Having problems with your Air Conditioners ?

I HAVE A RUUD SILHOUETTE II GAS FURNACE. THE UNIT COMES ON BUT THE BURNERS DON'T. IVE HAD THIS UNIT SINCE 1995. I DONT SEE A PILOT LIGHT HELP!!!


Answers :

Maybe you should check amazon, here: Amazon com ruud silhouette parts. Wish you best of luck. Karl
Your furnace probably has electronic ignition. Remove the panel that you have access to the burners, valve, electronic module. There should be a main power switch installed on the furnace. Turn it off. Set your t-stat on high. Turn on the power switch. After the unit purges (about 30 seconds) you should see an orange glow at the burner orifice. If not, Turn off the power & remove the heater and inspect it for cracks. (Or use an ohm meter) If open, replace it. Very common problem. If the igniter is of the sparking variety, you need to change the circuit board. Most of the furnaces, there is d diagnostic code chart and an LED on the board. Follow the chart.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I HAVE A RUUD SILHOUETTE II GAS FURNACE. THE UNIT COMES ON BUT THE BURNERS DON'T. IVE HAD THIS UNIT SINCE 1995. I DONT SEE A PILOT LIGHT HELP!!!


Maybe you should check amazon, here: Amazon com ruud silhouette parts. Wish you best of luck. Karl ... Ruud UBHC Air Conditioner

Hi , I have a Electronic pilot lighting system on my RUUD package unit. The pilot light flame keeps blowing out or is not working properly. I removed the panel to look and see what was wrong. I could not see any faults. The sparker worked just fine, the gas line tubing was fine no blockages( took it off to inspect it) every thing looked good. Worked fine for the last couple of weeks and now it will not ignite the pilot light to light the rest of the propane gas to heat the house. I tested the fl


Sounds like you have checked most things. A pilot will go out if it is dirty, if the gas valve is not holding or if the senser is dirty or bad. Remove the pilot and clean out the small orifice inside. Check all electrical connections, clean the senso ... Ruud UBHC Air Conditioner

I have a Rheem gas furnace, model # RGAA-100C and need help lighting the pilot. The instructions on the metal plate tell me to set the valve to off, then to pilot, push the valve down until lit, and then to on position. I do not see the off position, there is a pinhole size opening at the pilot position, is there where you light it? There is no other opening indicating where to light the pilot.


Hi, follow what I say and it is very easy. The knob that says off, on, and pilot, is where you need to start. You don't want to turn it off now, as its been off for awhile now. Turn the knob slowly pushing down on it until you fill it go down. The kn ... Air Conditioners

Brivis Wombat 92 heating unit - I am having trouble getting the pilot light to stay lit. The gas is on, the igniter is sparking and the pilot light ignites but when I gently release the red gas valve after 60 seconds as prescribed in instructions the pilot light flame extinguishes itself. Have tried venting the gas line to get rid of oxygen and this isn't helping. Any ideas?


Hear of a PRIMUS pricker?This is a very stiff but fine wire that was used to clear the jet on an old primus stove. The gas jet head at the pilot has a fine hole to allow gas to flow. When you hold it open with the button it allows for the ... Air Conditioners

Brand new unit have 3 ton inside and out but unit runs all day and will not hold temp i run my ac on 76 but as the day get hot the temp inside will not hold at 76 ARS says they dont know whats wrong but they installed the unit said i would have lower light bill but unit runs all day light bill 900 can someone help please with a solution


Call them back something is wrong if it is that new it is likely under charged. how big is your house square feet and what part of the country down south 400 square feet per ton if your house is more than 1250 square feet the unit is under sized ... Weather King 10AJA3601AH Air Conditioner

I have a dayton furnace with a honeywell vr8440p-2088 gas control. The ignition works fine but the problem is I am getting no gas it seems to light the pilot. I checked the orifices at the end of the pilot gas tube and could see light thru it so it was not blocked. Could this mean I would need to replace the gas valve completely? Any help appreciated [email protected]


Actually, after exhaustive troubleshooting and testing, all testing told me the gas valve was defective. I then replaced it. Problem was still there. I then took a shot for what it was worth and went down to purchase a new thermocouple to sense the p ... Honeywell Air Conditioners

We have a Fujitsu ASY-40UIM3 air conditioner here in Spain. We had to move the outdoor unit yesterday and since then we cannot get it to work. We are looking for error codes to help locate where the problem lies. The red light on start up goes off and we have a flashing green light (timer maybe?) that continues to flash at regular intervals. This outside unit was moved by a qualified engineer and the air-con worked perfectly up until the move. We cannot get heat or cold air.


There are two things that can cause this.\015\0121. Is the high voltage line energized. Is the power coming to the unit, make sure the disconnect is not tripped or manually shut off or pulled out and reversed. Check that the circuit breaker ... Air Conditioners

My unit dont turn on. it look like it is on, since the green light are on, but the unit dont cool neither make any noise


Hi, I looked up this unit, 5 to 8,000 b.t.u's about 1/2 of cooling, good unit. You say its not doing anything at all like maybe blowing just warm or room temperature air, or just a green light is on and its dead in the water? It didn't give me anythi ... Kenmore 75085 Air Conditioner

I have a 2 year old Mr slim system inside unit MSY-A24NA, outside MUY-A24NA. "2 lights mode" stays on when temp in room is actually 4 degrees LOWER than set temp. This is new, operation used to be 2 lights dropped to 1 when room temp was 2 degrees above set temp. Humidity control also seems poor. Had 2 service shops here, they both confirmed freon is OK and since unit is running were uninterested in pursing further. Any guidance you can give will be a help


Check that there is not an abnormal moisture source such\015\012as leaks into the building or its wall or ceiling cavities from any\015\012other source. Check to see if the condensate drain from the air\015\012conditioner is producing water. I ... Mitsubishi Mr. Slim MXZ30TN Air Conditioner

I have an Amana gas fired furnace which does not heat. It is a "90% Single-Stage" unit. I can see that the pilot light goes for a few seconds but nothing lights. It was new about 7 years ago


Bad gas valve or control board ... Amana Gas Furnace 90 AFUE 115,000 BTU Variable Speed

My parents had a frigidaire eletric heat pump installed 2 years ago. almost right away a soured water smell came out of the vents. service tech sprayed the coils and installed a black light. did not help. service tech said frigidaire did have this problem with some of its units. so the unit was replaced. new unit done fine for about 6 months. now the smell has came back mainly when the cooling is on. any suggestions. i dont believe it is the unit. they had a gas it pump before.


I feel that the gas lis leaking from a very minute hole which gets enlarged when the unit is cooling (it gets hot and enlarges). And it could be leaking from anywhere. A quick temporary remedy is to seal the possible leaking points with super glue or ... Frigidaire Air Conditioners

I have unit 48bne018301 mini split unit. For 2 summers now it is blowing a black substance almost like insulation all over, I have had the a/c man out 2 times and he has no idea. this substance is ruining everything it touches. there is no way to get tothe back of the unit under the coils, i dont know where to go. i am pretty upset since i feel something inside the unit is breaking down, and the reason i chose carrier is for the quality.please help. tel 252.261.5406. thank you


I have not heard of this in the Carrier mini splits, but sounds like you are on the right track, the back side of the indoor section is plastic and styrofoam, it could be breaking down. Did you check to see if the air filter is breaking down? \ ... Air Conditioners

I'm loosing the pilot & Burner flame after 5-7 minutes when I start the heater gas unit, the burner is working fine & controled by the thermostat, I' think the problem of loosing the pilot & burner flames after 5- 7 minutes is because some problem in the thermostat or the Solinoid gas valve, and I dont have the service manual of this type PW50-3 Hunter Natural Gas Heater, I' need your help


Faulty thermo couple replace it you can thank me later, do you have a carbon monoxide detector? ... Air Conditioners

I have an 1984 rudd 75,000btu forced hot air unit with pilot light, while cleaning unit an electrical connector broke off ! it looks like a blue plastic wing-nut, and It has 2 large black wires that go to the thermal cut off sensor. I dont know where it connects to???


The simple diagram for that specific problem it connected series to thermal cut off sensor.\015\012The two black wires, One came from a power supply line (it means an active power \015\012and the other one goes to the load motor) If you s ... Air Conditioners

My wintair AC unit ap08ck1fds is leaking water from the front - i dont know why this is happening, as i dont have the manual but the 'water full' light is not on. help me!


... Air Conditioners

Vulcan Comfort Control Central Heating unit - Our heater is situated outside and is ducted under the floor and operated by a remote control. When we activate the remote we can hear the unit starting up and have also witnessed the glow of the pilot light starting but the heater fails to start. I have had the technican three times and they cannot diagnose a problem - we have no heater at present - please help


... Air Conditioners

Amana air command 80 SSE started makeing humming sound id shut it off and wait a few minutes and it would work again been doing this for about a week and now its not working what so ever it was blowing cold air but when humming it wasnt blowing anything at all i checked to see if the fans were binding up but their spining freely any ideas i see a sensor light but i dont know how that works either. please help im melting thanks


Sounds as if the motor is heating up and shorting.Call a pro to find out for sure. ... Air Conditioners

Pilot is not trying to light on my carrier comfort 80 (electric pilot). I was getting a error code of 13 that has cleared but now have an error code of 33. I have tried turning the unit off by using the thermostat and the circut breaker. Any ideas? Thanks for your help in advance.


13 is a pressure switch error code. Check the venting for any blockage of snow, ice or debris. Make sure the air filter is clean. Check the condensate hose and drain and pump if you have one. Check the pressure switch to make sure there is no moistur ... Air Conditioners

I have a brevis buffalo central heating unit . It does not have a series number so I think it is an older one. I have not used one before. I am trying to find the pilot light to light but I don't know where to find it. Please help. Thanks G


Well there is a first time for everything. If you notice there is a pipe coming into the unit and a big usually grey box with a red or white knob on it. This is the Gas valve you have to turn the knob to "pilot" position and either hold the knob or t ... Air Conditioners

Hi, I have an ideal classic ff250 boiler which has stopped working. There is power going to the control unit but I can't see a pilot light, can't hear a fan and it is completely silent when trying I have followed the instructions to reignite. The overheat switch doesn't appear to have tripped, any suggestions?


... Air Conditioners

My Westpointe AC unit's "full light" keep flashing one even though I have emptied both tanks and made sure the water tank was aligned properly. No hoses are out of place as far as I can see; the display keeps saying P1 and won't allow me to access a different mode. Help?


... Air Conditioners

I am trying to light the pilot for a DESA ventless fireplace heater (Model #: VFB36C; Serial #: 7769262), but have been unable to since moving into the home a little over 2 years ago. Please help because I don't know what I'm doing.


... Desa International Air Conditioners

We have recently bought a house with Vulcan ducted gas heating (no pilot light). When the system comes on it produces plenty of heat so I don't think there is anything wrong with the unit itself. Frequently, however, it reaches the set temperature, turns off, and then will not come back on even if we press the on/off button. The only way we can get it back on is to cut power to the house and then press the on button. That would suggest that there may be some kind of program set, but since


By the things you said here it seams that is nothing wrong with the device itself but it has something to do with the thermostat ...The thermostat is the part that it supposed to shut it down when the temperature gets to the set value....and also it ... Air Conditioners

Ive tried to ignite the hot water gas cylinder and im not how do i know if its even working.? Cause we cant see the pilot light.?


It will all depend on what brand the hot water service isalthough you should be able to put the dial on pilot light setting which is normally light an * on the dial hold the dial down whilst pressing the clicker (piezo ignitor) normally ... Air Conditioners

My unit stopped blowing cold and started blowing hot.i turned off unit looked into furnace and saw pilot was still lit.i put out gas pilot and turned unit back on and it is blowing semi cool air (like fan)but not cool as it should.checked outside ac and it is running....munual says to turn unit off for 2 hrs and if it does not do right then it is compressor.we are currently in the 2 hr process. Any help would be helpful at this point.is there a reset switch or anything I could do to troubleshoo


100 degree temps/high humidity puts an extreme load on air conditioners - but if everything is right with the AC - 'overheating is not a big problem.\015\012\015\012The first thing I would check is whether or not the compressor is running ... Weather King 10AJA4201AH Air Conditioner

A detailed question is important to get you a relevant answers

  • Start your question with What, Why, How, When, etc. and end with a "?"
  • Be clear and specific