Indoor unit runs ok outdoor unit compressor and fan do not start

\015 Operation and timer light seem to be blinking a code..red and green lights blink together x2 then red lite blinks 5 times, then the cycle repeats? no condensing unit in heat or cool mode.\015

Answers :

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

I have a Sanyo Split System the indoor unit is a KHS0921 and the outdoor unit is a CH0921. When i first turn the indoor unit ON the fan will run for a few minutes and then go off. The outdoor unit never comes ON when there is a cll for cooling. The only way to get the fan to come ON again is to turn the breaker OFF and then back ON. The Operation loght will come ON when the fan is running but it will start flashing when the fan goes OFF. What should i look for?


... Sanyo Split System Air Conditioner

A mate has a fujitsu ast24rba-w, the outdoor unit runs but the indoor fan won't go. Found indoor board buggered so I replaced it, fan still no go. Got hold of a fan that I know works and still won't run!! Checked the start capacitor and that meters ok. It won't even run on fan only. From what I can see the fan should run, there is nothing left to replace. Any advice would be greatly appreciated!!!


... Fujitsu 24C1 Air Conditioner

Outdoor unit does not start. indoor unit fan does run.


By the sound of it the relay in the outdoor section is bad ... Air Conditioners

Hi. I recently installed 1.5 T, 3 * Split AC, LG. Whole day the AC works fine and no problem in cooling too. But once in 2 day outdoor unit start making thudding noise continously and does not stop for 4 to 5 second and after that indoor unit stops cooling and just fan runs. No cooling is done after that and room temperature keep increasing. The green LED of compressor in indoor unit is ON, compressor does not work. To achieve cooling again I have to switch off whole unit for like half an hour a


HelloSounds like the compressor is shuting down on high heat.There could be a couple reasons for this.1 Check that proper voltage is being supplied to compressor.2 Freon level may be low.This would be a service call.3 Ba ... LG Air Conditioners

AC Starts normally but after some time of coolinf compressor in outdoor unit trips. Compressor running light in indoor unit remains on and outdoor unit fan remains on. But no cooling. After a break of about one hour AC works again and problem repeats.


Probably overheating. Check the outdoor coil and see if it is stopped up with dust, grass etc. If so, disconnect power to the unit, and clean the condenser coil with water or air. Be careful not to bend the fins if you use a water sprayer. ... LG Air Conditioners

I have the MR36TQY3f outdoor unit with 2 MW09Y3FM units and 1 MW12Y3FM indoor units! The MW12.. works great and one of the MW9... works great! When I run the 2nd MW9 only (other MW9 & MW12 off)..... the outdoor unit compressor or fan does not come on! If I run all units then ... compressor kicks on runs great, fan runs... lines get cold on the 2 good units ... nothing on 3rd unit... then I turn 2 good units off....and it sounds like the compressor kicks off and the fan will continue to run reall


After looking at the manual for the units, I believe that the system is having trouble with the number of units that you have linked. Here is a portion of the manual about multi system operation>Also link to manual:http://www.fri ... Friedrich MR36TQY3F Split System Air Conditioner

I have carrier split unit the problem is the when switch it on indoor unit runs but when outdoor unit runs it make cool just for 5 mins and all unit indoor and outdoor go shutdown and green light start blinking and after 5 mins unit starts again after 5 mins again shutdown . any sugges please.


... Carrier 38CKC036 Air Conditioner

Indoor unit runs ok outdoor unit compressor and fan do not start


Hello rfrizzell, \015\012\015\012My unit is giving me the same alarm. If you have found the solution, please email me at [email protected] \015\ ... Friedrich MR18Y3F Split System Air Conditioner

Sanyo 18HS971 and CH1872 . Indoor unit fan will run, but outdoor unit won't start after power outage. Operation light flashes; Heat won't work.


Check pressur of gas have one protection overload gas ... Sanyo 18KHS72 Air Conditioner

Hi the outdoor unit turns on ( fan runs) the indoor unit does open, no heat or cold air blowing. In just fan mode the unit works fine etc speed setting ok. Its a sharp split type air model # ae-a244j outdoor,ay-a244j indoor unit what would be the problem, theres only two parts in the outside unit behind the side plate where the wires info is,small black box three wires and a round unit with wires. I hope this is help full cheers andrew


My gut says that this is evidence of a bad control board(circuit board). As usual, double check that your batteries are good in the thermostat. I have seen some weird things happen when the batteries are low. This one may be a job for your local con ... Sharp Air Conditioners

Compressor problem? My outdoor unit comes on with the fan blowing just fine. Then I hear a buzzing sound for about 2-3 seconds which I believe is the compressor trying to come on. (Incidentally, a couple of lights inside the house seem to dim at the same time that the buzzing sound occurs.) The buzzing sound reoccurs every couple minutes while the outdoor unit fan and the indoor blower both continue to run. I have shut down both the outdoor and indoor units for a couple hours and tried restarti


The buzzing is your compressor trying to start. It is going off on internal overload caused by heating up of the motor windings.If you have an amp meter you could check the amp draw of the comp against the locked rotor amps listed on the tag You cou ... Ruud UBHC Air Conditioner

Outdoor unit fan always runs even when indoor unit is off. I have disconnected all control wires from the headunit (at the outdoor end to rule out faulty signalling). The fan runs all the time, with just the supply wires connected. All connections to the unit are correct. Any ideas??


I have had this problem with a Fujitsu unit before. If the power is supplied to the outdoor unit first but unit is meant to have power supplied to indoor unit first, outdoor will only stop when power is cut off! In that case, you will have to run the ... Panasonic Air Conditioners

Fujitsu inverter air cond. just stopped working properly. Model outdoor AOT30PMAL, indoor unit AST30PBA-W. Code oper. red led flashes fast continously, green led (timer) repeats 13 slow flashes. After power reset, it takes rem. con. commands, however, while inside it looks normal, the fan in outdoor unit starts but compressor only makes attempts to start. After a number of series of 3-4 starting attempts, it stops and fan stops. Three way resistance test does not indicate open or short circuit c


Hello, my name is Heath and it will be my pleasure to assist you. Try using a hard start capacitor on the compressor. It sounds like the compressor is having a hard time starting and overamping the circuit. If you get a hard start capacitor it may he ... Inverter Air Conditioners

Fujitsu inverter air cond. Just stopped working properly. Model outdoor AOT30PMAL indoor unit AST30PBA-W. Code oper. Red led flashes fast continously green led (timer) repeats 13 slow flashes. After power reset it takes rem. Con. Commands however while inside it looks normal the fan in outdoor unit starts but compressor only makes attempts to start. After a number of series of 3-4 starting attempts it stops and fan stops. Three way resistance test does not indicate open or short circuit compress


It sounds like your inverter is at fault. You will need an inverter tester ( most good service techs will have one ) to prove that the output to the compressor is correct. If the inverter is okay then it will be the compressor at fault with a locatio ... Air Conditioners

LG split (3 indoor) LMU360CE system. The fans on the outdoor unit start and work. The compressors do not start-up. There is no error code on the indoor unit. On the outdoor unit the error code is continuous flashing of green LED #2. Any suggestions.


The LED #2 is only flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on). If you want to change it, note: this is not an easy job to do! You will need to remove the top panel, then remove the control paneland then the front ... LG LMU360CE/LMN120CE Air Conditioner

Fujitsu AST30LBAJ Indoor Unit & AOT30LMADL Outdoor unit . Outdoor unit not operating . Indoor unit fan is operational.rnThe Operation (Red ) Lamp flashes 5 times then stops for about secs then starts again, while the timer (green ) lamp flashs continuously.


... Fujitsu Air Conditioners

I have an LG mini split ac / heat pump system ( LAN096 ) that is only 4 months old was working great in all ways until suddenly it quit heating. I am sure it happened quickly because I was nearby when very warm air changed to cool ( unheated ) and hasn't heated since. When I shut it down and restart it the indoor fan runs right away, which is not normal and the outdoor unit will run for a minute or so then shut down and stay off. The indoor fan will continue to spin as though it is set in a 'fan


... LG Air Conditioners

My indoor unit on my heat pump will not shut off. The electric heat keeps running, and the fan keeps running. It only happens when it is really cold, like 25deg or below, above that and it functions fine. The outdoor unit shuts off, but the indoor stays running. I do HVAC work, but I have never seen a problem like this. I have switched the stat out, and its just so strange. I figured the relay may be stuck, but if I turn the stat off, it turns off shortly after which tells me it may not be the c


I would venture to say your stack relay is getting stuck. either that or you have a short in your low voltage wiring somewhere that is not always making contact....or it may be making contact through another median...like ice or frost. Remember ele ... Intertherm P3RA-036K Air Conditioner

SAME PROBLEMS 18k btu mini-split sys turn on blowing cold air for 3 mins, then turns warm for 3 mins then shuts down however the run lite blinks at 4 times intervals. outdoor unit fan alway runs at slow speed, even at start up. cleaning outdoor fan cleaning dont help. whats next? maybe the caps? thanks mike (us navy) at [email protected] in norfolk,va FAN MOVES FREELY, EVEN BY WIND BLOWN.


Glad to hear the issue is resolved.\015\012\015\012With regards. ... Air Conditioners

My Outdoor unit not starting ... but indoor is running fine


Check the capacitor. it might be defective, i would have a certified electrician or hvac tech trouble shoot it..if you never had worked on a/c b4...........you could probably ruin it more....................if you dont know what your doing...... ... Samsung AS18A6RB Air Conditioner

I have a Sanyo mdl.# CG1411, gas heater- A/C unit that starts on heat, compressor runs, combustion fan runs, fires up, sends heat to indoor unit. Runs for short time [1-2min.] then stops. No indicater lights come on. Any ideas ? Rick


... Sanyo Air Conditioners

Indoor unit freezes up, turn the mode button to the fan only to thaw out the indoor unit but the outdoor unit runs, What should I look for?


If the outdoor unit is not shutting off, your indoor coil will freeze up when the thermostat "satisfies" and shuts off the blower. The most common cause of a non-stop outdoor unit is the contactor. This part is usually black or brown in color. The li ... Air Conditioners

Lg Neo plasma inverter split model s18ahn isn't heating or cooling properly. When in heating mode air con will go into defrost/preheat mode for 5 minutes and then air con will blow out air for 5 seconds and then go back into defrost/preheat mode. When in cooling mode indoor fan will pump out air but will not get cold. In both heating and cooling modes the outdoor unit will not start up and the outdoor fan will not spin. I have just replaced the main pcb board and that hasnt made a difference. Bo


... Air Conditioners

My outdoor air unit runs but the indoor unit is just buzzing and the fan is not running. Any idea whats wrong


Replace the capacitor to the in door fan motor. If it still does not run,you will have to replace the fan motor also. ... Carrier Air Conditioners

I have a Maytag S3BA-024KA Split System Air Conditioner. I have power to the system indoors and outdoors. The outdoor unit is clean and the Contactor is also clean with power going into it. The compressor is not running. I can push the contactors and the compressor fan will run but it will not operate by itself? Not sure what to do now.


... Air Conditioners