Forced air heater lites but blower run a few minutes and shuts down. Service board blinks seven times. don't have manual


Answers :

Watch The Unit's Ignition Process See If The Unit Is Getting Fire Most Likely It Needs A New Thermostat. The Thermostat If Bad Will Cause The Unit To Turn On Ignite But Will Not Detect The Heat From The Flame And Then Shut Off The Gas To Protect The Home From Carbon Dioxide.
If The Unit Fails To Light At All Check The Igniter.
I Hope This Helps,
Sincerely,
Michael Scott
Hi!
\015\012
\015\012Please tell me the make and model number to provide you the solution.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Forced air heater lites but blower run a few minutes and shuts down. Service board blinks seven times. don't have manual


Watch The Unit's Ignition Process See If The Unit Is Getting Fire Most Likely It Needs A New Thermostat. The Thermostat If Bad Will Cause The Unit To Turn On Ignite But Will Not Detect The Heat From The Flame And Then Shut Off The Gas To Protect The ... Air Conditioners

Board in furnace is blinking seven times and only runs for a few secondsand then shuts off


Hi, remove the panel where the led is blinking, and you will find a chart glued to the panel, or there somewhere. It will tell you according to how many times it blinks what is going on. It may say that 7 times is a reset on a roll out switch you can ... Air Conditioners

I went on a job that has an intertherm G5RC080C-16- they are wanting the A/C to work. the circuit board has an error code light blinks three times - there is no troubleshooting guide or manual on site I need the manual


... Intertherm Air Conditioners

Freeze up new lennox x16 (2 yearsold) will not hold charge,leakdown over time capapilleries are frozen. at start up.sensor on condenser shows led light blinks 4 times. (manual states rotor problem, 1.voltage at line 2.overcharged 3.low voltage)checked line voltage,ok. checked for leaks none. i install for a contractor but have limited service exp. 410a is expensive. can u advise


It is possible that you have a leak at the charging port. this is often missed when the technician removes his gauges and does not make sure that the valve is seating properly. ... Air Conditioners

My hitachi Rak-35nh4 has a problem. When i turn it on to heat, the timer light blinks four times, and keps blinking like this. I know that is a failure code, but without the service repair manual can't figure it out. thanks in advance.


... Hitachi Air Conditioners

My Carrier 58WAV136 forced air heater's problem is as follows - Thermostat works fine, when desired temp is reached, the fan motor (blower) kicks on. Sometimes it stays blowing for a couple of seconds, sometimes a minute. Often, the electric heating element will heat up and the gas furnace will light. But, the system will shut itself off within a few seconds and will try all over again. The LED sensor will blink 3 times fast, then one time. I do not have the manual to look this info up. Thanks f


There should be a code list inside the furnace panel access door. Find it and see what code 41 says, as I can't remember right off hand. Some of the possible causes could be air in gas line or low gas pressure. Could have blocked vent especialy if ve ... Carrier Air Conditioners

AC complaint frm the dayofprcase my conditner is not working proprly no of times i hahe givn complaint to local service sstatiiiiiiiiiii but they never visited to solve it . problem is internal fan dont starts it needs manual sport by insertng pen etc & movng it after that it starts runing . mechanic says its compresser is week


You need tor replace the internal fan, it may be stuck up or weak running capacitor for internal fan. ... LG LSC121PMA Split System Air Conditioner

Everything is operating fine but the furnace wont fire. you can hear the gas kick in for like 3 seconds and kick back off when it doesn't ignite. then after about 5 tries it shuts down and the red light on the control board in-side blinks 4 times.


COULD POSSIBLY BE A BAD IGNIGHTER.I DON'T KNOW THIS SYTEM BUT THE SAFTY PROTOCALS ARE WORKING.THE THERMOCOUPLE(IT DETECTS HEAT)IS TELLING THE BOARD IT HAS NO IGNITION,THEREFORE KEEPING YOU FROM BLOWING YOUR HOUSE UP.IF IGNITION HAS'NT HAPPENED WITHIN ... Frigidaire Air Conditioners

SAME PROBLEMS 18k btu mini-split sys turn on blowing cold air for 3 mins, then turns warm for 3 mins then shuts down however the run lite blinks at 4 times intervals. outdoor unit fan alway runs at slow speed, even at start up. cleaning outdoor fan cleaning dont help. whats next? maybe the caps? thanks mike (us navy) at [email protected] in norfolk,va FAN MOVES FREELY, EVEN BY WIND BLOWN.


Glad to hear the issue is resolved.\015\012\015\012With regards. ... Air Conditioners

I have a Sta Rite Max E Therm pool heater and when I start the unit, the fan kicks on but the heater never does. After 45 seconds or so, I get a " Service Heater" light. The circuit board had leds for limit switch, pressure switch, air sensors, etc, but none are lit. The ignition contol module has a blinking red led which the manual says is a "ignition lockout" issue. What is an ignition lockout? Do I need to replace the HSI Ignitor? Or could it be something other than ignitor? Thanks


Hi,How many times that light is blinking?Is it 3 times sequence?Let me know,so that we could proceed.Thanks!! ... Air Conditioners

I have a GMP100 gas furnace. I need the diagnostics table that provides the meaning of the status light states. I get flame for 20 seconds and then the gas is shut off and LED on control board blinks 3 times. The flame sensor looks clean. I wired the flame sensor lead to ground as a quick test but then the gas goes out in 6-7 seconds. Any thoughts?


Hi!!! you just answer your question.change your flame sensor cleaning it wont work..\015\012\015\012\015\012 ... Air Conditioners

HAVE A COLEMAN MODEL DRHSO601CB --- THE UNIT WILL RUN FINE FOR SEVERAL HOURS WITH GOOD COOLING AND THEN PERIODICALLY THE TROUBLE LIGHT WILL COME ON THE THERMOSTAT AND THE UNIT HAS SHUT DOWN. TO RESTART - YOU MOVE THE THERMOSTAT TO OFF WAIT 5 MINUTES OR SO AND PUT IT BACK ON COOL -- IT WILL RESTART ALMOST EVERY TIME AND RUN FOR SEVERAL HOURS. IN THE PAST IN THE PAST I REPLACED THE DEFROST CONTROL BOARD BUT WHEN I DID THAT THIS TIME IT STILL SHUTS DOWN - WHAT OTHER PROBLEMS ARE YOU AWARE OF ON TH


You may have a low pressure or high pressure switch tripping out the board as well. You might try cleaning both the indoor (evaporator) coil and the outdoor (condensing) coil. Be sure to turn off the power source before servicing this. ... Coleman Air Conditioners

After experiencing a power outage in our home, our LG Heater Unit stopped working, there is a blinking code displyed CH 24. I've shut off power to the unit several times, units appears to reset for 10 minutes then the shuts down and the blinking code appears again. I've tried letting the power of all night the issue is still present. Any suggestions. Thanks


... LG Air Conditioners

I have a armstrong compak 10 gas pack and I replaced the circuit board and the lcd light is blinking 4 times then it stops and blinks 4 times again can you please tell me what this means.


Hi, Silver Wings\015\012\015\012Although there are a number of things that can cause this scenario (a "lockout"), it is usually related to an air flow problem (dirty filter, blower wheel, indoor coil, duct problem, dampers closed, return ... Air Conditioners

Recently purchased a second hand Carrier Split A/c -Model 42KPC019303 - 18000 BTU. The unit would work for awhile then shut off - fan included - and the green light would blink 5 times at intervals - but the unit did not start back. The sensor was changed and the unit started functioning normal for awhile - and then the problem resumed. Only difference is that this time the light blinks for about 10 mins and then the unit kicks back on. I want to know if this is a normal function, and if it ca


I have the same problem. What sensor did you change? Did you eventually solve the problem? ... Air Conditioners

Have a Multi Split Indoor unit ASU9RD - 2 units and Outdoor unit AOU18RD. Operation blinking GREEN; Timer blinking RED. Remotes not responding, Turn off units at circuit breaker, units still blinking the same. Both indoor units went down at same time. Had unit serviced in June 2010. What are the blinking lights telling us (Code)?


Hi.Here error codes:ERROR CONTENTS ... Fujitsu 12C1 Air Conditioner

Model coleman mach 8333c8714 serie 8000 my a/c start for 2-3 minutes and than the a/c shut down but the fan still working!! after a few minutes , it want to start again but dont seem to be able to. you can ear the clicker goes off and the compressor dont want to start.Does that all the time. maybe the compressor?? dont know ?? can i get some advise or tips please .


\015\012COLEMAN R.V. AIR CONDITIONER SERVICE AND REPAIR QUESTIONS\015\012COLEMAN R.V. PRODUCTS\015\012GO TO rvcomfort.com\015\012Click on RVP (RV PRODUCTS) \015\012Click on type of AC, if you can’t find the informa ... Coleman Mach III Air Conditioner

After a very cold frosty night my unit stopped working. The 'operation' light was blinking a series fo 5 blinks and the 'timer' light was constantly blinking. My service man has now said both the PUMP and PRINTED CIRCUIT BOARD need replacing! OUCH! $2,500 NZD! This unit is only 6 years old. I have been told that I might get away with just replacing the PCB but it's not recomended practice. Fujitsu will not help and it is just not good enough. This unit is only used for heating so only runs for 5


Try switching off and on circuit breaker it might solve the problem ... Air Conditioners

Hi, My parents have an Armstrong Furnace Ultra V Tech 80 Model #G1N80AR100014B-2A. I am a building engineer with service exp. and have also had a service tech. out. After much research here is my dilema. Furnace only at times (especially during longer off cycles) will fire up & then shut off for 3 or 4 tries and then will start & run great. The service tech installed a new smart valve to no avail. I cleaned the flame sensor with wool and double checked all wiring. There was a loose connecti


You can check the flame sensor with a microamp meter to see if the flame sensor is good unhook the wire going to the flame sensor put one wire lead of microamp meter in the wire and connect the other wire from the microamp meter to the flame sensor t ... Air Conditioners

Model G51MP-48C-110-6; I've downloaded a manual and troubleshooting is usually fun for me, but ;( this time. It ran fine last year, not this fall. Have alternating Green & Red code lights (FAST); I have checked thermostat; (and completely shut off, restarted power and gas several times too; each time goes back to "normal' simultaneous, slow flash until I turn the thermostat up to call for heat; then FAST, alt. Flash again), good ~25vac signal calling for heat. Have drained condensate from trap (


Apply power to the inducer motor, or check the voltage to it first.a relay or circuit board will control its operation, if the inducers not running, the pressure switch wont close and no operation . ... Air Conditioners

Ruud Silhouette II OK LED blinks 4 times then shuts off


... Air Conditioners

Not running; msg18 mini split , defrost board blinking 5 times.


Check freon to low or to high. must be charged liquid 410 tank upside down. ... Air Conditioners

I have a 10 year old Mitsubishi mxz 325v Multi unit airconditioner that is on the blink. The local service company has been trying to fix it since August and even with the assistance ? of Mitsubishi Tech Support they still are not confident they know what the problem is. So far the following parts have been replaced after dicussion and even an attendance by a Mitsubishi Technician from Tech Support. Main Board and Noise Filter Outdoor Main Board Relay Printed Circuit and Power Monitor Bo


Sadly this is a poor service without a proper sincere logical advice. To spend $2500 for a 10 year old set is surely too bad , as they have finally almost constructed a new set except the body/condensers.\015\012In the first place ... Mitsubishi Air Conditioners

I have a remote heat n glo fireplace - brand new that lights up and runs for about 10 minutes and then shuts down for no reason. We have the remote set to 'manual' so that it will not automatically do anything (i.e. We do not want it to shut off at a certain temperature or after a certain time). Help!


... Air Conditioners

I purchased and LG Model# LP1010SNR on 8-3-10 at Home Depot. It was a floor model and did not come with an owners manual. It has a digital display screen. It is intended to run for several hours at a time as it is used for a greenhouse. When I went to check the AC unit. The display screen displayed (P2) and blinking. The AC unit will not come on. It has power but, will not come on. I turned to AC of and the reset button, etc., Again the unit comes on but will not operate. It beeps 5 times and st


What happens on this unit is it will suddenly stop followed by a series of chimes. You can reset the unit, but it will end with the same set of chimes. My unit display had a P2 code. As mentioned above, I drained the water (small amount actually) ... LG Air Conditioners