Bryant furnance clicking, won't fire

\015 I had a furnace guy here twice. Each time he replaced parts, each time the furnace stopped working shortly after he left. The blower motor starts, but the furnace won't fire. A friend tried calling Bryant, but they wouldn't say anything until they had the model number. Ihave searched hi and low on the unit, and no number. Suggestions? Parts replaced: Inducer motor, inducer control board, main control board, pilot and flame sensor.\015

Answers :

Try checking the pressure sensing switch,it has a tube that should run somewhere close to the inducer fan.sometimes this hose fills with liquids,and makes the units act funny.I don't know if you have a condensing unit or what.the furnace wont try to light if it cant tell the inducer motor is running.any induced draft unit will work this way.you can also do a temp. bypass of the pressure switch to make sure the contacts on it are closing just be sure your inducer fan is running,and you cant leave it like that its just a test.that is a safety feature you really need.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Bryant furnance clicking, won't fire


Try checking the pressure sensing switch,it has a tube that should run somewhere close to the inducer fan.sometimes this hose fills with liquids,and makes the units act funny.I don't know if you have a condensing unit or what.the furnace wont try to ... Air Conditioners

Bryant furnace I have a Bryant forced air furnance series 3C-G serial # 44Y 368450 model # 125-394U upflow and model # 125-394C The furnance or central air is not coming on to run. The breaker has not been tripped the pilot light is lit and when I turn the thermostat I here it click but the furnance or central air does not come on to run. Can you help me with a solution to to get it running?


... Air Conditioners

Bryant furnace I have a Bryant furnance and central air. series 3C-G serial # 44Y 368450 model # 125-394U upflow and model # 125394C down flow. My problem is it is not coming on. the breaker is not tripped, the pilot light is lit, when I turn the thermostat i hear it click but the furnance or central air does not come on to run. Can you help me get it working?


... Air Conditioners

I have glow worm micron 40ff and wont fire up fan spins ,air pressure swithch clicks but no fire ? leds flash green on reset? any ideas tryed pcb board but same fault.


... Air Conditioners

My central heating is trying to start but wont fire up. It begins to run then clicks like ignition is trying then stops It is Omega ehe100


Hi,Here is a tip that will help you try to figure out why your furnace is not working.Basic Furnace or Heatin ... Air Conditioners

Hi, I have a ferroli falcon II combi boiler and have a problem with the hot water and heating. The hot water keeps turning cold for a few seconds and the boiler keeps firing up and clicking off all the time you have the hot water tap open. Also the heating gets to temp but then keeps clicking off for 2-3 seconds then fires up again. Have already changed sensors. Can you advise any further Cheers. Reagrds Phill


... Air Conditioners

Boiler wont fire up. changed old relay to new L8148j aquastat relay. boiler ran fine all day. now boiler wont fire again.


... Air Conditioners

Switch heating on, hear a click that we normally hear then boiler fires up. Then goes off after about 30 seconds. Then won't come back on, though we still hear the click. Wait a while before trying again and it fires up and goes off. Won't stay on. It is an Ideal boiler, not a combi. We are replacing soon but could do with it to keep going for a few weeks more. Any ideas please?


Could be a number of things, it could be cycling on the high limit switch, (lack of water flow, or pump) this would be my guess if you are not resetting power and the unit is trying to restart. It also could be the flame sensor not proving ignition. ... Ruud UBHC Air Conditioner

I have a ns 2800 vented cabin heater in my hymer motorhome, it has recently failed to fire up. Following the instructions on start up, heat switch to on, power lamp lights up to activate igniter, starts to click click. After a few minutes clicking stops and it starts to blow, begins clicking again,then blow, followed by red light on flame. Closer inspection thro inspection window, shows flame not lit. Any ideas please


... Toyotomi Air Conditioners

We have a gas fired Ferroli, Pegasus 2 NT Boiler with a Honeywell 4400c Controlling valve that is not allowing the boiler to fire up. We have pilot light okay and colloer is clicking as if it is trying to fire up but nothing is happening. Can you advise?


... Air Conditioners

Dru concerto fire pilot lights and stays on light fire ok for a minute or two clicks fire and pilot goes out


... Air Conditioners

My blackberry didnt get wet exactly maybe the steam got into it so i took the battery out and put the blow dryer on it, it was working okay but then it started short circeting on me, it wud stop then it would start again, my track button wont click and it's texting and calling everyone in my phonebook, i dont even have to click on anything as soon as the trackball goes over an icon it automatically clicks on the icon and starts doing its own thing, i just put it in a bag of dried rice will it fi


HI, the chances of the bag of rice doing anything is pretty slim, wht you should have done is left the battery out for a day or two to ensure the circuit board had dried out properly, then their may have been some slim chance of it working, now thats ... Air Conditioners

I am trouble shooting a Bryant Hi-bred system that uses an air cooled heat pump with high efficiency gas furnace for backup and low ambient operation. How does the system decide whether to use the air cooled heat pump or the gas fired high efficiency furnace. It appears to be outdoor air temperature related, but I can't find the setpoint for it. The main zone Bryant thermostat appears to control the system, but it doesn't always bring the backup heat if the heat pump doesn't function.


If you are using honeywell vision pro 8000 t-stat you need an outdoor sensor program on t-stat would have to look up ... Bryant Air Conditioners

Vulcan qasar gas wall heater. Pilot alight, but will not "fire up". Have performed the reset procedures as detailed on the heater, including complete shut down and relight of pilot (after audible click), but still no fire up.


If your hearter is an electronic model the solenoid has almost certainly failed. ... Air Conditioners

I have a bryant 661bj036g heat pump, new in 1995. It works fine except there is an intermittent clicking that occurs on both heating and cooling, the click is accompanyed with a flash on the control box (blue lite-energ..Heat). I repeat it works fine but I don't think this is right.


... Air Conditioners

L have an alvima gas fire calor gas and the knob on the top does not click when you light the fire can you help thank you


... Air Conditioners

The heat comes on but the fan does not it clicks but wont run i can put it on fan and not auto it clicks but you have to work wit it to get it to run then it runs fine untill you put it back to auto and it reaches temp


Failed temperature controler. Contact manufacture for replacement part. ... Intertherm P3RC-030K Air Conditioner

Raypak propane boiler does not fire up, can hear igniter clicking but does not fire up pilot light.


... Air Conditioners

Ive fitted a thermocouple to my kinder oasis he gas fire and it still wont light. there is gas but it wont spark. what can i do?


... Air Conditioners

Ive got a Alpha combi boiler and it just wont fire up and the prussure needle is below the green mark so ive put that flexey pipe on the two pipes under the boiler to bring the pressure needle back up to were its supposed to be but the needle wont rise so ive got no heating or hot water


There is 2 taps on the filling loop ... Air Conditioners

I have american standard freedom 90 gas furnace that continuously blows cold air and doesn't shut off until we unplug it. we have changed the ignitor several times to no avail. it still will fire up in the beginning, then click off and when it clicks back on, it blows cold air and continues blowing until i unplug it. very cold.


The igniter must have failed. replace the igniter. ... American Standard Air Conditioners

I have a Bryant package unit that clicks when I put in the fuses. It is not a loud click that you would expect with a gas valve however. The light on the furnace control is flashing 6 times.


The codes are generally printed on the back of the bottom cover on residential units (blower section). On light commercial, the cover for the controls section (follow the line voltage and thermostat wires.\015\012 Off the cuff, if it has a sparker, t ... Air Conditioners

My oil fired boiler wont stay fired i cleaned it out it will run for about 30seconds then shut


This can be a result of several things. The most common problem is the photo sensor. If there is a flame, and the photo sensor can't detect it - the furnace will shut down. If the furnace has run dirty and sooty - there's probably black soot cover ... Air Conditioners

Intertherm MGHA-075BFC-01 gas fired furnace - air runs but heat will not fire. Pilot light is lit, no click tho from thermostat when increasing temp. What or where is the most likely culprit? Thanks, KevinH


Probably the limit switch is open. ... Air Conditioners

My Bryant Quantum Plus with Puron Air Conditioner is two years old at max used for one season. The fan spins and then I hear a click and it shuts down for a minute clicks back on the fan spins for a minute and shuts back down this cycle will repeat itself until I turn the unit off. The house does not get cool at all. This happen if I put the thermostat on auto or fan. Any suggestions?


The outside unit is cycleing on a low pressure switch you need to call for service you have a leak and the system needs to be recharged afte the leak has been fixed ... Air Conditioners