Fan motor on furnace continues running after cycle is completed.

\015 Heating cycle completes and fan continues blowing colder air until I manually unplug fan unit. Could this be a fan relay. On system front we have name RPJ Exchanger. Model GUH100A016CIN serial number L923420280.\015

Answers :

Your fan time delay relay has failed.
\015\012Replace it.

Repair Help & Product Troubleshooting for Air Conditioners
You need a second opinion or clarification ? ask it in the comment box OR you can Ask Your Own Question

Tips for a great answer:

  • Please provide as much detail as possible as this will allow our members to better understand and respond to your Comment
  • If you need clarification, ask it in the comment box
  • It's 100% free, no registration required

Suggested Questions/Answers :

It is recommended you read all this kind of situations

Fan motor on furnace continues running after cycle is completed.


Your fan time delay relay has failed.\015\012Replace it. ... Carrier XHB123D X/Y Series Heat/Cool Air Conditioner

FAN MOTOR CONTINUES RUNNING AFTER HEATING CYCLE IS COMPLETED BLOW


Check the thermostat. Make sure it is set for AUTO fan not ON fan. If that is OK replace the fan relay. ... Carrier XHB123D X/Y Series Heat/Cool Air Conditioner

I HAVE A 2000 MONTANA 3252 WITH A DOMETRIC LP FURNACE AND ROOF AC WITH A DUO THERM THERMOSTAT...MY PROBLEM IS WITH THE FURNACE...IT WILL FIRE UP JUST FINE BUT ON OCCACION IT WILL SHUT OFF WHILE THE FAN CONTINUES TO RUN, AND NOT CYCLE BACK ON...BUT THE FAN STILL CONTINUES TO RUN.


... Dometic Rooftop RV Air Conditioner

The Coleman Mach thermostat in my 5th wheel blows its 2 A fuse a couple of times today and am trying to figure out what is causing this. Please help. I am unable to get the furnace to run even with a good fuse in the thermoatat. When I bypass the thermostat to run the Atwood furnace (red tied to white wire). THe furnace blower comes on and the burner sounds it lights for 5 seconds and then goes out. 15-20 seconds later it reignites and goes out and continues to cycle -- the blower motor


Hi\015\012\015\012Its blowing fuses because of short circuit inside the coleman mach or due to two wires being shorted with each other. You'll need to open up your thermostat system to look for the short circuit and also shorted wires.Ple ... Air Conditioners

Our furnace went into lock out and so I cycled powere and it reset it started working again but not correctly. The inducer motor wis coming on for a few minutes then the hot ignition comes on and the gas lights. then the blower comes on then shortly after the gas cycles off and then a few minutes later it cycles back on and usually the fan alternates on with the gas. I started checking the safety switches that go to hot ignition control. (24V) Once everything was running the 24V would drop to ze


Boy it sounds like a high limit opening up and shutting off the gas valve. It won't shut off the blower because it wants to cool off thge furnace. Check for any restriction in the air delivery system, filter, registers. Check for blockage of the exha ... Air Conditioners

I have a Arcoaire Gas Furnace (Model# GNJ100N12A1), that will not fire up. It has a White Rogers Digital Stat. First the Stat seems to be faulty, since it reads 70plus in a house that has a temp of 30 or below. I can adjust the Stat and the blower motor will run. The rollouts (3) were reset; the inducer fan would run; then the unit would cycle and shut off. Now the inducer won't run. The ignitor is good, but would never glow. A friend tested the current coming from the Stat, and found 24


Sounds like a faulty board. shut the power to the furnace off for a minute then turn it back on. Make a call for heat at the thermostat. The inducer should start and close contacts on a pressure switch . Once pressure switch closes the hot surface ig ... Air Conditioners

Sometimes, when the inside blower shuts down, the outside compressor and fan motor continue to run for some time. Other times, when the inside fan motor is running, the outside fan and compressor motors are not ... if I press the outside reset button, it starts up When both inside fan motor and outside fan and compressor motors are running, it works fine ... warm air blows out of registers. Other than that problem, both units work great!


Sounds like you have a dirty condenser. You are going to need to disconnect the power at the outside unit on the wall by pulling the fuse block out. Take a good look at the louvered covers that are attached to the outside of the unit. Remove the scr ... Ruud UAKA060 Air Conditioner

Firing up and runnig for 2 minutes ,burners shutdown, both fans still running for 1 and a half minutes ,furnace burners fires back up , and runs for other minute and ahalf and complete the cycle .


... Air Conditioners

Carrier Tech 2000 Model 38TUD24300 the D maybe an O serial # 2592E22496 The AC will run for 1/2 hour or so then furnace motor will continue to run unit outside will not cycle on. I think it maybe the capacitor or a limit switch???


... Air Conditioners

My Goodman furnace # GMPNO6O-4 is turning on fine but while running through it's cycle it will shut down for 3 to 5 seconds and continue with it's cycle, I have replaced all moving parts on it in the last yr and a half. The collector box and exhuast motor where lust replaced and the overheat sensor is fine but the collector box is very hot to the touch aswell. checked for cracks in the heat exchanger and checked seals to see if they where bad. I have great drainage from unit so it is not clogged


Yeah that auto cycling might be due to a contaminated flame sensor. Check out this vid dude: ... Air Conditioners

Have a Payne pg8uaa furnace. Furnace only works when I run a jumper between R and W. Replace wiring to furnace. I suspect that the outside blower motor is the problem. When furnace is running the blower motor has a humming sound but does not blow air. At this point, I would like to know how you would diagnose a Tjernlund HSUL-J blower motor. Should the motor itself be replaced or should the fan prover be replaced?


You would have to test the motor as well as the capacitor on the motor capacitor goes for alot less then the motor though.here is the pdf manual on your blower h ... Air Conditioners

After a power outage and surge, I tried to run the carrier high efficiency furnace "FAN" only to circulate air in the warm house. when I stated the blower, it ran on slower spped than normally.usually cycles between high and balst furnace high....now its running slow.I tried the heat cycle and the blower speeded up a minor amount over just with the fan circulating....is there an internal circuit breaker that could've beed bitten with the surge??


Try replacing the fan capacitor some time power surges zap them.its usually a 5uf or 10uf @ 370vac if you change it and runs fine it was the capacitor if not blower fans keeps slow verify that full voltage is getting to it ex 230 volts or ... Air Conditioners

I am an Electrician trying to fix a coleman blend air deluxe I already replaced motor and upper control board that was obviously bad, I am getting proper control voltage to the lower board and 34 volts dc leaving the lower control board to the upper board on the black and red wires. I have confirmed the voltage is entering the upper board but the problem continues to be that the roof vent fan will run constantly instead of cycling every 4 hours.I am wonder the upper control board was bad out


It sounds like a bad board or a slightly different version,perhaps another model or something.You also sound like the most knowledgable person I have dealt with on this site in my brief 3 months so this should be fairly quick and easy on both part's ... Coleman Air Conditioners

I have a Lennox Merit series residential AC unit, my furnace engages and blows air but the outside component WILL NOT turn engage! Furnance fans runs continuously with cycle as if outside unit was working but the outside unit will not engage.


... Air Conditioners

Honeywell thermostat; Lennox elite series furnace thermostat reaches and exceeds temperature setting but frunace continues to run, remove trermostat from wall and furnace continues to run. Not just fan- entire system, I have removed both panels from the furnaced itself and as soon as power is supplied the furnace immediately lights (gas) and begins to heat house. Current inside temperature is 77; set to heat to 70.


When the furnace exceeds the temperature set by the thermostat, this could be indicative of several issues. The thermostat mounted crooked. When a thermostat isn't level on the wall, it can affect the automatic on/off function. To fix this pro ... Air Conditioners

Thremostat reaches and exceeds temperature setting but frunace continues to run, remove trermostat from wall and furnace continues to run. Not just fan- entire system, I have removed both panels from the furnaced itself and as soon as power is supplied the furnace immediately lights (gas) and begins to heat house. Current inside temperature is 77; set to heat to 70.


... Air Conditioners

Lennox Conservator III G16, Furnace, Burners stay lite for 90 seconds; no blower; but exhaust fan runs continuous. If I use a jumper from the white heat wire (including white heat wire) to the green blower wire terminal (removed the green thermostat wire) the blower fan runs (non-stop) & igniter & burners restart every 10 mins. when I remove the jumper (& wire to specs from the thermostat to the furnace) igniter & burners kick on for 90 seconds then nothing on the unit works except the exhaust f


... Air Conditioners

I have an ultra sx90 unit. the compressor kicks on just fine and runs for about 10 seconds then the fan motor goes to kick in and it starts then stops about 3 to 4 times before it finally stas on. then when compressor stops the fan motor continues to run for about 20 sec then kicks off and on 4 or 5 times.


Hi,\015\012That fan is running off of either a pressure or temperature sensor....could be either one...\015\012bottom line is that this switch is going bad and the "deadband" is too small causing the unit to cycle too often...\015\0 ... Air Conditioners

My Rheem Corsaire furnace is short-cycling. It ignites, the burners stay lit the fans run for a while then the burner shuts off, the fans run until the cooling oft temp is reached then shut off. Right away the furnace starts right back up. It does this until it reaches the temp the thermostat is calling for. I had a problem with the flame sensor last year, but then the burner would light and then go right out.


Try blowing air thru the pilot tube. You may have a spider web in the burner tube. ... Air Conditioners

Hi, I have Lennox gas furnace Model G12Q3E-82 (about 30 yrs. old). When running the A/C, I noticed there was water leaking or dampness around the bottom of the furnace. I removed the hose from the drain spout on the evaporator and noticed it was plugged and unplugged it to drain some water out of it. I also removed some water that accumulated in the bottom of the frame that wraps around the blower motor and fan wheel. I have a problem where now the blower motor runs for about 1 to 2 minutes then


Hi Todd, you did the right thing by checking the uf on the run capacitor and it is with in range , the reading is good. What is happening is with the condensation building in the pan, the blower motor has picked up some water and burned the windings. ... Air Conditioners

The fan inside the furnace cycles on and off several times before finally turning on completely.


... Ruud Rheem Control Circuit Board 62-25338-01 1097-200-i

I have a 30 year old fedders furnace and the furnace fan runs continuously. I was told by several people that the problem was probably a defective fan limit switch. But because its an older furnace with a service boad or schematics we don't know where the fan limit switch is located. Can you tell me where its located or tell me how to obtain a manual or schematics.


Hi,The switch will be the silver/gray box just above the burner in the supply plenum...There really is nothing you can do to fix that if it is bad... the switch runs off of a bimetal spring and that has just plum worn out...Th ... Air Conditioners

I bought a Dayton 5K907G 1/4 HP continuous duty, single phase motor from Acklands Grainger. I installed the motor in a downdraft sanding table with a fan blade on it. I had it wired by an electrician for counter clockwise rotation. If the motor has any load on it it runs for 2 seconds and then quits for 10 seconds and back on for 2 seconds. I used a heavy duty extension cord and the motor is grounded. I am wondering if there is an adjustment on the motor for maximum load. The fan blade is rated


Is the motor a convertible motor that you can wire either 240 or 120 v/ac it sounds like it may be wired for the wrong voltage. let me know thanks Peyton ... Air Conditioners

Indoor fan motor continue to run even if the thermostat is in auto position with the cool and heat switch in the off position. The furnance don't have a fan on and off switch in the furnance like most. The only way to turn the fan motor off is to turn off thr high power switch. I change indoor fan relay but the problem still exist.


Try this, disconnect the fanwire (green) on the furnace, if it shuts off then the hot wire from the thermostat is touching the green wire or bad thermostat. Thank-you-very-much! ... Intertherm Air Conditioners

We have anintertherm M3RL series downflow condensing furnace in our park model home. When heat is required, the furnace cycles (seems normal) and then as soon as the cycle is complete it imediately cycles again and again until the desired temperature is reached. Each cycle is only a few minutes. Seems to me that it should run until the temperature has reached the desired setting on the thermostat.


Sounds like the anticipator on the thermostat is faulty.\015\012Try replacing the thermostat. ... Intertherm Air Conditioners