Regardless of weather the thermostats are calling for heat or not, or even if I shut the thermostats off completely the fan keeps running. the only way to stop the fan is to shutoff power to the furnace. Does this require replacement of the IFC board or is there something else that I can check first? The system does operate correctly in the heat mode and there are no flashing lights on the circuit board. Both green lights are lit and the orange is not, because I use an electric plenum as my p


Answers :

I would suggest buying the new unit or calling to have a tech sent out to you to have them fix it. If you can buy the part you'll save money from what the company will charge you, plus labor fees. Good Luck though! Sorry your having such a hard time with this!!
Hi there!

I've had the same problem with one of my customers and i ended up replacing the IFC board in one Identical Air Conditioner i picked up at the junk shop. Never head the customer complaint after that. I suspected first the regulating circuits as well as the thermostat but it yields okay for the ohm-meter.

Hope this helps.
levibit


Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Regardless of weather the thermostats are calling for heat or not, or even if I shut the thermostats off completely the fan keeps running. the only way to stop the fan is to shutoff power to the furnace. Does this require replacement of the IFC board or is there something else that I can check first? The system does operate correctly in the heat mode and there are no flashing lights on the circuit board. Both green lights are lit and the orange is not, because I use an electric plenum as my p


I would suggest buying the new unit or calling to have a tech sent out to you to have them fix it. If you can buy the part you'll save money from what the company will charge you, plus labor fees. Good Luck though! Sorry your having such a hard time ... Ruud UBHC Air Conditioner

Jan 12, 2010 - My air handler fan (american Standard #TWE065E13FBO) works during a/c operation but not during heating operation. Checked continunity through the the thermo sw and throught the heating coils - the coil on the heat relay is ohming good. I am thinking it might be the fan control card - but its expensive - 400+ Jan 12, 2010 - the fan in manual or auto no good in heat, there are some led light in the circurt board (fan controller) a green light (CFM) which is on when where is power


The blower won't come on with the thermostat switch set to manual either? Does the heating section come on and the fan just does not blow the heat out? This is usually a fan limit problem or relay but you say the relay is good so is there a fan limit ... Air Conditioners

I have a suburban lp furnace and duotherm air/heat pump roof unit. duothern thermostat. 20 amp breaker kicked ( reset breaker) & furnace quit. NOW furnace fan comes on but does not light, and the front AC will not work either, when in the COOL position on STAT the unit blows warm air instead of cold. I replaced the Thermostat and a Tech guy checked the board in the furnace and it was OK. He also switched the board from the rear air with the front and nothing changed. Rear air and heat pump works


I'm not sure what the problem may be but you could try calling All\015\012Seasons RV Appliance Parts & Service. There number is\015\0121-800-344-0673 they have helped me in the past. That and there tech\015\012calls are free so it wouldn't hurt ... Dometic Rooftop RV Air Conditioner

I have a friedrich ductless split m# mw24cy3f .. call for cool only fan runs inside, call for heat nothing runs, outdoor temp at the moment is 38 degrees, error code light blinks on indoor unit... operation and timer blinks simutaneously 2 times then operation blinks 5 more times. not sure what the error code means and how to reset and correct the problem.


Not able to find the error codes for the unit number you gave but, here is a number you can call to get them. sorry not more help.\015\012\015\012\015\012\015\012\015\012\015\012\015\0121-866-793-0323\015\012 ... Friedrich Air Conditioners

My outdoor heat will not operate. It is a Carrier 38YRA042330, with a Carrier Thermidistat thermostat and a Carrier Air Handler 40FFKB005300. I have an H5 error code on the thermostat will I put it in Heat mode and raise the setting to call for heating. I changed the air filter on the air handler when I realized the heat pump was not operating. The air filter was pretty dirty. The system will operate in aux/emerg heat mode, with the fan in Auto or On mode, and will maintain the thermostat


You need to go oside and look for a red reset button on the unit. you tripped the high ressure switch when you let your filter get that dirty. go check on this and when your done if it still is not working then ask me more. ... Carrier Air Conditioners

I have an intertherm electric furnace FEH-A020, with multispeed blower installed when A/C added. My problem is blower operation. at the end of the cooling season with fan set to auto operation the fan ran continuously. Now that I've turned the unit back on for heat the blower will only function with the switch in the on position (continuous operation), in auto mode the heating elements come on with the signal from the thermostat (Honeywell CT3400), but the fan does not. I checked the fan relay p


The model of T-stat you gave comes up as a discontinued model on Honeywell's web site, but it looks to be a manual stat that type of stat would have to be wired with a summer winter switch with electric heat, allowing it to turn on the fan with a cal ... Intertherm P3RA-048K Air Conditioner

A Nordyne air handler, model B3BV-030K, with 4 wire thermostat. Thermostat and AC works fine in "cool". Switch it to "heat" and nothing happens.No fan, no heat.(I have built in heat strips -resistors). I jumpered (on the nordyne circuit board-input from thermostat) from R to W. (24 volts from R to W, which should start the heater. Nothing. No relay "click" like when AC comes on. If i jumper R to Y, AC comes on ok. Does this sound like a relay gone bad on the circuit board? Or what? If relay bad,


Do you get heat when you jumper R, G & W? ... Ruud Central System Air Conditioner

Goodman Gas Pack Unit. Model PGB048125 Control Board 1068-400 Installed 1993. ** No Heat. ** Checked breaker at box. ** Have changed thermostat, no change. ** control board LED light shows: Red: System turned off at thermostat Red: A/C turned on. Flashing Red: Heat turned on at thermostat.


Count the number of flashes and consult your manual as to what the flashes mean. The blower access door may show the faults codes. What you probably have is a contaminated flame sensor or maybe a rollout switch tripped due to rusty burners or air res ... Air Conditioners

HI, I had a gas furnace (GOODMAN GMP125-4).When i turn heat on from thermostat, the burner is not light up, the induction motor is not running. I took off the panel and I also found that the status light (red light)on Circuit board is NOT on also.Is this a circuit board problem or thermostat problem?


... Air Conditioners

LENNOX HS26-048-3P Installing Honeywell wifi thermostat. C terminal on control board was connected to X on the old thermostat. The X terminal wire on the old thermostat is connected to the C terminal on the control board. I used this wire to connect to the thermostat C terminal and now the compressor fails to come on. The slow flashing lights indicate the thermostat is asking for cool and the fan comes on, compressor does not come on.


... Air Conditioners

I have an intertherm rpbmb030k combo a/c and heat. Had frion put in the unit over the summer and a new digital thermostat. Unit has worked great until we needed heat. Unit works great on aux. heat but keeps switching to to defrost mode when standard heat is on. Switched out the defrost board on the unit to no avail and an a/c guy checked to ensure the new thermostat was wired correctly.


Hi, if the unit had a leak in it, was the leak located and repaired? Did he check the pressures in the unit now? If it switches to the aux mode ( Heat Strips ) is normally caused when your primary unit, compressor and freon are low on charge. I would ... Intertherm P3RA-060K Air Conditioner

Goodman GSH130301AB heat pump with Braeburn 1200 multi-stage thermostat - both less than 1 year old and installed in new construction. Heat can be set at 60, fan on AUTO, with room temp at 70 and heat will kick on and stay on. When this happens, turning thermostat to OFF does nothing - system continues to blow heat - and I can only shut it off by flipping the breaker. This only happens now and then - typically works fine. All wiring appears to be correct though reversing valve for cooling is


The reversing valve wire needs to be on the o terminal.nothing will be on the b terminal on the thermostat ... Goodman Air Conditioners

My Mitsubishi Mr. Slim heat pump (indoor unit MSZ-A09NA / A-15NA / A12NA / A17NA, according to the operating manual; outdoor unit MXZ-3A30NA) is not providing heat. The left green indicator light blinks when I try to restart it (Breaker, emergency heat operation), so I've turned it off). The problem began when I was clearing the condenser of 3 feet of snow and ice. The fan inside the condenser can move freely. When I sent this question earlier, the wrong model number was in the headline. If heat


Here is the service manual for the model # you gave. http://www.mehvac.com/UploadedFiles/Resource/MSZ-FD09~12NA_S ... Air Conditioners

Fujitsu ASU9RLQ I have a new mini split heat pump/air conditoiner installed. The electronic air cleaner does not operate correctly. After 4-5 minutes of operation, the Operation (red) light on the front of the wall unit flashes 4 times and the Timer (grn) light flashes 7 times indicating an air cleaner monitor trial protection error. The filter is clean (new) and the front panel is closed. I'd appreciate advice re how to resolve the error.


Check indoor unit sirkit board ... Fujitsu 18C1 Air Conditioner

I use a Harbor Breeze fan/light remote to operate a ceiling light. On the back of the remote it has this set of num/letters: FCCID KUJCE9103; It has three speeds for fan and On/Off/Dim for the light. The remote no longer operates the light. The 9 volt battery is good. The remote is stamped 2005. 10. when it passed inspection. Can I buy any remote that's similiar and assume the frequency is correct or do I need a specific one? If so, can u send me the one I need?


The receiver is dead. It doesn't have any batteries, and why would it? It operates on 110v household current. The receiver needs to be replaced. ... Air Conditioners

Gold Star mini split heat pump 24,000 btu. Changed indooe as we as outdoor boards and still goes in cooling mode only. Reset button on outdoor board calls in heat but not by inside hand set. Len Cabana Techno Refrig. Inc. PS: Sometimes indoor green light flashes five times. Close power breaker and try again with inside hand set. Still no heat or fan on.


On a heat pump the difference from heat to cool is the reversing valve.\015\012In cooling or heating the Y1 terminal will always be energized, this is the contactor.\015\012Depending on brand the reversing valve will either be energized i ... LG LS-K2430HL Heat Cool Mini Split Air Conditioner

Our Furnace doesnt seem to be working correct. We an: Air Pro BGM075128 and is Natural Gas. It will turn on when we turn up the thermostat.. but we never get any heat through the vents. There is a switch on the side that is "on" and one that is "fan". If we turn on the "fan" only cold air gets blown through. It looks like this is for cool air. So, if we leave the fan off and the "on" swith on, we get the furnace firing up, but no heat ever comes through the vents. I tested out the thermo


Sounds like the blower motor is not working, if the furnace is actually lighting up and the burns are ignited. You should set your thermostat to auto, as if it is on fan then the fan runs all the time until you take it off of fan. I am a little confu ... Air Conditioners

I have a Goodman Model number AR24-1 unit and the blower moter will not start with it turned on to fan or cool or heat. I have checked the thermostat and the unit runs outside. Just no blower. Can I jump the blower motor as I replaced the capacitor today. Hear are some numbers that may help. Part Number #15212-50 Volt 208/240 Amp 1.5 HP 1/5 No heat Kit It has a Goodman switch board # B1370735 that I can check with my meter if needed. I have checked the thermostat in the attic also. Seems like


... Air Conditioners

Carrier 58RAV095-16 will process thru the test sequence properly: inducer fan, ignitor, blower high, blower low, all ok. fuse checked good on controller board. when commanded to supply heat by the thermostat controller in the living space the unit runs with fan only, no gas, no ignition. changed thermostat controller, no joy. Comments: Jan 31, 2010 - thermocouple/ignitor is ok and positioned well. It tests ok too. I changed it last year. I am not getting gas flow so I suspect gas control va


Go to the furnace and turn off the power take the door off you must have a multimeter inhand with the cover off the furnace and access to the gas valve put yor meter leads on the wires going to the gas valve turn the power on and after the ignitor gl ... Air Conditioners

Carrier 58RAV095-16 will process thru the test sequence properly: inducer fan, ignitor, blower high, blower low, all ok. fuse checked good on controller board. when commanded to supply heat by the thermostat controller in the living space the unit runs with fan only, no gas, no ignition. changed thermostat controller, no joy.


Hello \015\012Your closing the circut,and getting power to the ignitor.\015\012\015\012Have you tried another t stat or check your wiring low voltage side.\015\012\015\012Is there a pre purge fan for gas to be cleaned ou ... Air Conditioners

Honeywell thermostat; Lennox elite series furnace thermostat reaches and exceeds temperature setting but frunace continues to run, remove trermostat from wall and furnace continues to run. Not just fan- entire system, I have removed both panels from the furnaced itself and as soon as power is supplied the furnace immediately lights (gas) and begins to heat house. Current inside temperature is 77; set to heat to 70.


When the furnace exceeds the temperature set by the thermostat, this could be indicative of several issues. The thermostat mounted crooked. When a thermostat isn't level on the wall, it can affect the automatic on/off function. To fix this pro ... Air Conditioners

Have an amana 80 furnace blows but wont light now wont shut off . When I started testing it upper fan was stuck loosened it up. Then I reset the small button, fans started. But no heat. Then I cleaned up the heat sensor and igniter. now It wont shut it off unless I shut it of fthe breaker. Also It has a 5 blinking code. Does this sound like a thermostat? Thank you


... Air Conditioners

The bard geothermal (open loop) furnace will not produce heat. I will turn on the heat and the furnace will begin to turn on. The water will start to flow and then the furnace turns off. A green light on the top of the bard thermostat will then turn on. The fan unit will not turn on when the fan control is turned to ON not auto. Help.


... Friedrich WY12A33G 11300 10900 BTU HEAT PUMP AIR CONDITON IN STOCK Air Conditioner

We have model # 58SXA080-JG Gas Furnace-the fan is not turning on-heat is not coming thru the vents. We had the control unit/circuit board replaced yesterday. The fan, pilot light and heat came thru the vents for a few minutes-then stopped. Can't get it to come back on..Trying to find what else it could be


Blower Control Circuit Board (Carrier, Payne, Bryant) is the faulty partInput Control Voltage: 18-30 VAC.\015\012Frequency: 50/60 Hz.\015\012Power Consumption: 5 watts max.\015\012Output Ratings:-on high contact: 20 amps resistive @ ... Carrier XHB123D X/Y Series Heat/Cool Air Conditioner

Heater: Rheem Classic 90 Model RGRJ In service since 7/02 Problem: Thermostat calls for heat Steady Green Light Inducer motor starts and runs lighter comes on and glows no gas, no flame Voltage across gas valve is zero no yellow light lighter goes out inducer motor quits blower is off no heat Troubleshooting activities: Resetting (power off then on) will bring on the flame 99% of the time checked for exhaust clogs, none found no evidence of water at inducer fan housing barb have


Failed control board. Replace circuit board. ... Air Conditioners