showed the heat to be on.We checked the pilot flame and it is on.It is a reverse cycle Brivis Buffalo system(1984) model.The fan is alo working fine.


This is too deep to explain, so its best to call a service tech, with all his diagnostic tools Thank-you-very-much! ... Air Conditioners

Amana PTH153B35AK This unit is less than 30 days old, heats fine cools fine, but when i have it in heat mode,set @ 70 or so, as soon as the room heats up, the unit will cycle into a/c mode and blow super cold air for about 5 minutes than return to heating. Sometimes it will reach the desired temp. and turn off like it is supposed to do, but for the most part it just cycles back and forth from hot to cold...Amana has the worse help/service i have ever seen, i was on the phone for an hour,everybod


This often happens if the unit is oversized or to close to a wall or object. ... Amana PTC153B35AK Air Conditioner

I have a goodman gsh130361 3 ton heat & air. It was installed 05/05/2008. all seemed well until cold weather, in 2009. The fan turns on and start blowing before the heat box is even warm. The heat set on 70----- when it gets 68 or 69 {in the house} the out side pump kicks in, 10 to 20 seconds later the fan turns on and blows freezing air into the house. the temperture will drop dramatically for the next 1 & 1/2 minute. The box will heat up and then all is well untill the next cycle.


The PCB unit that controls the thermostat and Coolant is malfunctioning... check that particular unit...that would help.... ... Goodman Air Conditioners

Fugitsu ART45LUAK ducted airconditioning. To heat the house I set the fan low, heat manual and thermostat 24C, the temperature keeps creaping up to 27C. The you can hear the thermostat being reached but the heat comes on agin, then agin till its really hot. Same thing happens when using the cooling setting, but in opposing temp ie set to 24 will drop to 20. If the select temp and fan is set to auto, it will heat up too much and then will then auto cool down too much like its fighting itself.


... Fujitsu Air Conditioners

Not heating I have a Intertherm. the heater does not turn on, I can get the fan and every thing to turn on but not the heating coil. the heating coil starts but then shuts off before the fan kicks on.


1st you said the fan runs..but partial info so best guess it fan limit contor bad. ... Intertherm P3RA-048K Air Conditioner

My thermastat is just a regular one with on,fan,auto, on the left side and heat off and cool on the right. what I would like to know is what should the left side be set at whjen the heat is on. I have it just on the on and heat but fan seems to be running all the time. Please help. thank you.


Hi,The left side fan switch should normally be in the "auto" position.If the fan is still running all the time, then there is a problem in the furnace/air handler... the fan switch in there is bad and keep the fan on when it should not be ... Honeywell Air Conditioners

Over the summer we shut our thermostats off so that our furnace would not turn on since the weather was beautiful. But we noticed that our heaters in our downstairs part of our house were warm. The furnace did not sound like it was on, but for some reason, the heaters were emitting heat. In order to stop this, we had to manually shut off the valves on the furnace. This stopped the heat from coming out of the heaters. But now that it is fall, I have the thermostats on and even when the tempera


Do you have a water heating system? ... Air Conditioners

Our Furnace doesnt seem to be working correct. We an: Air Pro BGM075128 and is Natural Gas. It will turn on when we turn up the thermostat.. but we never get any heat through the vents. There is a switch on the side that is "on" and one that is "fan". If we turn on the "fan" only cold air gets blown through. It looks like this is for cool air. So, if we leave the fan off and the "on" swith on, we get the furnace firing up, but no heat ever comes through the vents. I tested out the thermo


Sounds like the blower motor is not working, if the furnace is actually lighting up and the burns are ignited. You should set your thermostat to auto, as if it is on fan then the fan runs all the time until you take it off of fan. I am a little confu ... Air Conditioners

Hello, I have a Heater/Furnace problem. I have a Carrier 58RAV095-16 Natural Gas Furnace. My furnace keeps restarting it's heating process. Upon turning the heater on, a small fan will engage and run for about 60 seconds, then the fan turns off and the gas engages and the igniter clicks and you hear the gas combust and the flames spew out onto the heating rods(?) and after a minute or so, the big fan will turn on and begin circulating air throughout the house. Sounds all good so far? Well


... Air Conditioners

I have Amtrol water heater. Recently I noticed that boiler trying to start several times till it finally starts. I decided to check if it is a boiler or water heater problem and turned on house heating system that was OFF for summer time. Boiler started immediately without any trying atemptes. Looks like it is a water heater problem. My qustion is: what should I change most likely - temp. sensor or temp.control? Thank you. Vlad


That's a good question. What a shop would do, is try one, then, if that didn't work, try the other, in this case- if they had the parts. It's hard to test the sensor correctly, and the temp. control might be intermittent, which means it would sh ... Air Conditioners

RUUD heater The heater will run for about 20 to 30 minutes then it will cycle on and off. The igniter lights every time. It turns on the gas but only stays on for about 5 seconds then shuts off. The fan comes on for about 2 minutes then the cycle starts all over again.


Sounds like a dirty flame sense rod. Be sure to shut off power before removing the rod and cleaning it with sandpaper or steel wool. Do not touch or disturb the hot surface ignitor or you may cause it to fail. ... Air Conditioners

Have an amana 80 furnace blows but wont light now wont shut off . When I started testing it upper fan was stuck loosened it up. Then I reset the small button, fans started. But no heat. Then I cleaned up the heat sensor and igniter. now It wont shut it off unless I shut it of fthe breaker. Also It has a 5 blinking code. Does this sound like a thermostat? Thank you


... Air Conditioners

Weather King 8PJ10NDR01 When I turn the heater switch to ON position the furnace runs what sounds like an internal fan. Second, the igniter glows and when it reaches it's hottest stage the fan thrusts air through the air ducts / vents and the burners light for about 30 seconds to a minute blowing cool air. After a period of about 30 seconds to a minute the burner turns off. After the igniter and burners repeat this about 2 times the heater shuts down by it's self, even when the temp gauge has no


The gas valve is not sensing flame, and the unit shuts down on safety.\015\012\015\012Chances are the flame sensor is bad, its a common problem.\015\012\015\012If its a thermocouple you can buy one for 10 bucks, If its a newer ... Weather King 12AJA4801AH Air Conditioner