Having problems with your Air Conditioners ?

Furnace ignition York P2DP10N gas furnace - when its called to heat some times ingnition sequence is normal. Other times its haulted after 20 seconds and the sequence is restarted. Some times this happens 2-3 times before the burner gas valve is openind. There is nothing wrong with the hot surface, the sequence is not allowed to get to the stage when its stopped.


Answers :

The probable cause is the pressure switch. It's a round disk either silver or black in color. They can stick in either the closed position or the open position depending on what your unit needs to fire. You can take the rubber hose off from the inducer motor and blow lightly and **** in lightly to make sure the switch is free from debris. Then try again and if it continues, then you will need to replace the switch. It can also be a limit switch that is going bad as well.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Furnace ignition York P2DP10N gas furnace - when its called to heat some times ingnition sequence is normal. Other times its haulted after 20 seconds and the sequence is restarted. Some times this happens 2-3 times before the burner gas valve is openind. There is nothing wrong with the hot surface, the sequence is not allowed to get to the stage when its stopped.


The probable cause is the pressure switch. It's a round disk either silver or black in color. They can stick in either the closed position or the open position depending on what your unit needs to fire. You can take the rubber hose off from the in ... Air Conditioners

I have a goodman furnace model gmpn 080-4 92% 1997 Gas vave would not open after igniter came on. the voltage was 15 prior to sequence and 26 upon time for gas valve to come on. I ran a jumper from trans to gas valve and it opened. I replaced board. it functions properly now, but I still have 15 volts at gas valve when it is not calling for it to open. Is this normal? If not what could cause this?


General rule is 24 volts to operate control valve. check common at valve to white at valve or out of board. 24 in call, less than 24 when off. sometime s these things back feed or give a false reading. voltage can read say 15 volts but under a load i ... Goodman Air Conditioners

I have a problem with my Johnstone furnace "Mod.# MBA 040 nh2r" every time the furnace calls for heat the gas valve release the gas a few seconds before the igniter witch causes a small explosion. This happens after the firt initial start and continues every few seconds.Also I can't seem to find this brand of furnace.


Hi, this is called delayed ignition which raw gas is let into the combustion chamber and ignited a little to late. which causes this explosion. I have had my eye brows and eye lashes burned completely off do to this. Johnstone is a very popular brand ... Air Conditioners

Rheem-Gas Furnace I have a gas furnace that will not ignite. I have attempted many times to start/ignite it using the manual suggested sequence, and I have been unsucessful. In diagnosing the problem(s) the technicial manual flowchart suggests that I replace the vent pressure switch. How do I not know I need to replace the igniter. What tests can I do to ensure it is.If I let a proffessional trained technician perform the work, How much should I expect to spend?


It may be a little difficult to diagnose if you don't have a volt/ohm meter to check the switches with, but I will try to help what I can.\015\012\015\012The first thing to check is the pressure hose from the vent fan to the pressure swit ... Air Conditioners

I have two heatpumps up and downstairs and two furnaces (piigy back). At times my pump outside freezes up and cold air blows in the house. I was told that I needed a kit to tell my furnace to turn on when it gets to cold for the heat pump. It will cost 400. This is the third time they came out. 1-nothing wrong. 2-New thermostat 3-Need kit. Is this something I can do? Amana Heat Pump RHA36B2A


Hi,\015\012A couple of things... First your furnace should be 2nd stage on a 2 stage thermostat and if the heat pump don't keep up your furnace should be coming on anyway...If you get a Honeywell Vision Pro 8000 series thermostat for 2 stage he ... Air Conditioners

I have a 2 year old Goodman GDS80703ANA furnace that has always had a problem starting. Sometimes it starts on the first attempt but other times it takes 2 or 3 attempts. This is what I see happening: The Induced Draft Blower starts and runs- the Igniter will glow for a few seconds and just as the igniter starts to stop glowing I hear the Gas Valve click and open but it is too late. On the next attempt or so, the Gas Valve will open sooner and burner will ignite. My question is: Is the Integrate


The board controls the timing ... Air Conditioners

A 2 month old Goodman GMH95 natural gas furnace has been working properly until tonight. Now it starts up properly, but after 30 seconds (and right when the cirulator fan kicks on) it shuts the gas valve stopping the flame. LED light flashes 8 times, which is not an option on the trouble shooting guide. Unit will retry every few minutes and cycles this way over and over. It appears the control module is not receiving the gas flame detection signal. What do we need to do?


Goodman's control boards are very sensitive as well as the connections to the gas valves. Check the wires and make sure they are snug and tight. With it being only 2 months old, I doubt the board is bad or the flame sensor(unless it is a used syste ... Air Conditioners

I have a problem with an Armstrong SX90 gas furnace. model GUK100D14-2B serial number 8497G26541 The ignitor is not 'glowing' and therefore the pilot won't light. Everything seems to be sequencing okay...the blower starts and you can hear the gas valve click when the ignitor should glow but no glow....any ideas?


Buy a new ignitor either from the ignitor store online, or your local distributer, Contracter, dealer.. they usually run from 15 dollars to 35. Their simple to change out and deffinite do it yourselfer... Oh and turn off power at breaker panel, y ... Air Conditioners

I'm working on a Payne gas pack furnace heater and a/c unit. I replaced the tstat cause the a/c worked but not the heat,also replaced the spark ignition module with gas valve,the transformer, and the contacter now nothing comes on.


Pull the fuses and check voltage line to line with the fuses out you should have 208 to 240 volts if you have 50 or so volts try line to ground if you have 120 on one leg it will back feed with the fuses in,because of the windings involved. in any ca ... Air Conditioners

I have an amana dual fuel heat pump with LP gas furnace. the furnace will not light. the ignitor heats up, acts like it's not getting LP to the burner and i don't get 24 volts to the pressure switch just above the gas valve, or to the gas valve itself. i cut the power to the unit, removed pintle to the gas valve to ck for gas to the valve and it's o.k.,. what do i need to check next, i don't know how to get codes out of self diagnostic system and don't know if these codes would effect the furnac


... Amana Air Conditioners

I have a mobile home furnace Intertherm #1378. The pilot light is on, but the burner will not light. The thermostat clicks on and everything seems to be running properly, but there is no flame. Last year I had the motor replaced and the relay switch. What could be wrong? Is there a gas valve that is not opening properly.


First make sure that the gas valve is in the on position. There is a spring load diaphragm that will stick when not in use over time, When the t-stat clicks on for heat tap the valve with a hammer L ... Intertherm Air Conditioners

I have a Bryant package unit that clicks when I put in the fuses. It is not a loud click that you would expect with a gas valve however. The light on the furnace control is flashing 6 times.


The codes are generally printed on the back of the bottom cover on residential units (blower section). On light commercial, the cover for the controls section (follow the line voltage and thermostat wires.\015\012 Off the cuff, if it has a sparker, t ... Air Conditioners

OK I am a dumb A--. I did not turn the power off to my Payne PG9MAA Condensing Gas Furnace. Also A/C. In my futile attempt at relocating the thermostat. I 1. did not turn off the unit 2. I did not have enough wire so I spliced in a new longer one. 3. Voila' there is absolutely nothing on the thermostat showing power. I used the voltage regulator and put the contacts one on red and the other I went in sequence to all the other wires and it read 11.00 or so volts.. If I changed the (lead) or


Depends if its a 12 volt or 24 volt system and if your meter is reading right also check meter then check red wire if its a 12 volt thats what you should have and 24 so on or you have a dead short good luck with that one just be calm a go thru all t ... Air Conditioners

Intertherm gas furnace 80 % mod# MMHA-070ABHR-05 will not open gas valve and light <changed gas valve <control board<ignitor all three limits and still not working I have been in the hvac buisness for 10 years but cant solve this one ,the board is flashing a 3 code < i have called a fellow tech who had the same problem on the exact same model last year and he spent 10 hrs trying to repair this unit but was unsuccesfull also<i can make this furnace burn by wiring 24 volts direct t


... Intertherm Air Conditioners

I have a 1985 Bryant central air Furnace model 395BAW048095 with a White Rogers 36E gas valve. The flue is metal and there is a fan within the furnace to create a vacume at the base of the flue pipe conection that turns on when a call for heat comes from the thermostat at startup to ignition. The spark fires but no gas is released by the valve for the pilot to lite. Added information: The blower fan is set to continually run, I replaced the pressure switch (306621) and the limit switch (HH12ZB18


... Air Conditioners

Ignitor fires early or gas valve turns on too late - no ignition


Put your hand on the gas valve and see if the click of the valve is opening just before the ignitor goes off if it does your valve is going bad ... Air Conditioners

I have a furnace and i just replaced a combonation hsi sensor and after i did the gas valve wants to open the second the hsi starts to glow but then two seconds later the gas valve opens and closes and opens and closes VERY DANGEROUS WHY IS THIS HAPPENING I have 28 Volts going to my gas valve and it is steady


Was this a direct replacement sensor os was ther rewiring possible short ... Air Conditioners

Furance I have 2 Ruud Achiever 90 Plus gas furnaces. Units were installed in 2004. One unit flames out after ignition and just prior to the fan kicking in. Confirmed gas valve is functional by switching out valves. Check all wire connections. Could it be the remote sensor or another 24 volt sensor at the IFC that is locking out the gas valve?


There should be a flame rod that senses the flame , if not will shut off gas valve. It is a stainless steel rod that is in the flame path and wires into the panel ground. You might try to clean it with some steel wool or fine paper. Sometimes they wi ... Ruud UAKA030 Air Conditioner

My intertherm furnace ignitor glows but the gas valve doesn't open


... Intertherm Gas Furnaces - M1GB-056-AA

Model rgdg-100auer 100,000 btu with pilot light. i light the polit that is fine turn on gas that is ok runs for 1 minute then shut all gas off and i have to relight the pilot time after time but never stays lit. replaced gas combination controll valve and also replaced themocouple but neighter one did not fix the promblem.


If this happens each time the blower starts, you have a crack in the heat exchanger and need to replace furnace. If the blower is not starting, it could be a high limit opening up because of the heat being generated. By pass the high limit circuit to ... Air Conditioners

Dura-Glo Centurion Model 48 gas fireplace gas valve not letting pilot stay on; has new Tpile, which is activating valve (I can hear click internally when I hook up leads from hot Tpile. Unit wasn't used for quite a while and was found in "pilot" position but not lit. upon re-lighting (long manual hold time) started working properly. We thought maybe intermittent wind blowout, but then Tcouple quit making juice. Replaced, but now just a click from inside valve. I haven't found any tags on the va


Ed, when you installed the new Thermocouple did you finer tighten and just 1/4 turn more with a wrench? Or did you tighten it more than that? If you did over tighten it, the Thermocouple probably locked up the control valve. Unscrew it, give it a co ... Air Conditioners

I have a heil furnace / air conditioner unit. The heil is model # N9MP2075812A3 serial# L024970895. It has an intl comfort evap coil Model EPD24B15C2 serial# X120393352. It was installed in 2003. I turned on my air conditioning and the furnace keeps cycling on and off. I checked the filter and it is new. It is a gas furnace and the gas valve is blinking stadily which means it is ok. It humms....tries to turn on.....blows for about 10-20 seconds....turns off...tries to turn back on...again and ag


Not sure I understand the description.\015\012You said the "furnace" keeps cycling on and off when you turn on the AC.\015\012But you must have meant the AC cycles, because if the actual furnace went on, that would an extremely seroius pr ... Air Conditioners

I have a Marco gas fireplace model# 794019C. It is the millivolt pilot generator type. I first changed the thermopile and cleaned the spark ignitor to get it to light. I have checked continuity and everything checks out. Damper switch opens and closes, burner wall switch is good. When I jump the the redundant gas valve with jumper wire from one of the three terminals it does turn the burner on. Some of the time it is hard to keep pilot light lit, it will trip gas valve when you move from pilot t


Mike, I suspect that the problem you're having is not related to the new Thermoplie (Pilot Generator) you installed. Its with the Thermocouple. The clue was "Some of the time its hard to keep the pilot light lit". The Thermopile controls the opening ... Air Conditioners

I have a dayton gas furnace aand bought the kit to change it to lp gas. Ater installing the parts it does not work. The pilot is to big and i have adjusted the control all the way down. And thge valve wont open and let the lp gas to the burners. I replaced the valve and the thermostat and the thermocouple. Also am trying to use a propane bottle off my grill. is this the problem? I didnt want to spend the money for a large tank until I knew it worked.


Hi, Let me get this straight, you converted the original valve to l.p by replacing the spring and other small parts in the valve orfice ect. Then you had the problems. So, you replaced the valve, thermostat and thermocouple after that? If I am corre ... Air Conditioners

Have old Amana gasfurnace combo unit. Has Natural gas to it. First the diaphram went bad so i replaced it. Also replaced ignitor when the diaphram did'nt fix it. It cycles 3 times and locks out. If I remove exaust fan hose while it's cycleing then the gas valve will open other wise never will. if I shut it off and wait a very short time it will relight automatitly. If I wait to long it's back to 3 cycles and lock out.I'm thinking maybe the board at this point


Check the exhausthose or pipe cand check for restrictions ... Air Conditioners

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific